Beruflich Dokumente
Kultur Dokumente
1
2
3
4
5
11. FIBER ORIENTATION / MATING Typical fiber (core) orientation is either north, south, west, east
or a combination of those Fibers for testing have almost centered orientation Ability to maintain
best results and repeatability Expensive and hard to get
12. OPTICAL SOURCES Light Emitting Diodes (LED) Used for multimode: 850 nm or 1300 nm
Wide beam width fills multimode fibers Wider spectrum (typically 50 nm) Inexpensive Lasers
Used for singlemode: 1310 nm or 1550 nm Two Common Types: Fabry-Perot (FP) and Distributed
Feedback (DFB) Narrow spectrum (can be less than 1 nm) Narrow beam width (does not fill
6
multimode fibers) Highest power and fastest switching Most expensive (especially DFB)
Wavelength Wavelength
7
8
9
19. Sources of Loss in Fiber Optic Paths Dirty connections The fiber material Impurities
Variation in material density Coupling losses between fibers Bends in the fiber
10
11
12
13
14
15
32. ANSI/TIA-568-C.0 and ISO/IEC 11801:2002 Test Limit Lets calculate the allowable loss for the
link below: 850 nm: Adapters Splices Fiber = 2 * 0,75 dB = 0 * 0,3 dB = 0,1 km * 3,5 dB Allowable loss
= 1,50 dB 0,00 dB 0,35 dB 1,85 dB
16
34. FIELD FACT FACT FROM FIELD: I DO NOT NEED TO TEST WE CONNECT THE FIBER AND IF THE
LED LIGHTS UP GREEN WE ARE GOOD TO GO!!! THE USER APPLICATION WILL BE JUST FINE...
17
18
19
20
21
22
46. OLTS One Jumper Reference Tier 1 Setting Reference Added dB dB includes link + ALL
connectors Supports a Permanent Link Measurement
23
48. OLTS Two Jumper Reference Tier 1 Unfortunately is the most intuitive method but NOT correct
Setting Reference dB includes Link + ONLY ONE End Connector dB
24
25
52. Understand OTDR plots: Reflective events Almost always two mated fiber connectors (air gap)
Could be a bad mechanical splice too On the OTDR trace, they are characterized as a spike
Higher reflectance means better mating
26
27
28
29
60. Proposed tests at each step of the way Proposed test each step of the way Network and
Equipment Installation stage Verify total loss budget Link Characterization Coupler and Splices
Characterization End to End Loss & Back Reflection Testing OLT and ONT turn up Maintenance
stage How many ONTs are out? One? Some? All?
30
61. Network and Equipment Installation stage Verify total loss budget 16 dB for 1:32 10 dB
for 1:8 7 db for 1:4 2 3 dB 0,35 dB/km@1330 nm
31
32
33
34
'70. Connectivity Layer 1 Verify Link Up and MDI settings Verify Speed, duplex and flow control
Layer 2 and 3 Layer 2, verify MAC connectivity ARPing the address Layer 3 connectivity, verify
IP address is valid before doing any additional test PING
35
36
37
ranscripts - Measuring Fiber / Merenja na optikim vlaknima
40
NEVER use 8 method to clean 5. Check end-face with microscope or camera, place cap on
test reference cord
37. Cleaning ports For dirty port use wet method (1st foam tip is wet to clean the dirty
port, second foam tip is dry to pickup dirt from port)
38. Inspection Two methods Microscope Cheap no built-in filter Higher cost built-
in protection filter Inspection camera Safest method for inspection of ports and
connectors
39. Connectivity Verification The basic test before any testing is to use a VFL to determine:
Where there is a break in the fiber panel Where there is an excessive bend in the fiber
panel (typically an issue in FTTx networks and home installations) Verify correct polarity
40. Connectivity Verification Limitations of a VFL: The fiber can be broken in multiple
places, yet you will still see light coming out at the end It is of no use in trunk cable, the
light will never pass through the outer black jacket VFLs rely on the fiber jacket being
translucent
41. 5 Standard Ways To Test Fiber In 2010, the old OFSTP-14 was replaced by a new ISO
standard. The TIA has adopted IEC 61280-4-1 as the replacement of OFSTP-14. Most of the
two documents is the same, with some important exceptions. For insertion loss, three
reference methods are are still approved, but the nomenclature is different - no more
"Method A, B or C" designations- it's now 1, 2 or 3 reference cables. OTDR testing is now
an approved test method as long as you use both launch and receive cables. Reference
test cables with "reference grade connectors" are recommended. Methods are given for
testing and verifying the loss of reference test cables. For multimode modal control, CPR
with a mandrel wrap is gone, replaced by "Encircled Flux," a complex - and not completely
debugged - method of measuring the source output.
42. TESTING (structured cabling) Network Designers may include two levels of testing in
fiber test specifications: Tier 1: OLTS (Optical Loss Test Set) Testing the installed cable
plant for link loss and verifying the cabling length and polarity Polarity for some backbone
simplex applications may not need to be verified. Tier 2: Tier 1 plus an OTDR trace
Testing for anomalies and assuring uniformity of cable attenuation and connector insertion
loss. The higher level of testing providing quantitative measures of the installed condition
and performance of the cabling system and its components. Evidence that cable is installed
without degrading events (e.g., bends, bad connections, bad splices)
43. TESTING (structured cabling) Using the Right Method is Essential ISO/IEC TR 14763-3
specifies Method 2 one jumper reference for testing the fiber link. A mismatch of the
connector type between the OLTS and the link requires a modified method. Using the
wrong method can result in a significant measurement error. ALL LIGHT SOURCES TAKE
TIME TO STABILIZE
44. Multimode MANDRELS Required, not optional If I dont use them? You may end up
failing perfectly good links What do they do? They strip out the higher order modes in
multimode TRCs Result is more repeatable, consistent optical power measurements when
using LED sources. Do not use non bend insensitive fiber TRCs The mandrels will have no
affect
45. Encircled Flux The New Standard in Multimode Testing Accuracy
46. OLTS One Jumper Reference Tier 1 Setting Reference Added dB dB includes link + ALL
connectors Supports a Permanent Link Measurement
47. OLTS - Modified One Jumper Reference Tier 1 The connector is a Setting different type
then the Reference one on the OLTS Added dB includes link + all connectors dB
48. OLTS Two Jumper Reference Tier 1 Unfortunately is the most intuitive method but NOT
correct Setting Reference dB includes Link + ONLY ONE End Connector dB
49. OLTS Three Jumper Reference Tier 1 The connector can be a Setting Reference
different type then the one on the OLTS dB Includes Link/Channel BUT NO End Connectors
dB Supports a Channel Measurement
41
50. OLTS Method comparison Tier 1 The standards clearly define the referencing
method, but the nomenclature is confusing Link End Connections Included in Loss Results
Latest Versions Previous Versions TIA/EIA-526-14A (multimode) TIA/EIA-526-7 (singlemode)
IEC 61280-4-1 (multimode) IEC 61280-4-2 (singlemode) 1 Connection 2 Jumper Method A
Method A Method A.2 Method 1 Method A2 2 Connections 1 Jumper Method B Method B
Method A.1 Method 2 Method A1 None 3 Jumper Method C Method C Method A.3 Method
3 Method A3
51. Supplemental OTDR Trace Tier 2 OTDR trace is a supplement to OLTS Determined
cause of excess loss Troubleshoot fiber link Telco / Service providers still rely on OTDR
testing This is good for veryfing the installation, still OLTS is required to meet the
application requirements
52. Understand OTDR plots: Reflective events Almost always two mated fiber connectors
(air gap) Could be a bad mechanical splice too On the OTDR trace, they are characterized
as a spike Higher reflectance means better mating
53. Reflectance in connectors When the light travels down the fiber, if it sees a change in
refractive index, their will be a reflection (reflectance) The most common causes are: Ideal
world no undercut Air gap between the connectors Dirt or residue left behind by the
cleaning solution Good reflectance for UPC connector is -40 to -50 dB (recommended < -
45 dB) Reality -best factory terminated connectors will have an undercut better than 50 nm
(thats 0.05 m).
54. Understand OTDR plots: Non-Reflective events Almost always a splice, could also be a
very good APC connection can be an issue when using limit lines Good reflectance for
APC is < -60 dB If you only see it at 1300nm (MM) or 1550 nm (SM), then it is a bend in the
fiber On the OTDR trace, they are characterized as a dip in the trace
55. OTDR Bi-directional Averaging Do I need to do this? If the customer asks for it, YES
ANSI/TIA-526-14-B; if the launch fiber has a different backscatter coefficient to the fiber you
are testing, then you should ISO/IEC 14763-3; This is not necessary where the cabling
under test comprises a single length of fixed cabling with terminating connectors and where
the optical fibres of the launch and tails cords have the same scattering characteristics.
Will always give the most accurate loss at each event Must use Launch + Receive Fiber
Compensation in Setup
56. OTDR Launch fiber Each connector used in the Launch Fiber network MUST have the
same connector type for mating Using short patch cords make results even worse Will give
loss of the first connector
57. OTDR Receive fiber Receive Fiber Will give loss of the last connector
58. Common Measurement Issues Setting Reference When done do NOT remove fiber
from the source, otherwise repeat reference method Negative Loss reading Sources not
stabilized Bad reference Gainer (mismatch of MM cables used in link) Ghosting Long
Attenuation dead zone Dirty or damaged connectors/mating Poor reflectance
Bad/damaged launch fiber Dirty connetors Dirt on the fiber endface Good reflectance, but
high loss only on one wavelength Excessive fiber bending
59. Passive Networks vs. Active Passive Optical Networks (PON) implement a: Point-to-
Multipoint Topology Triple-play Fiber-to-the-Desktop (FTD) Has two (2) active
components (OLT and ONT)
60. Proposed tests at each step of the way Proposed test each step of the way Network
and Equipment Installation stage Verify total loss budget Link Characterization Coupler
and Splices Characterization End to End Loss & Back Reflection Testing OLT and ONT turn
up Maintenance stage How many ONTs are out? One? Some? All?
61. Network and Equipment Installation stage Verify total loss budget 16 dB for 1:32
10 dB for 1:8 7 db for 1:4 2 3 dB 0,35 dB/km@1330 nm
62. Link characterization Done before splicing or connectorizing splitter From OLT
towards splitter and from splitter to the ONT OTDR at wavelengths 1310, (1490) and 1550
nm
42
63. Coupler and Splices Characterization Done after splice and connectorizing process
From splitter output back to OLT OTDR with 1310, (1490) and 1550 nm with launch fiber
Backreflection or coupler ports should be -35 dB or better (ITU-T G.983.1) End to End Loss
& Back Reflection Testing Done with a power meter and source at 1310, 1490 and 1550 nm
Max Loss 25 dB for Class-B PON (20 dB Class-A and 30 dB Class-C) OTDR trace OLT->ONT
and ONT->OLT to confirm back reflections to be -35 dB or more and splice losses less than
0,1 dB
64. OLT and ONT turn up Before any ONT turn-up Verify power at ONT coming from
OLT at drop point Masure at 1310, 1490 and 1550 nm to get a go-no-go power reading
(pass/fail criteria is user defined and depends on OLT)
65. Maintenance Stage ONT Outage when SOME are out Check power level at the closest
faulty ONT No power fiber defect between OLT and ONT Strong power (in the limits of
OLT spec) exchange the ONT Weak power use fiber identifier to measure total power
on fiber or visual fault locator for possible macrobending
66. ONT Outage when ALL are out Easy to overcome and fix Either OLT is out of order
or a major fault has occurred between the OLT and the spliter point Check feeding (F1)
fiber OTDR trace for OLT side at 1550 nm OTDR facts when testing in PON environment
1625 nm must be used in live PON and fro ONT -> OLT If testing from OLT side a PON
optimized OTDR must be used in order to see through splitters
67. OTDR OLT->ONT Example
68. WHAT IF? I rent fiber from a provider? Do I need to sign SLA? I want to test how fast my
network is? WHAT DO I DO????
69. Ethernet testing To verify a link performance you do not need to understand standards
Key paramaters for Ethernet testing Determining the layer of testing and the nature of
the link under test Connectivity Physical connectivity Layer 2 and up connectivity
Throughput Burstability Latency/Jitter
70. Connectivity Layer 1 Verify Link Up and MDI settings Verify Speed, duplex and flow
control Layer 2 and 3 Layer 2, verify MAC connectivity ARPing the address Layer 3
connectivity, verify IP address is valid before doing any additional test PING
71. And what about T-PUT and others BER Testing Familiar concept Throughput Testing
Better but not complete All in one RFC2544 Frame loss Burstability Jitter Latency
RFC2544 Various Frame Sizes All tests in one set of measurements Provide A to B and
B to A results to identify the direction of the network having problems (if any)
72. Performing RFC2544
73. FUTURE APPLICATIONS?
74. 40G, 100G 40GBASE-SR4 and 100GBASE-SR10 MPO trunks (12 core fiber), utilizing
several 10G fiber links Fiber standards for certification?
75. THANK YOU! Green Light / Red Light IS NOT ENOUGH YOU NEED TO TEST IN ORDER
TO GUARANTEE THE PERFORMANCE OF THE USER APPLICATIONS
43