ELECTRICAL SAFETY IN

PHOTOVOLTAIC POWER SYSTEM

P K Bhattacharyya
BENDER INDIA
1
Typical Photovoltaic System

PV Systems from tens of W to multi MW

Voltages from 12 V to 1.000 V and more

Leakage Capacitances 50F 1000 F

earthed and unearthed arrays and array frames

Transformer and inverter isolation:


- 50/60 Hz Transformers
- Transformerless
- HF transformer
BENDER INDIA
2
Standards

International (IEC) for installations


IEC 60364-7-712:2002-05 Electrical installations of buildings Part 7-
712: Requirements for special installations or locations Solar
photovoltaic (PV) power supply systems
Technical specifications IEC TS 62257-7-1:2006-12 Recommendations
for small renewable energy and hybrid systems for rural electrification
Part 7-1: Generators Photovoltaic arrays
-Technical specifications IEC 62257-5:2005-07 Recommendations for
small renewable energy and hybrid systems for rural electrification
Part 5: Protection against electrical hazards

International (IEC) for PV inverters


IEC 62109-1 Ed.1: IEC 62109-1 Safety of power converters for use in
photovoltaic power systems - Part 1: General requirements
IEC 62109-2 Ed.1: Safety of power converters for use in photovoltaic
power systems - Part 2: Particular requirements for inverters

BENDER INDIA
3
Topologies of PV Power System

String inverter Centralised inverter

BENDER INDIA
4
Earthing Configuration in PV Power System

BENDER INDIA
5
Benefits of Ungrounded/Unearthed PV Power System

Continuity of supply in case of 1st Fault

Increased safety against Fire risks

Increased Personal Safety


- - No AC ripple at PV modules
- - Double Faults do not lead to dangerous touch
voltages

BENDER INDIA
6
Protective goals acc. to IEC 60364-4-41

Reliability
Availability
Quality
&
Security of
Power Supply

BENDER INDIA
7
Installation requirements acc. to IEC 60364-7-712

IEC 60364-7-712
- 712.312.2 Earthing of DC side is permitted if separation between AC and DC side
- 712.411.1 Protection by SELV / PELV max. DC 120 V
- 712.413.1 Protection by automatic disconnection
On AC side, the PV supply cable shall be connected to
the supply side of the protective device for automatic
disconnection of circuits supplying current-using equipment
PV system without separation between AC and the
DC side an RCD installed to provide fault protection
by automatic disconnection of supply shall be type B
Protection by us of class II or equivalent insulation
shoud preferable be adopted on the DC side
- 712.522.8.3
PV string cables, PV array cables and PV DC main cables shall be selected and erected
so as to minimize the risk of earth faults and short circuits
- 712.536.2.1.1
To allow maintenance of the PV inverter, means of isolating
PV inverter from the DC side and the AC side shall be provided.

BENDER INDIA
8
Typical Photovoltaic Power System

BENDER INDIA
9
Electric Safety in PV Power System

Condition Monitoring System to provide advance alarm


without tripping.

- Insulation Monitoring & fault location system for


ungrounded system

- Residual Current Monitoring System for grounded system

BENDER INDIA
10
On-line Insulation Monitoring & Fault Location
System for Ungrounded Power System

BENDER INDIA
11
Advanced information thanks to early indication

BENDER INDIA
12
Insulation Monitoring in Ungrounded PV Power System

BENDER INDIA
13
Ungrounded System with Localization of Faults

Ip
Insulation fault
IRDH575
R=10kOhm EDS460-L
EDS:off-auto-
EDS on auto
Adr2 k3 12mA

RS485

BENDER INDIA
14
Insulation Monitoring/ Insulation Fault Location System

BENDER INDIA
15
Field Implementation

BENDER INDIA
16
Residual Current Monitoring System for
Grounded Power System

BENDER INDIA
17
Advanced information thanks to early indication

BENDER INDIA
18
Residual Current Monitoring in Earthed PV System

Inverter with separating transformer, array and application circuit earthed

BENDER INDIA
19
Residual Current Monitoring in Earthed PV System

Transformerless inverter, application circuit earthed

BENDER INDIA
20
Grounded System with Localization of Faults

BMS

BENDER INDIA
21
Thank you very much!