Considering the temperature in Morong, Rizal which is equal to 35 C
I. Floor space
Heat gain = Floor space x Factor
= (11.48 ft. x 13.448 ft.) x 3 = 463.15 Btu/hr x 1.055 = 488.62 KJ/hr
II. Volumetric capacity
Heat gain = Volumetric capacity x Factor
= (11.48ft. x 13.448 ft. x 7.872ft.) x .6 = 2187.54 Btu/hr x 1.055 = 2307.86 KJ/hr
III. Window exposed to the sun
Heat gain = Window exposed to the sun x Factor
= [(5.74(2)ft. x 4.72ft.)] x 45 = 2429.856 Btu/hr x 1.055 = 2563.49 KJ/hr
IV. All windows not included in III
NONE
V. Wall exposed to sun
Heat gain = Wall space x Factor
= [(13.448 x 7.872)-(5.74(2)ft. x 4.72ft.)+(11.48 x 7.872)] x 13 = 1838.85 Btu/hr x 1.055 = 1939.99 KJ/hr VI. All exterior walls not included in V
Heat gain = Wall space x Factor
= [(13.448 x 7.872) + (11.48 x 7.872)] x 9 = 1766.10 Btu/hr x 1.055 = 1863.23 KJ/hr
VII. Partitions
Heat gain = Partition space x Factor
= (11.48ft. x 7.872ft.) x 4 = 527.124 Btu/hr x 1.055 = 556.116 KJ/hr
VIII. Ceiling or roof
Heat gain = Floor space x Factor
= (15 ft. x 14.17 ft.) x 3 = 361.48 Btu/hr x 1.055 = 381.36 KJ/hr
IX. Number of people
Heat gain = 5 x 600
= 3000 Btu/hr x 1.055 = 3165 KJ/hr
X. Lights and electrical equipment in use
Heat gain = [(LIGHT ) + (APPLIANCE)
x Factor = [(1 x 80 w) + (1 x 100W)] x 3 = 380 Btu/hr x 1.055 = 400.9 KJ/hr
XI. Total Cooling load
Total Heat gain = ( 672.72 + 1251.26 +826.065 + 275.355 +1674.60 +
= 2575.81 +556.116 +672.72 +3798 +199.395 ) KJ/hr = 12 502.048 KJ/hr Total Cooling load is 13,666.57 KJ/hr Conclusion: With this Cooling Load Value it is recommended to select the model CW 1200 FPH / CW 1202FPH