COOLING LOAD CALCULATION

Considering the temperature in Morong, Rizal which is equal to 35 C

I. Floor space

Heat gain = Floor space x Factor


= (11.48 ft. x 13.448 ft.) x 3
= 463.15 Btu/hr x 1.055
= 488.62 KJ/hr

II. Volumetric capacity

Heat gain = Volumetric capacity x Factor


= (11.48ft. x 13.448 ft. x 7.872ft.) x .6
= 2187.54 Btu/hr x 1.055
= 2307.86 KJ/hr

III. Window exposed to the sun

Heat gain = Window exposed to the sun x Factor


= [(5.74(2)ft. x 4.72ft.)] x 45
= 2429.856 Btu/hr x 1.055
= 2563.49 KJ/hr

IV. All windows not included in III

NONE

V. Wall exposed to sun

Heat gain = Wall space x Factor


= [(13.448 x 7.872)-(5.74(2)ft. x 4.72ft.)+(11.48 x 7.872)] x 13
= 1838.85 Btu/hr x 1.055
= 1939.99 KJ/hr
VI. All exterior walls not included in V

Heat gain = Wall space x Factor


= [(13.448 x 7.872) + (11.48 x 7.872)] x 9
= 1766.10 Btu/hr x 1.055
= 1863.23 KJ/hr

VII. Partitions

Heat gain = Partition space x Factor


= (11.48ft. x 7.872ft.) x 4
= 527.124 Btu/hr x 1.055
= 556.116 KJ/hr

VIII. Ceiling or roof

Heat gain = Floor space x Factor


= (15 ft. x 14.17 ft.) x 3
= 361.48 Btu/hr x 1.055
= 381.36 KJ/hr

IX. Number of people

Heat gain = 5 x 600


= 3000 Btu/hr x 1.055
= 3165 KJ/hr

X. Lights and electrical equipment in use

Heat gain = [(LIGHT ) + (APPLIANCE)


x Factor
= [(1 x 80 w) + (1 x 100W)] x 3
= 380 Btu/hr x 1.055
= 400.9 KJ/hr

XI. Total Cooling load

Total Heat gain = ( 672.72 + 1251.26 +826.065 + 275.355 +1674.60 +


= 2575.81 +556.116 +672.72 +3798 +199.395 ) KJ/hr
= 12 502.048 KJ/hr
Total Cooling load is 13,666.57 KJ/hr
Conclusion: With this Cooling Load Value it is recommended to select the model
CW 1200 FPH / CW 1202FPH