Sie sind auf Seite 1von 10

IEEE TRANSACTIONS ON CONTROL SYSTEMS TECHNOLOGY, VOL. 23, NO.

1, JANUARY 2015 27

Wide-Area Damping Controller for Power System


Interarea Oscillations: A Networked
Predictive Control Approach
Wei Yao, Member, IEEE, Lin Jiang, Member, IEEE, Jinyu Wen, Member, IEEE,
Qinghua Wu, Fellow, IEEE, and Shijie Cheng, Fellow, IEEE

Abstract Wide-area damping controller (WADC) requires transfer capability (ATC) of the tie-lines between different
communication networks to transmit remote signals. The usage power control areas [1], [2]. The interarea oscillations often
of communication networks will introduce time delays into the suffer from poor damping since power systems generally
control loop of the WADC. Ignoring this time delay would
deteriorate the damping performance provided by the WADC operate closely to their maximum ATC under deregulated
or even cause the whole system instability. This paper employs electricity market environment [3]. Therefore, they should be
networked predictive control (NPC) to design a WADC for effectively damped. Traditionally, they are damped together
the generator exciter to enhance the damping of interarea with the local mode oscillations by tuning power system
oscillations in a large-scale power system. The NPC incorporates stabilizers (PSSs) installed on the excitation systems of
with a generalized predictive control (GPC) to generate optimal
control predictions, and a network delay compensator to detect the synchronous generators or designing decentralized local
and compensate both constant and random delays. Moreover, controllers [2], [4]. However, the effectiveness of such
model identification is used to obtain an equivalent reduced- controllers to damp interarea oscillations is limited because
order model of the large-scale power system and deal with interarea modes are not always controllable or observable
the model uncertainties and variation of operating conditions. or both from the local signals [5]. With the development
Case studies are based on the New England 10-machine 39-bus
system. Effectiveness of the proposed WADC is verified by of wide-area measurement system (WAMS) and deploy-
simulation studies and compared with a conventional WADC and ment of synchronized phasor measurement units, wide-area
a GPC-based WADC without delay compensation. damping controllers (WADCs) based on remote signals have
Index Terms Delay compensation, interarea oscillations, been proposed to enhance the damping of the interarea
model identification, networked predictive control (NPC), oscillations [5][8].
wide-area damping controller (WADC). The implementation of WADC requires communication
channels to transmit remote signals, which introduce time
I. I NTRODUCTION
delays into the control-loop of the WADC [9], [12]. These

A S ONE of the main concerns of a power system small


signal stability, interarea oscillations greatly influence the
reliable and economical operation of the large-scale intercon-
time delays can typically range from tens to several hundred
milliseconds, depending upon the type of communication
channels, routines of signal transmission, transmission pro-
nected power systems because they would limit the available tocols, and communication loads [9][11], [13]. As the time
delays would degrade system damping performance or even
Manuscript received August 9, 2013; revised December 5, 2013; accepted
February 25, 2014. Date of publication March 31, 2014; date of current version cause system instability, they must be taken into account
December 15, 2014. Manuscript received in final form March 12, 2014. This during the design of the WADC [14]. Another challenge of
work was supported in part by the National Natural Science Foundation designing a WADC is the availability of an accurate model of
of China under Grant 51207063, in part by the National High Technology
Research and Development of China under Grant 2011AA05A119, and in the large-scale power system, because of model uncertainties
part by the Engineering and Physical Sciences Research Council of U.K. of a large number of components and variation of operating
under Grant EP/J014249/1. Recommended by Associate Editor P. Korba. conditions [15].
W. Yao is with the State Key Laboratory of Advanced Electromagnetic Engi-
neering and Technology, Huazhong University of Science and Technology, Time delays and model uncertainties have been taken into
Wuhan 430074, China, and also with the Department of Electrical Engineering account in the design/synthesis of the WADC. The existing
and Electronics, The University of Liverpool, Liverpool L69 3GJ, U.K. research results can be mainly classified into the following
(e-mail: w.yao@hust.edu.cn).
L. Jiang and Q. H. Wu are with the Department of Electrical Engineering two categories. The first one is to apply the robust control
and Electronics, The University of Liverpool, Liverpool L69 3GJ, U.K. methods to handle the model uncertainties. Among these
(e-mail: ljiang@liv.ac.uk; qhwu@liv.ac.uk). results, some of them did not consider the impact of the
J. Wen and S. Cheng are with the State Key Laboratory of Advanced
Electromagnetic Engineering and Technology, Huazhong University of Sci- time delays at the design stage [15][19], whereas most
ence and Technology, Wuhan 430074, China (e-mail: jinyu.wen@hust.edu.cn; of them treated the delays as part of system uncertainties
sjcheng@hust.edu.cn). [20][24]. The second one considers the compensation of
Color versions of one or more of the figures in this paper are available
online at http://ieeexplore.ieee.org. communication delays at the design stage, such as a smith
Digital Object Identifier 10.1109/TCST.2014.2311852 predictor-based H controller [21], [22], recurrent neural
1063-6536 2014 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
28 IEEE TRANSACTIONS ON CONTROL SYSTEMS TECHNOLOGY, VOL. 23, NO. 1, JANUARY 2015

network-based adaptive WADC [25], stochastic subspace


identification-based adaptive WADC [26], and fuzzy-logic
control-based WADC [27]. Most of these results handle
constant delays with a known upper-bound, whereas random
delays and data unavailability caused by data packet drop
or physical failure of communication channels have not
been investigated. For compensating constant and time-
varying delays, an adaptive phasor power oscillation damping
controller [28] and a delay-dependent state feedback WADC
based on Lyapunov stability theory and linear matrix inequal-
ities technique [12] have been proposed. However, the design Fig. 1. Scheme of the NPC.
of the WADC proposed in [12] is based on the accurate
linearization model of a large-scale power system, which is not
easily available and the linearization may cause extra errors. data packet drop, disordering into the control loop, they also
Based on the rapid development of communication networks offer one main advantage that a group of data is transmitted in
in the last two decades, networked control systems (NCS) have a packet at one transmission. The NPC takes advantage of this
emerged as a new type of spatially distributed control system, feature and transmits the optimal control prediction sequence
in which sensors, actuators, and controllers are connected obtained by the GPC to the plant side, then employs an
through a shared digital communication network with limit NDC to identify time delays and determine the corresponding
bandwidth [29]. In terms of the control system, the large- control prediction. Model identification is used to deal with
scale power system equipped with the WADCs is a typical model uncertainties and provide an adaptive predictive model
NCS because of the involvement of communication channels for GPC.
in the control loop [12], [34]. To tackle those challenges At each control step, the current control prediction
introduced by communication networks, such as time delays sequence, together with time stamp, are transmitted in one
and data packet drops, networked predictive control (NPC) packet from the controller side to the plant side. At each
has been proposed as one of the effective control algorithms sampling step, the current and the past several steps of
as it can simultaneously provide online optimal control and measurements will be sent in one packet with time stamp from
compensation of delays [30][32]. the measurement side to the controller side. The buffer will
This paper investigates the design of a new WADC only be updated if a packet with a new time stamp is received.
for a selected generator exciter based on NPC, so-called This case probably happens because of packet disordering.
NPC-WADC, to enhance the damping of interarea oscillations Compared with the conventional GPC, which only uses the
and provide active compensation of delays in the control first step of the control prediction, the NPC utilizes all steps
loop. Moreover, model identification technique is adopted of the control prediction.
to obtain an equivalent low-order model for the prediction
model of the NPC. This paper extends [33] and [34], in A. Generalized Predictive Control
which model identification and generalized predictive control Future optimal control sequence is obtained by the GPC
(GPC) are employed to design an adaptive GPC-based WADC and based on a controlled autoregressive and moving average
(GPC-WADC) [33] and the preliminary result about (CARMA) model [36], [37] shown as follows:
NPC-WADC design as well as its verification on a simple
four-machine power system is given in [34]. A(z 1 )y(t) = B(z 1 )u(t 1) + C(z 1 )e(t) (1)
The remainder of this paper is organized as follows. where y(t) and u(t) are the output and input of the system,
Section II briefly recalls the NPC and model identification respectively. A(z 1 ) R[z 1 , n a ], A(z 1 ) = a0 + a1 z 1 +
methods. The design procedure of the proposed NPC-WADC + ana z na and a0 = 1, B(z 1 ) R[z 1 , n b ], B(z 1 ) =
is given in Section III. In Section IV, a case study based on the b0 + b1 z 1 + + bnb z nb . For simplicity, it is assumed that
New England 39-bus system is carried out to demonstrate the e(t) is white noise giving C(z 1 ) = 1. Details of the GPC
effectiveness of the NPC-WADC. Finally, Section V presents based on CARMA model are not described in this paper [36].
the conclusions. At the tth sampling instant, delay in the feedback channel
is tsc , then the plant outputs y received at the controller side
II. C ONTROL M ETHODOLOGIES is y(t tsc ). The design of WADC for power systems is a
regulation problem. Thus, the quadratic cost function to be
This section will briefly present the NPC scheme [30][32] minimized is defined as follows:
and a model identification algorithm based on recursive least-
j =N
squares (RLS) with a variable forgetting factor [34], [35].
J (N, Nu ) = E 
y(t tsc + j |t tsc )2
The configuration diagram of an NPC combined with model
j =1
identification is shown in Fig. 1, which includes three main
components: 1) GPC; 2) network delay compensator (NDC); j=Nu
and 3) online model identifier. Although communication + r j u(t tsc + j 1|t tsc )2 (2)

networks introduce new challenges, such as time delay, j =1
YAO et al.: WADC FOR POWER SYSTEM INTERAREA OSCILLATIONS 29

where E{.} is the expectation operator, and  y(t tsc + j |t tsc ) This method can measure both constant and random delays
is an optimal j -step ahead prediction of the system output at as it does not rely on the type and traffic condition of
time t tsc . N is the prediction horizon, u(t tsc + j 1| the communication networks. Note that GPC without delay
t tsc ) is an optimal j -step ahead prediction of the system compensation will use the first step of control from the current
input at time t tsc , Nu is the control horizon, and r j is control available control prediction, i.e., u(t) = u(ts |ts ).
weighting sequence and usually defined as a constant value,
r j = r , for j = 1, 2, . . . , Nu . C. Online Model Identification
By solving the Diophantine equations,  y(t tsc + j |t tsc )
As a large-scale power system is a complex, nonlinear, and
is obtained as follows:
high-order dynamic system, it is difficult to obtain its full-
y(t tsc + j |t tsc) = G j (z 1 )u(t tsc + j 1|t tsc ) + f j (3)
 scale detailed model. However, for the design of a damping
controller, a low-order equivalent linear model, whose struc-
where G j (z 1 ) is an unique polynomials of order j 1, ture is fixed and parameters vary with the operating conditions,
f j = F j (z 1 )y(t tsc ) + H j (z 1 )u(t tsc 1).
is accurate enough and can be estimated by a RLS algorithm
The N j-ahead predictions can be represented by the with a varying forgetting factor [35]. For CARMA model
following matrix equation:
shown in (1), the algorithm can be written as
Y = GU + f (4) (t) = y(t) T (t)
(t 1)
, G, U , and f are denoted in the Appendix in
Y K (t) = P(t 1)(t)/[1 + T (t)P(t 1)(t)]
detail. 
(t) = 
(t 1) + K (t)(t)
In practice, the constraints of the control signal should be
considered and can be expressed as follows: (t) = 1 [1 (t)T K (t)](t)2 /0
P(t) = [I K (t) T (t)]P(t 1)/(t) (11)
I Umin U I Umax (5)
where  (t) = [a1 , . . . , ana , b0 , . . . , bnb ]T is the estimated
where Umin and Umax denote the lower and upper limits of parameter vector. (t) = [y(t tsc 1), . . . , y
the control signal. I denotes the Nu identity vector. (t tsc n a ), u(t tsc 1), . . . , u(t tsc n b 1)]T
According to (2), (4), and (5), the implementation of denotes the measurement vector. P(t) is the covariance
GPC with bounded signals can be represented as a quadratic matrix, I is an identity matrix, K (t) is the adjustment gains,
programming (QP) problem, which can be stated as 0 < < 1 is the forgetting factor used to progressively reduce
1 T the effects of old measurements, and 0 is the preselected
min J (U ) = U H U + bT U + f0 constant. In addition, moving boundaries are introduced for
2
s.t. AqpU bc (6) every parameter to protect the parameters from large modeling
errors, which are caused by a variety of sudden disturbances
where H = 2(G T G+ R), R = diag[ r1 , r2 , . . . r Nu ],
in the power system [34].
b = 2 f T G, f 0 = f T f , Aqp = [T, T ]T , and bc =
[I Umax , I Umin ]T . T is the identity matrix.
III. D ESIGN P ROCEDURE OF THE NPC-WADC
The optimal future Nu steps control vector U can
be obtained by solving the above QP problem. Then, U are The selection of the wide-area stabilizing signals and con-
packed together with a time stamp t tsc and sent to the plant trol location plays an important role in the design of the
side. WADC [18], [41]. Modal controllability/observability-based
approaches have been often used to select location and a
suitable feedback signal for the WADC, such as residues
B. Network Delay Compensator
approach [5] and geometric approach [38]. As the comparison
The NDC determines the time delay and chooses the cor- results of this two approaches provided in [40] show that
responding control prediction. All time delays existing in the the damping controller using the signals recommended by the
closed-loop are defined as a round-trip time (RTT) delay in geometric approach can always obtain the best robustness and
the feedback loop as follows [32]: performances, the geometric approach is also adopted to select
tr = tsc + tc + tca (7) the wide-area stabilizing signals and control location for the
WADC in this paper.
where tr is the RTT delay, tsc is the delay of the feedback The configuration of a large-scale power system equipped
channel, tca the delay of the forward channel, and tc is the with an NPC-WADC is shown in Fig. 2. The selected wide-
processing time of the controller. By comparing the current area signals y(t) are measured via the WAMS and sent to
time t at the controller side with the time stamp ts at the the WADC installed at the selected generator as the input
latest control packet U (ts ), the RTT and current control u(t) signal through communication networks. The proposed WADC
can be obtained as adopts a structure similar with [5] and [33]. The conventional
PSS with the local rotor speed as the input and u l as the
tr = t ts (8)
output signal, is designed to provide damping for local mode
U (ts ) = [u(ts |ts ) u(ts + 1|ts ) u(ts + Nu 1|ts )] (9) oscillations, whereas the output signal u g of the WADC is
u(t) = u(ts + tr |ts ) = u(t|ts ) (10) added to the excitation system of the selected generator to
30 IEEE TRANSACTIONS ON CONTROL SYSTEMS TECHNOLOGY, VOL. 23, NO. 1, JANUARY 2015

Fig. 2. Configuration of the generator equipped with a local PSS and an


NPC-WADC.

damp the interarea mode oscillation. tca = 0 as the WADC is


installed at the generator side.
Detailed steps of design an NPC-WADC are summarized as
follows. Fig. 3. New England 10-machine 39-bus power system.
Step 1: Carrying out modal analysis of the detailed nonlinear
TABLE I
model based on MATLAB/SIMULINK and selecting the wide-
area feedback control signal and the generator to install the C LASSIFICATION OF O SCILLATION M ODES OF THE T EST

WADC, using geometric approach [18], [38]. S YSTEM (W ITH PSS M EANS G1, G3, G4, G7, G8,
AND G9 E QUIPPED W ITH PSS)
Step 2: Determining the order of the reduced-order model
of the power system, excluding the WADC using the Schur
balanced truncation method, based on the frequency response
in the frequency range of interarea oscillation [14].
Step 3: Based on the model order determined in Step 2, the
low-order equivalent model is obtained via model identifica-
tion algorithm and used as the prediction model for the NPC.
Step 4: Design of NPC-WADC using the model obtained
in Step 3 as the prediction model and choosing the following
parameters: 1) the output prediction horizon N; 2) the control
horizon Nu , N > Nu ; 3) the weighting sequence r ; and
4) sampling period Ts . For effective compensation of the
time delays, Nu should be larger than the maximal RTT A. Modal Analysis
communication delays. The nonlinear model of the New England 39-bus power
Step 5: Simulation studies are carried out based on the system is linearized at a nominal operating condition [39].
detailed nonlinear model, under different faults and vari- The classification results of oscillation modes of this test
ous operating conditions, to verify the effectiveness of the system without PSS and with several PSSs are given in
NPC-WADC and compare it with the GPC-WADC without Table I. Since the test system without PSS has two modes with
delay compensation and the conventional lead-lag WADC. negative damping ratios, several PSSs are added to generators
to improve the stability of the system. It can be found that
IV. C ASE S TUDY this system with several PSSs still has several local and
interarea modes whose damping ratios are <0.1. Modes 13
To demonstrate the effectiveness of the NPC-WADC, case
are interarea modes, whereas Modes 49 are local ones.
study is based on the New England 10-machine 39-bus system,
Compared with the Mode 1, Modes 29 have relatively higher
as shown in Fig. 3. This test system consists of 10 machines,
frequencies and larger damping ratios, thus it is not necessary
39 buses, and 46 lines, and its detailed parameters are given
to provide supplementary damping to these modes [28]. There-
in [39]. It has been widely used as a test benchmark for
fore, the WADC should be designed to provide damping for
studying the low-frequency oscillations as it performs several
the critical Mode 1, as it has smallest damping ratio 0.0442
interarea modes under disturbances or faults. Each of the gen-
and lowest oscillation frequency 0.6273 Hz.
erators is represented by a fourth-order model and equipped
with an IEEE ST1A excitation system. The transmission
B. Location of WADC and Selection of Wide-Area Signals
system is modeled as a passive circuit, whereas the loads
are considered as constant impedances. The output of the To determine controller location and wide-area feed-
mechanical power of each generator is treated as a constant back signals, geometric measures of modal controllabil-
value for simplicity. ity/observability are used to evaluate the relative strength
YAO et al.: WADC FOR POWER SYSTEM INTERAREA OSCILLATIONS 31

Fig. 4. Geometric controllability/observability associated with Modes 13. Fig. 5. Responses to fault Scenario I, without communication delay.

of candidate signals and the performance of controllers at compared with the GPC-WADC [33] and the conventional
different locations with respect to a given interarea mode WADC (CWADC) [5]. The GPC-WADC and NPC-WADC
[18]. The geometric controllability/observability associated use same parameters for the GPC part. The main difference
with different interarea modes is shown in Fig. 4. Note that between them is the NPC-WADC uses the N-step forward
the number of transmission lines is given in [39]. The WADC control prediction to compensate the communication delay
should be located on the generator, which has larger geometric existing in the control-loop, whereas the GPC-WADC only
controllability with respect to the mode concerned, whereas uses the first step control prediction. In addition, the transfer
smaller geometric controllability with respect to other modes function of the CWADC is given as follows:
in order to reduce the effect on other modes. Therefore, G4 is

selected as controller location. Similarly, it can be found that 10s 1 + 0.6280s 3
HWADC(s) = 0.01 (12)
active power of the transmission line 7 (P318 , line between 1 + 10s 1 + 0.1025s
bus 3 and bus 18) has the largest geometric observability with Simulation studies are carried out based on the detailed
respect to Mode 1 and smaller geometric observability with nonlinear model to verify the effectiveness of the proposed
respect to Modes 2 and 3. Hence, deviation of P318 is chosen NPC-WADC under a wide range of operating conditions
as the wide-area feedback signal for the proposed WADC. and different constant and random communication delays.
The following two scenarios are considered.
C. Design of NPC-WADC Scenario I: A three-phase-to-ground fault (fault F1 shown
Using the model reduction techniques given in [14], the in Fig. 3) occurs at the end terminal of line between bus 3
order of the equivalent model is chosen to be n a = 7 and and 4 near bus 3 at t = 0.5 s, followed by switching off the
n b = 7 since this model is enough accurate for design faulty transmission line at t = 0.6 s.
of WADC. Based on the general guidelines given in [35], Scenario II: A three-phase-to-ground fault (fault F2 shown
parameters of the online identifier are chosen as: 1) 0 = 0.2; in Fig. 3) occurs at the end terminal of tie-line between bus
2) T = 10; and 3) = 0.02. The wide-area signal P318 15 and 16 near bus 15 at t = 0.5 s, followed by switching off
(p.u.) is scaled to 0.1P318 . A washout filter is added to the faulty tie-line at t = 0.6 s.
eliminate constant deviation of P318 when the operating Note that the test system operates at a new operating point
condition of the system is changed. during the postfault period because of the outage of the faulty
For the NPC-WADC, the sampling period Ts = 100 ms is transmission line, and the Scenario II represents a larger
obtained based on the frequency range of the critical interarea change of operating conditions.
mode. As the range of the communication delays introduced
from WAMS vary from tens to several hundreds milliseconds,
Nu = 12 is chosen to compensate the delays less than D. Without Communication Delays
Nu Ts = 1.2 s. As prediction horizon N is usually larger System responses to fault Scenario I without communication
than Nu , N = 25 is used. The desired response can be delays are shown in Fig. 5. Responses of active power of
achieved by setting weighting sequence r = 0.3. To avoid the transmission line P318 and P1718 are presented as they
excessive interference of the local control mode, the output of illustrate the oscillation behavior of the Mode 1. It reveals
the WADC is limited to 0.1 p.u. [34]. that the NPC-WADC provides slightly better damping perfor-
Effectiveness of the proposed NPC-WADC is verified by mance than the CWADC. Note that the GPC-WADC provides
simulation studies based on MATLAB/SIMULINK software, the same damping performance with NPC-WADC, because
32 IEEE TRANSACTIONS ON CONTROL SYSTEMS TECHNOLOGY, VOL. 23, NO. 1, JANUARY 2015

Fig. 6. Identified parameters A(z 1 ).


Fig. 8. Responses to measurement noise under fault Scenario I, adding white
noise with magnitude 0.05 p.u. (5 MW) in feedback signal P318 .

Fig. 7. Identified parameters B(z 1 ).

Fig. 9. Responses to fault Scenario I, with 100 ms constant delay.


the only difference between NPC-WADC and GPC-WADC is
that the NPC-WADC has an NDC.
The identified parameters of the prediction model are shown
in Figs. 6 and 7. It shows that the identified parameters update
fast enough to track the dynamic of the power system and then
converge to a new operating condition.
In addition, since there always exists the measurement
noise in a real system, the performance of the proposed
NPC-WADC in case of measurement noise is verified by
adding white noise with magnitude of 0.05 p.u. (5 MW) into
the feedback signal P318 . System response to fault Scenario I
is shown in Fig. 8. It reveals that the proposed WADC can still
provide a good damping performance in case of measurement
noise.

E. With Constant Communication Delays


System responses to fault Scenario I with two different
constant delays 100 and 200 ms are shown in Figs. 9 and 10, Fig. 10. Responses to fault Scenario I, with 200 ms constant delay.
respectively. From the two figures, it can be observed that the
CWADC cannot maintain the stability of the whole system time delay reaches 200 ms. However, at both cases, the
when the time delay reaches 100 ms, whereas the GPC-WADC NPC-WADC can maintain the stability of the whole system,
cannot provide satisfactory damping performance when the which demonstrate its ability of compensation the time delays.
YAO et al.: WADC FOR POWER SYSTEM INTERAREA OSCILLATIONS 33

Fig. 11. Responses to fault Scenario I, with different constant delays.

The responses under larger time delays, 400, 600, and


800 ms, are also given in Fig. 11. It is found, with
larger delays, NPC-WADC can still provide satisfactory
damping performance and compensate the delay effectively.
Responses provided by CWADC and GPC-WADC are not
presented because both of them cannot maintain the stability
of the whole system. In addition, it also can be found that the
NPC-WADC under different constant communication delays
provides almost the same damping performance.

F. With Random Communication Delays


With random communication delays distributing between
200 and 600 ms, the system responses to fault Scenario I
are shown in Fig. 12. It can be found that the identified
value of the RTT delays tr varies from three-step to six-step
delays (note that sampling period Ts = 100 ms). The NDC
will choose the corresponding control prediction according
to the value of tr at each control step. It is shown that the
NPC-WADC can damp the interarea oscillation effectively,
whereas the GPC-WADC cannot maintain the stability of the
whole system.

G. Delay Margin of NPC-WADC Fig. 12. Responses to fault Scenario I, with 200600 ms random delays.

The responses of the test system installed with NPC-WADC


as 1700 ms (i.e., 17-step delays). Note that when the value of
in presence of longer time delays are shown in Fig. 13. It is
delays is increased, the damping performances provided by
found, when the time delay is under 1200 ms, NPC-WADC
the NPC-WADC degrade slightly due to the inaccuracy of the
performs better than without WADC, whereas the NPC-WADC
identified model and prediction.
cannot handle the constant delays, which are bigger than
Due to the combination of the model identification
1500 ms. This is because that the control prediction horizon
algorithm and NPC, the calculation of delay margin of a power
Nu = 12 and the sampling interval is 100 ms.
system equipped with an NPC-WADC is a challenge task via
The maximal delay with which NPC-WADC can com-
the method reported in [14] and will be investigated here only
pensate is limited by the control prediction horizon Nu .
via simulation studies.
By increasing the values of Nu and the corresponding predic-
tion range N, the delay handled by NPC-WADC will increase.
To test this capability, Nu = 17 is chosen. The system H. Different Operating Conditions
responses with large delays are shown in Fig. 14. It reveals that System response to fault Scenario II, which causes large
NPC-WADC can still work properly when the delay is as large variation of operation conditions after the outage of the faulty
34 IEEE TRANSACTIONS ON CONTROL SYSTEMS TECHNOLOGY, VOL. 23, NO. 1, JANUARY 2015

Fig. 13. Delay margin of NPC-WADC with Nu = 12, under fault Scenario I. Fig. 15. Responses to fault Scenario II, without communication delays.

Fig. 14. Delay margin of NPC-WADC with Nu = 17, under fault Scenario I. Fig. 16. Responses to fault Scenario II, with different communication delays.

tie-line between bus 15 and 16, and without communication effort to achieve better performance than the CWADC even
delays are considered, is shown in Fig. 15. It is observed without the time delays.
that the NPC-WADC effectively damps the power oscillations,
whereas the CWADC cannot maintain the whole system sta- V. C ONCLUSION
bility due to the large change of operation condition caused
by the outage of tie-line between bus 15 and 16. Furthermore, A WADC has been proposed based on NPC and model
system responses to fault Scenario II with 300- and 500-ms identification technique for enhancing the damping of power
constant communication delays are also given in Fig. 16. system interarea oscillations and improving power system
It reveals that the oscillations are well damped because stability. The proposed NPC-WADC can effectively damp
the NPC-WADC compensates the communication delays interarea oscillations and actively compensate time delays in
effectively. the wide-area feedback signals. Moreover, model identifica-
tion has been applied to deal with model uncertainties of
the large-scale power systems and obtain a reduced-order
I. Comments equivalent prediction model for the NPC-WADC. Detailed
Simulation results show that the NPC-WADC can provide design procedures of the NPC-WADC have been given and
better damping performance than the CWADC. However, it is demonstrated via case studies based on the New England
worth pointing out that the NPC-WADC has a more complex 10-machine 39-bus system, comparing with the GPC-WADC
structure and thus requires more computation time than the without delay compensation, conventional lead-lag WADC
CWADC. Moreover, the NPC-WADC requires more control and only local PSSs without WADC. Simulation results
YAO et al.: WADC FOR POWER SYSTEM INTERAREA OSCILLATIONS 35

demonstrate that the NPC-WADC can damp out the concerned [7] Y. Chompoobutrgool, L. Vanfretti, and M. Ghandhai, Survey on power
critical interarea oscillation and compensate constant and system stabilizers control and their prospective applications for power
system damping using synchrophasor-based wide-area systems, Eur.
random delays effectively under a wide range of operating Trans. Electr. Power, vol. 21, no. 8, pp. 20982111, Nov. 2011.
conditions. The necessity of considering the impact of delays [8] S. Zhang and V. Vittal, Design of wide-area power system damping
at the design stage of a WADC has also been revealed as controllers resilient to communication failures, IEEE Trans. Power
Syst., vol. 28, no. 24, pp. 42924300, Nov. 2013.
damping performance provided by a WADC under delays [9] B. Naduvathuparambil, M. C. Valenti, and A. Feliachi, Communication
may be even worse than that of a system without installing delays in wide area measurement systems, in Proc. 34th Southeastern
a WADC. In addition, simulation results also verify the Symp. Syst. Theory, 2002, pp. 118122.
[10] J. W. Stahlhut, T. J. Browne, G. T. Heydt, and V. Vittal, Latency viewed
NPC-WADC can coordinate with local PSSs and to adapt to as a stochastic process and its impact on wide area power system control
variation of operating conditions. Future works will focus on signals, IEEE Trans. Power Syst., vol. 23, no. 1, pp. 8491, Feb. 2008.
the design of a multiple input multiple output NPC-WADC [11] K. Tomsovic, D. E. Bakken, V. Venkatasubramanian, and A. Bose,
Designing the next generation of real-time control, communication,
to damping multiple interarea oscillations in the large-scale and computations for large power systems, Proc. IEEE, vol. 93, no. 5,
interconnected power system. pp. 965979, May 2005.
[12] S. Wang, X. Meng, and T. Chen, Wide-area control of power system
through delayed network communication, IEEE Trans. Control Syst.
A PPPENDIX Technol., vol. 20, no. 2, pp. 495503, Mar. 2012.
[13] C. H. Hauser, D. E. Bakken, and A. Bose, A failure to communicate:
Definitions of symbols of (4) are as follows: Next-generation communication requirements, technologies, and archi-
tecture for the electric power grid, IEEE Power Energy Mag., vol. 3,
y(t tsc + 1|t tsc ) no. 2, pp. 4755, Apr. 2005.
Y = [14] W. Yao, L. Jiang, Q. H. Wu, J. Y. Wen, and S. J. Cheng. Delay-
y(t tsc + N|t tsc ) dependent stability analysis of the power system with a wide-area
damping controller embedded, IEEE Trans. Power Syst., vol. 29, no. 1,

u(t tsc |t tsc ) pp. 233240, Feb. 2011.
U = [15] H. Ni, G. T. Heydt, and L. Mili, Power system stability agents using
robust wide area control, IEEE Trans. Power Syst., vol. 17, no. 4,
u(t tsc + Nu 1|t tsc ) pp. 11231131, Nov. 2002.
 T [16] I. Kamwa, R. Grondin, and Y. Hebert, Wide-area measurement based
f = f1 f2 f N stabilizing control of large power systemsA decentralized/hierarchical
approach, IEEE Trans. Power Syst., vol. 16, no. 1, pp. 136153,

g0 0 0 Feb. 2001.
.. .. . .. .. [17] F. Okou, L. A. Dessaint, and O. Akhrif, Power system stability
. . . enhancement using a wide area signals based hierarchical controller,

g Nu 1 g Nu 1 g0 IEEE Trans. Power Syst., vol. 20, no. 3, pp. 14651477, Nov. 2005.
G = [18] Y. Zhang and A. Bose, Design of wide-area damping controllers

g Nu g Nu s1 for interarea oscillations, IEEE Trans. Power Syst., vol. 23, no. 3,
.. .. . . .. pp. 11361143, Aug. 2008.
. . . . [19] Y. Pipelzadeh, B. Chaudhuri, and T. C. Green, Control coordination
g N1 g N2 s NNu within a VSC HVDC link for power oscillation damping: A robust
decentralized approach using homotopy, IEEE Trans. Control Syst.

i Technol., vol. 21, no. 4, pp. 12701279, Jul. 2013.
si = gj. [20] H. X. Wu, K. S. Tsakalis, and G. T. Heydt, Evaluation of
j =0
time delay effects to wide-area power system stabilizer design,
IEEE Trans. Power Syst., vol. 19, no. 4, pp. 19351941,
The elements gi of the matrix G, with dimensions N Nu , Nov. 2004.
[21] B. Chaudhuri, R. Majumder, and B. C. Pal, Wide-area measurement-
are points of the plants step response and can be computed based stabilizing control of power system considering signal transmis-
recursively from the model. The elements f i of the matrix f sion delay, IEEE Trans. Power Syst., vol. 19, no. 4, pp. 19711979,
can be computed similarly. Nov. 2004.
[22] R. Majumder, B. Chaudhuri, B. C. Pal, and Q. C. Zhong, A unified
smith predictor approach for power system damping control design using
R EFERENCES remote signals, IEEE Trans. Control Syst. Technol., vol. 13, no. 1,
pp. 10631068, Nov. 2005.
[1] M. Klein, G. J. Rogers, and P. Kundur, A fundamental study of inter- [23] D. Dotta, A. S. Silva, and I. C. Decker, Wide-area measurements-based
area oscillations in power systems, IEEE Trans. Power Syst., vol. 6, two-level control design considering signal transmission delay, IEEE
no. 3, pp. 914921, Aug. 1991. Trans. Power Syst., vol. 24, no. 1, pp. 208216, Feb. 2009.
[2] P. Kundur, Power System Stability and Control. New York, NY, USA: [24] R. Preece, J. V. Milanovic, A. M. Almutairi, and O. Marjanovic,
McGraw-Hill, 1994. Damping of inter-area oscillations in mixed AC/DC networks using
[3] S. P. Azad, R. Iravani, and J. E. Tate, Damping inter-area oscillations WAMS based supplementary controller, IEEE Trans. Power Syst.,
based on a model predictive control (MPC) HVDC supplementary vol. 28, no. 2, pp. 11601169, May 2013.
controller, IEEE Trans. Power Syst., vol. 28, no. 3, pp. 31743183, [25] S. Ray and G. K. Venayagamoorthy, Real-time implementation of
Aug. 2013. a measurement-based adaptive wide-area control system considering
[4] G. N. Taranto, J. H. Chow, and H. Othman, Robust redesign of power communication delays, IET Generat. Transm. Distrib., vol. 2, no. 1,
system damping controllers, IEEE Trans. Control Syst. Technol., vol. 3, pp. 6270, Jan. 2008.
no. 3, pp. 290298, Sep. 1995. [26] P. Zhang, D. Y. Yang, K. W. Chan, and G. W. Cai, Adaptive wide-
[5] M. E. Aboul-Ela, A. A. Sallam, J. D. Mccalley, and A. A. Fouad, area damping control scheme with stochastic subspace identification and
Damping controller design for power system oscillations using global signal time delay compensation, IET Gener. Transmiss. Distrib., vol. 6,
signals, IEEE Trans. Power Syst., vol. 11, no. 2, pp. 767773, no. 9, pp. 844852, Sep. 2012.
May 1996. [27] M. Mokhtari, F. Aminifar, D. Nazarpour, and S. Golshannavaz, Wide-
[6] V. Terzija et al., Wide area monitoring, protection and control area power oscillation damping with a fuzzy controller compensating the
of future electric power networks, Proc. IEEE, vol. 99, no. 1, continuous communication delays, IEEE Trans. Power Syst., vol. 28,
pp. 8093, Jan. 2011. no. 2, pp. 19972005, May 2013.
36 IEEE TRANSACTIONS ON CONTROL SYSTEMS TECHNOLOGY, VOL. 23, NO. 1, JANUARY 2015

[28] N. B. Chaudhuri, S. Ray, R. Majumder, and B. Chaudhuri, A new Lin Jiang (M00) received the B.Sc. and M.Sc.
approach to continuous latency compensation with adaptive phasor degrees in electrical engineering from the Huazhong
power oscillation damping controller (POD), IEEE Trans. Power Syst., University of Science and Technology, Wuhan,
vol. 25, no. 2, pp. 939946, May 2010. China, and the Ph.D. degree in electrical engineering
[29] J. P. Hespanha, P. Naghshtabrizi, and Y. G. Xu, A survey of recent from the University of Liverpool, Liverpool, U.K.,
results in networked control systems, Proc. IEEE, vol. 95, no. 1, in 1992, 1996, and 2001, respectively.
pp. 138162, Jan. 2007. He was a Post-Doctoral Research Assistant with
[30] P. L. Tang and C. W. Silva, Compensation for transmission delays the University of Liverpool from 2001 to 2003 and
in an Ethernet-based control network using variable-horizon predictive a Post-Doctoral Research Associate with the Depart-
control, IEEE Trans. Control Syst. Technol., vol. 14, no. 4, pp. 707718, ment of Automatic Control and Systems Engineer-
Jul. 2006. ing, University of Sheffield, Sheffield, U.K., from
[31] S. C. Chai, G. P. Liu, D. Rees, and Y. Q. Xia, Design and practical 2003 to 2005. He was a Senior Lecturer with the University of Glamorgan,
implementation of Internet-based predictive control of a servo system, Wales, U.K., from 2005 to 2007, and joined the University of Liverpool in
IEEE Trans. Control Syst. Technol., vol. 16, no. 1, pp. 158168, 2007. He is currently a Senior Lecturer with the Department of Electrical
Jan. 2008. Engineering and Electronics, University of Liverpool. His current research
[32] W. S. Hu, G. P. Liu, and D. Rees, Networked predictive control over interests include control and analysis of power system, smart grid, and
the Internet using round-trip delay measurement, IEEE Trans. Instrum. renewable energy.
Meas., vol. 57, no. 10, pp. 22312241, Oct. 2008.
[33] W. Yao, L. Jiang, J. Y. Wen, S. J. Cheng, and Q. H. Wu,
An adaptive wide-area damping controller based on generalized pre-
dictive control and model identification, in Proc. IEEE PES General
Meeting, Jul. 2009, pp. 17. Jinyu Wen (M10) received the B.Sc. and Ph.D.
[34] W. Yao, L. Jiang, Q. H. Wu, J. Y. Wen, and S. J. Cheng, Design of degrees in electrical engineering from the Huazhong
wide-area damping controllers based on networked predictive control University of Science and Technology (HUST),
considering communications delays, in Proc. IEEE PES General Meet- Wuhan, China, in 1992 and 1998, respectively.
ing, Jul. 2010, pp. 18. He was a Visiting Student from 1996 to 1997
[35] S. J. Cheng, Y. S. Chow, O. P. Malik, and G. S. Hope, An adaptive and a Research Fellow from 2002 to 2003 with
synchronous machine stabilizer, IEEE Trans. Power Syst., vol. 1, no. 3, the University of Liverpool, Liverpool, U.K., and a
pp. 101107, Aug. 1986. Senior Visiting Researcher with the University of
[36] D. W. Clarke, C. Mohtadi, and P. S. Tuffs, Generalized predictive Texas at Arlington, Arlington, TX, USA, in 2010.
controlPart I: The basic algorithm, Automatica, vol. 23, no. 2, From 1998 to 2002, he was a Director Engineer
pp. 137148, Mar. 1987. with XJ Electric Company, Ltd., Xuchang, China.
[37] J. A. L. Barreiros, A self-tuning generalized predictive power system In 2003, he joined the HUST, where he is currently a Professor with the
stabilizer, Int. J. Electr. Power Energy Syst., vol. 20, no. 3, pp. 213219, School of Electrical and Electronics Engineering. His current research interests
Mar. 1998. include renewable energy integration, energy storage, multiterminal HVDC,
[38] A. Heniche and I. Kamwa, Control loops selection to damp inter-area and power system operation and control.
oscillations of electrical networks, IEEE Trans. Power Syst., vol. 17,
no. 2, pp. 378384, May 2002.
[39] M. A. Pai, Energy Function Analysis for Power System Stability. Boston,
MA, USA: Kluwer, 1989.
[40] A. Heniche and I. Kamwa, Assessment of two methods to select wide- Qinghua Wu (M91SM97F11) received the
area signals for power system damping control, IEEE Trans. Power M.Sc. and Ph.D. degrees in electrical engineering
Syst., vol. 23, no. 2, pp. 572581, May 2008. from the Huazhong University of Science and Tech-
[41] W. Yao, L. Jiang, J. Y. Wen, Q. H. Wu, and S. J. Cheng, Wide- nology (HUST), Wuhan, China, and the Queens
area damping controller of FACTS devices for inter-area oscillations University of Belfast (QUB), Belfast, U.K., in 1981
considering communication time delays, IEEE Trans. Power Syst., and 1987, respectively.
vol. 29, no. 1, pp. 318329, Jan. 2014. He was a Lecturer in Electrical Engineering at
HUST from 1981 to 1984, a Research Fellow and
Senior Research Fellow at QUB from 1987 to 1991,
and a Lecturer and Senior Lecturer with the Depart-
ment of Mathematical Sciences, Loughborough Uni-
versity of Technology, Leicestershire, U.K., from 1991 to 1995. Since 1995, he
has been the Chair of Electrical Engineering with the Department of Electrical
Engineering and Electronics, University of Liverpool, Liverpool, U.K., as the
Head of the Intelligence Engineering and Automation Group. His current
research interests include adaptive control, mathematical morphology, neural
networks, learning systems, evolutionary computation, and power system
control and operation.

Wei Yao (M13) received the B.Sc. and Ph.D. Shijie Cheng (M86SM87F11) received the
degrees in electrical engineering from the Huazhong B.S. degree from Xian Jiaotong University, Xian,
University of Science and Technology (HUST), China, the M.Sc.degree from the Huazhong Univer-
Wuhan, China, in 2004 and 2010, respectively. sity of Science and Technology (HUST), Wuhan,
He was a Post-Doctoral Researcher with the China, and the Ph.D. degree from the University
Department of Power Engineering, HUST, from of Calgary, Calgary, AB, Canada, all in electrical
2010 to 2012, where he is currently a Lecturer with engineering, in 1967, 1981, and 1986, respectively.
the School of Electrical and Electronics Engineering. He has been a Professor with the School of Electri-
Since 2012, he has been a Post-Doctoral Research cal and Electronics Engineering, HUST, since 1991.
Associate with the Department of Electrical Engi- His current research interests include power system
neering and Electronics, University of Liverpool, control and stability analysis, application of artificial
Liverpool, U.K. His current research interests include power system stability intelligence, and energy storage.
analysis and control, and renewable energy. Prof. Cheng is a fellow of the Chinese Academy of Sciences.

Das könnte Ihnen auch gefallen