Conventional Detectors

Orbis

The Ampac Orbis range of conventional fire detectors incorporates state-of-the-art technology designed to deliver the
fastest response times in the event of incipient fire whilst reducing the risk of unwanted alarms.
A suite of patents and “worlds first” accompany this range of detectors:
 StartUp™ - facilitates fast commissioning
 DustDefy™ - ultra modern housing that limits ingress of dirt into the chamber
 DirtAlert™ - a warning system incorporating drift compensation technology
 FasTest® - reduces the time it takes to test a detector
 SensAlert® - provides indication when detector becomes faulty
 TimeSaver Base® - designed for fast installation and cable termination
Other features include:
 Modern styling
 Wide voltage and operating temperature ranges
 New optical sensor for high reliability and reduced false alarm incidence
FIRE DETECTORS
AND DEVICES

 New Multisensor smoke detector for detecting fast-burning fires


 Algorithms for transient rejection
 Chamber designed to inhibit dirt penetration and thus reduce false alarms
 Automatic drift compensation with DirtAlert™ warning
 Optional flashing LED to indicate normal operation
 Multi-functional detector LED with 360º viewing
The range includes:
 Heat type detector
 Photo optical detector
 Multisensor detector
 TimeSaver Base in 4 (four) variants
> TimeSaver Base (standard)
> LX – allows Orbis detector to be fitted to Apollo Series 60/65 base
> Diode – when active End-Of-Line (EOL) devices are required
> Relay – relay is energised when detector LED is active
The ionisation type detector is not available in the Orbis range for 2 (two) main reasons:
1. Due to the nature of ionisation detectors, they are more sensitive to phenomena that cause unwanted alarms than
photo optical detectors
2. Ionisation detectors use a tiny radioactive foil. Although they are entirely safe to use, ionisation detectors are
subject to strict regulations concerning transport, storage and disposal. Thus it is becoming increasingly difficult to
use them.

Branding
All Orbis detectors are Ampac branded

DUE TO AM PAC’ S COMMIT ME NT T O C O NT INU O U S


FOR A QU O TATI O N A ND F U R TH ER I NF O R M ATI O N , G O TO :
54 I M PROVEM EN T, SPECIFIC AT IO NS MAY C H A NG E
WI THOUT N OTI CE
w w w. a m p a c . n e t
Conventional Detectors Orbis

Heat - Orbis (CSIRO & LPCB Approved)

Features Operating Voltage 8.5 to 33 VDC


Quiescent current 65μA
• Wide voltage and operating temperature ranges Alarm current 40mA at 24 VDC
• StartUp™ for fast commissioning Remote Output 1.2k7 to -ve supply
• FasTest® which reduces the time taken to test Size (ex base) 100Dia x 50H mm
detectors Operating temp. -40°C to +70°C
• SensAlert® which indicates that the detector is Humidity 0 to 98%
not operating properly IP rating 23D (EN60529)
• Multi-functional detector LED with 360° viewing Weight (ex base) 70 grams

Order Code Compliance Approved By


201-0500 BR/“A” type AS7240.5/EN54.5 CSIRO/LPCB
201-0504 A2S/“B” type AS7240.5/EN54.5 CSIRO/LPCB
201-0508 CR/“C” type AS7240.5/EN54.5 CSIRO/LPCB
201-0510 CS/“D” type AS7240.5/EN54.5 CSIRO/LPCB

REFER TO DATA SHEET: PDS201-0500

Heat - Orbis (LPCB Approved)

FIRE DETECTORS
Features Operating Voltage 8.5 to 33 VDC

AND DEVICES
Quiescent current 65μA
• Wide voltage and operating temperature ranges Alarm current 40mA at 24 VDC
• StartUp™ for fast commissioning Remote Output 1.2k7 to -ve supply
• FasTest® which reduces the time taken to test Size (ex base) 100Dia x 50H mm
detectors Operating temp. -40°C to +70°C
• SensAlert® which indicates that the detector is Humidity 0 to 98%
not operating properly IP rating 23D (EN60529)
• Multi-functional detector LED with 360° viewing Weight (ex base) 70 grams
Order Code Compliance Approved By
201-0520 A1R/”A” type EN54.5 LPCB
201-0522 A2S/”B” type EN54.5 LPCB
201-0524 BR/”A” type EN54.5 LPCB
201-0526 BS/”B” type EN54.5 LPCB
201-0528 CR/”C” type EN54.5 LPCB
201-0530 CS/”D” type EN54.5 LPCB

REFER TO DATA SHEET: PDS201-0500

Heat - Orbis (Flashing LED)

Features Operating Voltage 8.5 to 33 VDC


Quiescent current 65μA
• Wide voltage and operating temperature ranges
• StartUp™ for fast commissioning Alarm current 40mA at 24 VDC
• FasTest® which reduces the time taken to test detectors Remote Output 1.2k7 to -ve supply
• SensAlert® which indicates that the detector is not Size (ex base) 100Dia x 50H mm
operating properly Operating temp. -40°C to +70°C
• TimeSaver Base® designed for fast installation and cable Humidity 0 to 98%
termination IP rating 23D (EN60529)
• Flashing LED to indicate normal operation Weight (ex base) 70 grams
• Multi-functional detector LED with 360° viewing
Order Code Compliance Approved By
201-0521 A1R/“A” type flash LED EN54.5 LPCB
201-0523 A2S/“B” type flash LED EN54.5 LPCB
201-0525 BR/“A” type flash LED EN54.5 LPCB
201-0527 BS/“B” type flash LED EN54.5 LPCB
201-0529 CR/“C” type flash LED EN54.5 LPCB
201-0531 CS/“D” type flash LED EN54.5 LPCB

REFER TO DATA SHEET: PDS201-0500

DUE TO AM PAC’ S COMMIT ME NT T O C O NT INU O U S


FOR A QU O TATI O N A ND F U R TH ER I NF O R M ATI O N , G O TO :
I M PROVEM EN T, SPECIFIC AT IO NS MAY C H A NG E
WI THOUT N OTI CE
w w w. a m p a c . n e t 55
Conventional Detectors Orbis

Photo Optical Smoke – Orbis

Features Operating Voltage


Quiescent current
8.5 to 33 VDC
65μA
• Wide voltage and operating temperature ranges Alarm current 40mA at 24 VDC
• StartUp™ for fast commissioning Remote Output 1.2k7 to -ve supply
• DustDefy™ housing limits ingress of dirt into detector Size 100Dia x 42H mm
• New optical sensor reduces unwanted alarms Operating temp. -40°C to +70°C
• Algorithms for transient rejection Humidity 0 to 98%
• Chamber inhibits dirt penetration IP rating 23D (EN60529)
• Automatic drift compensation with dirtAlert™ warning Weight 75 grams
• FasTest® for fast testing detectors
• SensAlert® indicates faulty detector
• Multi-functional detector LED with 360° viewing
• Optional flashing LED to indicate normal operation
Order Code Compliance Approved By
201-0512 AS7240.7/EN54.7 CSIRO/LPCB
201-0532 EN54.7 LPCB
201-0533 flashing LED EN54.7 LPCB

REFER TO DATA SHEET: PDS201-0500

Multisensor – Orbis
FIRE DETECTORS

Features Operating Voltage 8.5 to 33 VDC


AND DEVICES

Quiescent current 65μA


• Wide voltage and operating temperature ranges Alarm current 40mA at 24 VDC
• StartUp™ for fast commissioning Remote Output 1.2k7 to -ve supply
• DustDefy™ housing limits ingress of dirt into detector Size (ex base) 100Dia x 50H mm
• New optical sensor reduces unwanted alarms Operating temp. -40°C to +70°C
• Algorithms for transient rejection Humidity 0 to 98%
• Chamber inhibits dirt penetration IP rating 23D (EN60529)
• Automatic drift compensation with dirtAlert™ warning Weight (ex base) 80 grams
• FasTest® for fast testing detectors
• SensAlert® indicates faulty detector
• Multi-functional detector LED with 360° viewing
• Optional flashing LED to indicate normal operation
Order Code Compliance Approved By
201-0514 AS7240.7/EN54.7 CSIRO/LPCB
201-0534 EN54.7 LPCB
201-0535 flashing LED EN54.7 LPCB

REFER TO DATA SHEET: PDS201-0500

TimeSaver Base® – Orbis

Features Size 100Dia x 8H mm


Operating temp. -40°C to +70°C
• Designed for fast installation and cable termination Humidity 0 to 98%
• Unique E-Z fit fixing holes for easy mounting IP rating 23D (EN60529)
• Wide cable entry Weight 60 grams
• Lockable base
• Multiple variatns of bases available
– LX – allows Orbis detector to be fitted to Apollo
Series 60/65 base
– Diode – when active EOL devices are used
– Relay – activates when detector LED is on
• White finish
Order Code Compliance Approved By
201-0536 TimeSaver AS7240/EN54 CSIRO/LPCB
201-0537 LX AS7240/EN54 CSIRO/LPCB
201-0538 Diode AS7240/EN54 CSIRO/LPCB
201-0539 Relay AS7240/EN54 CSIRO/LPCB

REFER TO DATA SHEET: PDS201-0500