Air System Design Load Summary for CENTREPOINT

Project Name: 21014 BARKA MALL R4 08/01/2017


Prepared by: Amjaad 07:55AM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.2 C / 29.8 C HEATING OA DB / WB 12.0 C / 10.0 C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 919 m 9027 - 919 m 3166 -
Roof Transmission 3340 m 43414 - 3340 m 27086 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 0 m 0 - 0 m 0 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 153640 W 107542 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 16700 W 16699 - 0 0 -
People 278 24076 37102 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 200758 37102 - 30252 0
Zone Conditioning - 201989 37102 - 5600 0
Plenum Wall Load 20% 2257 - 0 0 -
Plenum Roof Load 70% 101300 - 0 0 -
Plenum Lighting Load 30% 46090 - 0 0 -
Return Fan Load 17207 L/s 0 - 17207 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 17207 L/s 6373 - 17207 L/s -6373 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 1% 2008 - 1% 303 -
>> Total System Loads - 360016 37102 - -471 0
Central Cooling Coil - 360016 37107 - 0 0
>> Total Conditioning - 360016 37107 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.50 Page 1 of 1