The mix design M-50 grade (Using Admixture Sikament) provided here is for reference

purpose only. Actual site conditions vary and thus this should be adjusted as per the location
and other factors.

Parameters for mix design M50


Grade Designation = M-50
Type of cement = O.P.C-43 grade
Brand of cement = Vikram ( Grasim )
Admixture = Sika [Sikament 170 ( H ) ]
Fine Aggregate = Zone-II
Sp. Gravity
Cement = 3.15
Fine Aggregate = 2.61
Coarse Aggregate (20mm) = 2.65
Coarse Aggregate (10mm) = 2.66
Minimum Cement (As per contract) =400 kg / m3
Maximum water cement ratio (As per contract) = 0.45
Mix Calculation:
1. Target Mean Strength = 50 + ( 5 X 1.65 ) = 58.25 Mpa

2. Selection of water cement ratio:-


Assume water cement ratio = 0.35
3. Calculation of water:
Approximate water content for 20mm max. Size of aggregate = 180 kg /m (As per Table No. 3

5 , IS : 10262 ). As plasticizer is proposed we can reduce water content by 20%.


Now water content = 180 X 0.8 = 144 kg /m3

4. Calculation of cement content:-


Water cement ratio = 0.35
Water content per cum of concrete = 144 kg
Cement content = 144/0.35 = 411.4 kg / m3
Say cement content = 412 kg / m3 (As per contract Minimum cement content 400 kg / m3 )
Hence O.K.
5. Calculation for C.A. & F.A.: [ Formulas can be seen in earlier posts]-

Volume of concrete = 1 m3
Volume of cement = 412 / ( 3.15 X 1000 ) = 0.1308 m3
Volume of water = 144 / ( 1 X 1000 ) = 0.1440 m3
Volume of Admixture = 4.994 / (1.145 X 1000 ) = 0.0043 m3
Total weight of other materials except coarse aggregate = 0.1308 + 0.1440 +0.0043 =
0.2791 m3
Volume of coarse and fine aggregate = 1 0.2791 = 0.7209 m3
Volume of F.A. = 0.7209 X 0.33 = 0.2379 m3 (Assuming 33% by volume of total aggregate )
Volume of C.A. = 0.7209 0.2379 = 0.4830 m3
Therefore weight of F.A. = 0.2379 X 2.61 X 1000 = 620.919 kg/ m3
Say weight of F.A. = 621 kg/ m3
Therefore weight of C.A. = 0.4830 X 2.655 X 1000 = 1282.365 kg/ m3
Say weight of C.A. = 1284 kg/ m3
Considering 20 mm: 10mm = 0.55: 0.45
20mm = 706 kg .
10mm = 578 kg .
Hence Mix details per m3
Increasing cement, water, admixture by 2.5% for this trial
Cement = 412 X 1.025 = 422 kg
Water = 144 X 1.025 = 147.6 kg
Fine aggregate = 621 kg
Coarse aggregate 20 mm = 706 kg
Coarse aggregate 10 mm = 578 kg
Admixture = 1.2 % by weight of cement = 5.064 kg.
Water: cement: F.A.: C.A. = 0.35: 1: 1.472: 3.043
Following table shows the M-35 Mix Designs as per IS-10262-2009, hope this helps all civil
engineers here

CONCRETE MIX DESIGN

As per IS 10262-2009 & MORT&H

A-1 Stipulations for Proportioning

1
Grade Designation M35

2
OPC 53 grade confirming to IS-
Type of Cement 12269-1987

3
Maximum Nominal Aggregate Size 20 mm

4
Minimum Cement Content (MORT&H
1700-3 A) 310 kg/m3

5
Maximum Water Cement Ratio
(MORT&H 1700-3 A) 0.45

6
Workability (MORT&H 1700-4) 50-75 mm (Slump)

7
Exposure Condition Normal

8
Degree of Supervision Good

9
Type of Aggregate Crushed Angular Aggregate

10
Maximum Cement Content (MORT&H
Cl. 1703.2) 540 kg/m3

11
Superplasticiser Confirming to IS-
Chemical Admixture Type 9103
A-2 Test Data for Materials

1
Cement Used Coromandal King OPC 53 grade

2
Sp. Gravity of Cement 3.15

3
Sp. Gravity of Water 1.00

4
Chemical Admixture BASF Chemicals Company

5
Sp. Gravity of 20 mm Aggregate 2.884

6
Sp. Gravity of 10 mm Aggregate 2.878

7
Sp. Gravity of Sand 2.605

8
Water Absorption of 20 mm
Aggregate 0.97%

9
Water Absorption of 10 mm
Aggregate 0.83%

10
Water Absorption of Sand 1.23%

11
Free (Surface) Moisture of 20 mm
Aggregate nil

12
Free (Surface) Moisture of 10 mm
Aggregate nil

13
Free (Surface) Moisture of Sand nil
14
Sieve Analysis of Individual Coarse
Aggregates Separate Analysis Done

15
Sieve Analysis of Combined Coarse
Aggregates Separate Analysis Done

15
Sp.Gravity of Combined Coarse
Aggregates 2.882

16
Sieve Analysis of Fine Aggregates Separate Analysis Done

A-3 Target Strength for Mix Proportioning

1
Target Mean Strength (MORT&H
1700-5) 47N/mm2

2
Characteristic Strength @ 28 days 35N/mm2

A-4 Selection of Water Cement Ratio

1
Maximum Water Cement Ratio
(MORT&H 1700-3 A) 0.45

2
Adopted Water Cement Ratio 0.4

A-5 Selection of Water Content

1
Maximum Water content (10262-
table-2) 186 Lit.

2
Estimated Water content for 50-75
mm Slump 160 Lit.

3
Superplasticiser used 0.5 % by wt. of cement

A-6 Calculation of Cement Content


1
Water Cement Ratio 0.4

2
Cement Content (160/0.42) 400 kg/m3

Which is greater then 310 kg/m3

Proportion of Volume of Coarse Aggregate & Fine Aggregate


A-7 Content

1
Vol. of C.A. as per table 3 of IS
10262 62.00%

2
Adopted Vol. of Coarse Aggregate 62.00%

Adopted Vol. of Fine Aggregate ( 1-


0.62) 38.00%

A-8 Mix Calculations

1
Volume of Concrete in m3 1.00

2
Volume of Cement in m3 0.13

(Mass of Cement) / (Sp. Gravity of


Cement)x1000

3
Volume of Water in m3 0.160

(Mass of Water) / (Sp. Gravity of


Water)x1000

4
Volume of Admixture @ 0.5% in m3 0.00168

(Mass of Admixture)/(Sp. Gravity of


Admixture)x1000

5
Volume of All in Aggregate in m3 0.711

Sr. no. 1 (Sr. no. 2+3+4)


6
Volume of Coarse Aggregate in m3 0.441

Sr. no. 5 x 0.62

7
Volume of Fine Aggregate in m3 0.270

Sr. no. 5 x 0.38

A-9 Mix Proportions for One Cum of Concrete (SSD Condition)

1
Mass of Cement in kg/m3 400

2
Mass of Water in kg/m3 160

3
Mass of Fine Aggregate in kg/m3 704

4
Mass of Coarse Aggregate in kg/m3 1271

Mass of 20 mm in kg/m3 915

Mass of 10 mm in kg/m3 356

5
Mass of Admixture in kg/m3 2.00

6
Water Cement Ratio 0.40
Mix Design M-40 Grade (0.98)
The mix design M-40 grade for Pier (Using Admixture Fosroc) provided here is for reference
purpose only. Actual site conditions vary and thus this should be adjusted as per the location
and other factors.

Parameters for mix design M40


Grade Designation = M-40
Type of cement = O.P.C-43 grade
Brand of cement = Vikram ( Grasim )
Admixture = Fosroc ( Conplast SP 430 G8M )
Fine Aggregate = Zone-II
Sp. Gravity Cement = 3.15
Fine Aggregate = 2.61
Coarse Aggregate (20mm) = 2.65
Coarse Aggregate (10mm) = 2.66
Minimum Cement (As per contract) = 400 kg / m3
Maximum water cement ratio (As per contract) = 0.45
Mix Calculation:
1. Target Mean Strength = 40 + (5 X 1.65) = 48.25 Mpa

2. Selection of water cement ratio:-


Assume water cement ratio = 0.4
3. Calculation of cement content:
Assume cement content 400 kg / m3
(As per contract Minimum cement content 400 kg / m3)
4. Calculation of water:
400 X 0.4 = 160 kg Which is less than 186 kg (As per Table No. 4, IS: 10262)
Hence o.k.
5. Calculation for C.A. & F.A.: As per IS : 10262 , Cl. No. 3.5.1

V = [ W + (C/Sc) + (1/p) . (fa/Sfa) ] x (1/1000)


V = [ W + (C/Sc) + {1/(1-p)} . (ca/Sca) ] x (1/1000)
Where
V = absolute volume of fresh concrete, which is equal to gross volume (m3) minus the volume
of entrapped air ,
W = mass of water ( kg ) per m3 of concrete ,
C = mass of cement ( kg ) per m3 of concrete ,
Sc = specific gravity of cement,
(p) = Ratio of fine aggregate to total aggregate by absolute volume ,

(fa) , (ca) = total mass of fine aggregate and coarse aggregate (kg) per m 3 of
Concrete respectively, and
Sfa , Sca = specific gravities of saturated surface dry fine aggregate and Coarse aggregate
respectively.

As per Table No. 3 , IS-10262, for 20mm maximum size entrapped air is 2% .

Assume F.A. by % of volume of total aggregate = 36.5 %

0.98 = [ 160 + ( 400 / 3.15 ) + ( 1 / 0.365 ) ( Fa / 2.61 )] ( 1 /1000 )

=> Fa = 660.2 kg

Say Fa = 660 kg.

0.98 = [ 160 + ( 400 / 3.15 ) + ( 1 / 0.635 ) ( Ca / 2.655 )] ( 1 /1000 )

=> Ca = 1168.37 kg.

Say Ca = 1168 kg.

Considering 20 mm : 10mm = 0.6 : 0.4


20mm = 701 kg .
10mm = 467 kg .
Hence Mix details per m3
Cement = 400 kg
Water = 160 kg
Fine aggregate = 660 kg
Coarse aggregate 20 mm = 701 kg
Coarse aggregate 10 mm = 467 kg
Admixture = 0.6 % by weight of cement = 2.4 kg.
Recron 3S = 900 gm
Water: cement: F.A.: C.A. = 0.4: 1: 1.65: 2.92

M-30 Mix Designs as per IS-10262-2009

M-30 CONCRETE MIX DESIGN

As per IS 10262-2009 & MORT&H

A-1 Stipulations for Proportioning

1
Grade Designation M30

2 OPC 53 grade confirming to IS-


Type of Cement 12269-1987

3
Maximum Nominal Aggregate Size 20 mm

4 Minimum Cement Content (MORT&H


1700-3 A) 310 kg/m3

5 Maximum Water Cement Ratio


(MORT&H 1700-3 A) 0.45

6
Workability (MORT&H 1700-4) 50-75 mm (Slump)

7
Exposure Condition Normal

8
Degree of Supervision Good
9
Type of Aggregate Crushed Angular Aggregate

10 Maximum Cement Content


(MORT&H Cl. 1703.2) 540 kg/m3

11 Superplasticiser Confirming to IS-


Chemical Admixture Type 9103

A-2 Test Data for Materials

1
Cement Used Coromandal King OPC 53 grade

2
Sp. Gravity of Cement 3.15

3
Sp. Gravity of Water 1.00

4
Chemical Admixture BASF Chemicals Company

5
Sp. Gravity of 20 mm Aggregate 2.884

6
Sp. Gravity of 10 mm Aggregate 2.878

7
Sp. Gravity of Sand 2.605

8
Water Absorption of 20 mm Aggregate 0.97%

9
Water Absorption of 10 mm Aggregate 0.83%

10
Water Absorption of Sand 1.23%
11 Free (Surface) Moisture of 20 mm
Aggregate nil

12 Free (Surface) Moisture of 10 mm


Aggregate nil

13
Free (Surface) Moisture of Sand nil

14 Sieve Analysis of Individual Coarse


Aggregates Separate Analysis Done

15 Sieve Analysis of Combined Coarse


Aggregates Separate Analysis Done

15 Sp. Gravity of Combined Coarse


Aggregates 2.882

16
Sieve Analysis of Fine Aggregates Separate Analysis Done

A-3 Target Strength for Mix Proportioning

1 Target Mean Strength (MORT&H


1700-5) 42N/mm2

2
Characteristic Strength @ 28 days 30N/mm2

A-4 Selection of Water Cement Ratio

1 Maximum Water Cement Ratio


(MORT&H 1700-3 A) 0.45

2
Adopted Water Cement Ratio 0.42

A-5 Selection of Water Content

1 Maximum Water content (10262-table-


2) 186 Lit.
2 Estimated Water content for 50-75 mm
Slump 160 Lit.

3
Superplasticiser used 0.5 % by wt. of cement

A-6 Calculation of Cement Content

1
Water Cement Ratio 0.42

2
Cement Content (160/0.42) 380 kg/m3
Which is greater then 310 kg/m3

A-7 Proportion of Volume of Coarse Aggregate & Fine Aggregate Content

1
Vol. of C.A. as per table 3 of IS 10262 62.00%

2
Adopted Vol. of Coarse Aggregate 62.00%
Adopted Vol. of Fine Aggregate ( 1-
0.62) 38.00%

A-8 Mix Calculations

1
Volume of Concrete in m3 1.00

2
Volume of Cement in m3 0.12
(Mass of Cement) / (Sp. Gravity of
Cement)x1000

3
Volume of Water in m3 0.160
(Mass of Water) / (Sp. Gravity of
Water)x1000
4
Volume of Admixture @ 0.5% in m3 0.00160
(Mass of Admixture)/(Sp. Gravity of
Admixture)x1000

5
Volume of All in Aggregate in m3 0.718
Sr. no. 1 (Sr. no. 2+3+4)

6
Volume of Coarse Aggregate in m3 0.445
Sr. no. 5 x 0.62

7
Volume of Fine Aggregate in m3 0.273
Sr. no. 5 x 0.38

A-9 Mix Proportions for One Cum of Concrete (SSD Condition)

1
Mass of Cement in kg/m3 380

2
Mass of Water in kg/m3 160

3
Mass of Fine Aggregate in kg/m3 711

4
Mass of Coarse Aggregate in kg/m3 1283
Mass of 20 mm in kg/m3 924
Mass of 10 mm in kg/m3 359

5
Mass of Admixture in kg/m3 1.90

6
Water Cement Ratio 0.42
CONCRETE MIX DESIGN (GRADE M60)

(a) DESIGN STIPULATION:-


Target strength = 60Mpa
Max size of aggregate used = 12.5 mm
Specific gravity of cement = 3.15
Specific gravity of fine aggregate (F.A) = 2.6
Specific gravity of Coarse aggregate (C.A) = 2.64
Dry Rodded Bulk Density of fine aggregate = 1726 Kg/m 3
Dry Rodded Bulk Density of coarse aggregate = 1638 Kg/m 3

Step-1
Calculation for weight of Coarse Aggregate:
From ACI 211.4R Table 4.3.3 Fractional volume of oven dry Rodded C.A for 12.5mm size
aggregate is 0.68m3
Weight of C.A = 0.68*1638 = 1108.13 Kg/m3
Step-2
Calculation for Quantity of Water:
From ACI 211.4R Table 4.3.4
Assuming Slump as 50 to 75mm and for C.A size 12.5 mm the Mixing water = 148 ml
Void content of FA for this mixing water = 35%
Void content of FA (V)
V = {1-(Dry Rodded unit wt / specific gravity of FA*1000)}*100
= [1-(1726/2.6*1000)]*100
= 34.62%
Adjustment in mixing water = (V-35)* 4.55
= (34.62 35)*4.55
= -1.725 ml
Total water required = 148 + (-1.725) = 146.28 ml
Step-3
Calculation for weight of cement
From ACI 211.4R Table 4.3.5(b)
Take W / C ratio = 0.29
Weight of cement = 146.28 / 0.29 = 504.21 kg/m3

Step-4
Calculation for weight of Fine Aggregate:
Cement = 504.21 / 3.15*1000= 0.1616
Water = 146.28 / 1*1000= 0.1462
CA = 1108.13 / 3*1000= 0.3690
Entrapped Air = 2 / 100= 0.020
Total = 0.7376m3
Volume of Fine Aggregate= 1-0.7376
Weight of Fine Aggregate= 0.2624*2.6*1000= 683.24 kg/m 3

Step-5
Super plasticizer:
For 0.8% = (0.8 / 100)*583.53 = 4.668 ml
Step-6
Correction for water:
Weight of water (For 0.8%) =146.28 4.668 =141.61 kg/m 3

Requirement of materials per Cubic meter


Cement = 504.21 Kg/m3
Fine Aggregate = 683.24 Kg/m3
Coarse Aggregate = 1108.13 Kg/m3
Water = 141.61 Kg/ m3
Super plasticizers = 4.6681 / m3
So the final ratio becomes
Cement : Fine agg (kg/m ) : Coarse agg (kg/m ) : Water (l/m ): Superplasticizer (l/m3)
3 3 3

1: 1.35 :2.19 :0.29 :0.8