This tutorial is designed to acquaint new users with the basic functions of OneLiner. We assume you have
installed OneLiner (Section 2.1 or 2.3) and started the program (Section 2.2 or 2.4). If not, do so now. This
tutorial will take about an hour to complete.
OPENING A BINARY DATA FILE
A 30-bus system is used in most of this tutorial. You will now open its binary data file.
1. Select the File | Open Binary Data File command.
Note: To select this command you first click the left mouse button on 'File' to open
its pull down menu. Then click the left mouse button on 'Open Binary Data File'.
A dialog box will appear asking you for the name of the binary data file
that you want to open.
2. Open the file SAMPLE30.OLR as follows.
Click once on the file name 'SAMPLE30.OLR' in the list box. The
name will appear in the File Name edit box. Click on the "Open"
button.
The dialog box will disappear. After a short time the one-line diagram of
the 30-bus system will appear in the Main Window.
Note: See Section Error! Reference source not found. if you are unsure of the
meanings of the various symbols.
The line symbol will turn dotted red. A dialog box for this line will
appear.
4. Select the File | Exit command to close the on-line help window.
The on-line help window will disappear.
5. Press OK to close the line dialog box.
The dialog box will disappear.
ADDING EQUIPMENT
You can add new equipment to the system by selecting the equipment type from the device palette and dropping
a new device on the diagram. You will learn in the following how to create new buses and lines. Similar
procedures apply to other types of equipment.
ADDING A NEW BUS:
1. Select command View | Device Palette to show the Device Palette if it is not
already visible
A dialog box will appear. The parameters in the bus dialog box are those
of the last bus.
3. Modify the bus data.
Enter New Bus in the edit box labeled 'Name'.
Enter 33 in the edit box labeled 'Nom. kV'.
Change the area number to 1, and the zone number to 1.
Change location to NEW.
Note: The second page of the bus dialog box (not visible), labeled
'Breaker Data', is for circuit breaker information. The breaker data are
used by the ASPEN Breaker Rating Module (an optional module of
ASPEN OneLiner) to evaluate the adequacy of the breaker interrupting
rating.
4. Press OK.
The dialog box will disappear and a new bus will appear at the location
you selected in step 2.
5. Press the <Esc> key on your keyboard to exit from the Add-Equipment
mode.
The mouse cursor will change back to the normal arrow cursor.
GETTING AROUND
Your computer monitor usually can display only a portion of your system's one-line diagram. OneLiner has
several features that let you to navigate from one part of the system to another:
Find Bus: Move the viewport to the location of a given bus. This can be
accomplished by using either the bus name or number.
Scroll: Move the viewport horizontally or vertically.
Zoom: Show the one-line diagram in the viewport with different
magnifications.
Split Screen: View the one-line diagram in two different panes at the same
time.
These features are described in the following sections.
Note: You can also press the F key on the keyboard to bring up this
dialog box.
3. Click on the name California 33. kV 26 in the list box.
The number 26 is the bus number.
4. Press OK.
A big green arrow will appear next to the bus.
Note: You can locate a bus by its number by selecting the Find Bus By
Number command in step 2.
SCROLLING TO VIEW DIFFERENT SECTIONS OF THE NETWORK:
1. Scroll the one-line diagram vertically and horizontally by clicking the mouse
on the scroll bars of the window or by dragging the scroll bar button.
If you have a mouse with a wheel, rotating the wheel will scroll the
one-line diagram vertically. Also, moving the mouse with the wheel
pressed down will cause the viewport to move with the mouse.
Note: If the network disappears, use the Find Bus command mentioned
above.
2. Now while holding the left mouse button down, drag the double bars to the
center of the screen.
The viewport will now be split into two panes.
The active pane will have a yellow tint at the bottom of the screen. You
can now scroll the two sections and modify each independently.
Note there are four fault types within the Phase Connection group box:
3LG: Three-phase fault. 1LG: Single phase to ground fault.
2LG: Two phase to ground fault. L-L: Line to line fault.
The 1LG check box should already been marked.
5. Press Simulate.
A dialog box will appear asking you to specify branch outages.
The bus voltages are shown directly beneath the bus names and nominal
kV. The branch currents are shown on the branch symbols. Both the
voltage and the current will be displayed as complex numbers in polar
coordinates. The zero-sequence quantities are displayed by default for a
Notice the '3' in the 'No. of tiers' edit box. This tells OneLiner that you
want to see the solution for all the equipment within three buses back
from the fault.
9. Click Phase a" radio button to display the phase 'a' voltages and currents.
The radio button labeled "Physical" at the lower-left corner is highlighted
(by default) to indicate that the voltages will be in units of kV line-to-
ground, and the currents in amperes.
10. Press Display.
The dialog box will disappear. The one-line diagram will be refreshed to
show the phase 'a' currents and voltages. Note the letter 'A' between the
magnitude and angle of the branch currents.
The '0', '+', and '-' buttons are for displaying the zero-, positive- and
negative- sequence quantities, respectively. The 'A', 'B' and 'C' buttons
are for displaying the phase 'A', phase 'B' and phase 'C' quantities. The
button that resembles a 'clock' is used for displaying the relay operating
times.
Click on the 'B' shortcut button to display the phase 'B' quantities.
The one-line diagram will be re-drawn showing the phase 'B' quantities.
12. View the fault summary in text.
OneLiner always prepares a summary for the fault being displayed. The
summary includes the fault MVA, the fault current, the relay current, the
Thevenin impedance, the x/r ratio, and the voltage at both ends of the
relay branch. You can see this summary by opening the TTY Window.
Click on the TTY button on the toolbar.
The TTY Window will appear. You will see the last part of the summary
when the window opens. You can click on the scroll bars of this window
to bring the other parts of the summary into view.
Right click on the dialog box and select Phasor properties from the
popup menu to see all the different options that you can set for the
phasor display.
Click on the red X button on the top right corner of the dialog box.
The phase-probe dialog box will disappear.
The fastest relay time in each relay group is displayed above the relay-
group symbol. The operating time is preceded by the symbol:
'FU' if it is from a fuse.
'OG' if it is from an overcurrent ground relay.
'OP' if it is from an overcurrent phase relay.
'RG' if it is from a ground recloser.
'RP' if it is from a phase recloser.
'ZG1', 'ZG2', 'ZG3' or 'ZG4' if it is from a ground distance relay. The
numbers 1, 2, 3 and 4 are the zone numbers.
'ZP1', 'ZP2', 'ZP3' or 'ZP4' if it is from a phase distance relay. The
numbers 1, 2, 3 and 4 are the zone numbers.
The words 'No active relay' are shown if there are no relays of the type
being displayed within the relay group. The quantity '9999s' is shown if
none of the relays of the type being displayed has operated.
3. Click on the entry 'OC ground relay NV-G1' in the list box.
Click on the "OK" button.
The Curves Window will appear showing the characteristics of the
overcurrent relay NV-G1. The relay parameters will be shown inside a
box to the right of the plot.
4. We will add the curves of several neighboring relays to this plot.
Select the Add | Relay Curves command.
A dialog box will appear asking you to select the relay curves to be added
to the plot. The list box labeled "Relays in Vicinity" contains the relays
that are in the vicinity of the relay being displayed.
5. Increase the No of tiers to 1. Select the entries for NV Fuse, NV-G2 and
RE-G1 in the list box by marking the check box in front of each name.
Click on 'Hatch' within the Fuse Curves box to fill in the area
between the total clear and minimum melt curves.
Click on 'Decades only' within the Grid Style box to display only the
decade lines on the Curves Window.
Click on "OK" to close the Misc. | Options dialog box.
The Curves Window should appear as shown below.
3. Click on the up arrow of the vertical scroll bar to increase the time dial
setting.
The time dial value is shown below the scroll bar. As you click on the
scroll bar, the time dial value, as well as the relay's time delay, will
change.
2. Click once on the file name EXAMPLE.DXT in the list box. Press Open.
The dialog box will disappear. After a brief pause during which OneLiner
reads and process the text data file, you will see a blank Main Window.
A message box will appear informing you that 7 buses have been read in
and none are visible now.
Press OK.
The bus WOODSIDE 115 kV will appear at the position of your last
mouse click. The generator at this bus is automatically added by
OneLiner. Its neighboring buses MTN. VIEW 115 kV and SANTA
CLARA 115 kV are also automatically placed.
OneLiner will add four lines, representing the four branches, between
WOODSIDE 115kV and its neighboring buses. As a general rule,
OneLiner will automatically add the generator, load and shunt at the new
buses, as well as all the branches between them and the buses that are
already on the screen.
Note the bus symbol for WOODSIDE is solid, while the symbols for its
neighbors are hollow. A solid bus symbol means all the neighbors of that
bus are visible on the screen. A hollow symbol means one or more
neighbors remain hidden.
Tidy up the one-line diagram by dragging the symbols with the
mouse. Use the picture below as a guide.
Press OK.
The buses PALO ALTO and MENLO PARK will appear on the screen.
6. Place remaining buses by repeating step 5.
Use the diagram on this page as a guide for the placement of the buses.
After the last bus is placed on the screen, a message box will appear,
informing you that the one-line diagram has been completed.
Press OK.
There is also an Export Network command, which creates a text data file
based on the network data stored in the binary data file. The exported
text data file can be in ASPEN format or one of the following foreign
formats: PTI PSS/E format, GE PSLF and short-circuit format, ANAFAS
format or ANAREDE format.
7. Select Output to text file" in the drop-down combo box. Press OK.
The standard save-file dialog box will appear.
Use controls in the standard file-save dialog box to specify the output file
name SAMPLE30.txt, and click on "Save".
When the simulation and file output are complete, the Progress dialog
box will disappear and the Main Window will report that 4 faults were
written successfully to the file C:\ASPEN\IEEE30.txt.
You will see this message box.
A dialog box will appear asking you to specify the initiating fault at t=0.
Press the forward button on the toolbar to view the next event.
When you reach the last event (event no. 5), the one-line diagram will
look like this.
TO EXPLORE FURTHER
This tutorial covered only a small subset of the commands in OneLiner. You can find a detailed description of
all the commands in Section 3 of the on-line help. You may also read Section 4 to see how OneLiner models the
various network elements. Finally, you may wish to browse through the appendices, which cover a wide range
of topics that include the solution method and techniques for transformer modeling.
You can find tutorials for the ASPEN Overcurrent Curve Editor and the ASPEN Distance Relay Editor in
Section 2 of the respective User's Manual. (Not included in the Working Model.)