Beruflich Dokumente
Kultur Dokumente
(PLANT II)
Sub-Contract No.
F175M021
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
FOREWORD
The purpose of this manual is to clearly identify all the equipments supplied within
the kiln & raw mill dedusting system and to provide comprehensive information to
ensure the safe and efficient operation and maintenance of the plant.
The basic information contained within this manual provides clear and concise
written instructions on the operational functions of the equipment and identifies the
maintenance requirements of the system.
1
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
CONTENTS
CHAPTER DESCRIPTION
ANNEX DESCRIPTION
MANUAL
2
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
INDEX
1. TECHNICAL SPECIFICATION
3. MAINTENANCE PROCEDURES
3.1. GENERAL
3.2. PERIODICAL MAINTENANCE
3.3. FILTER BAG CHANGING PROCEDURES
3.4. REGULATION OF CLEANING CYCLE
3.5 COMMON PROBLEMS & SOLUTIONS
3
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
1 - TECHNICAL SPECIFICATION
INDONESIA
The AAF XLC Fabripulse Model fabric collector is designed for on-line maintenance and
on-line cleaning .
The pulse jet filter employs the principle of compressed air pulsing for bag cleaning. A
short pulse of compressed air is directed accurately downwards from a pulse pipe through
a venturi into a row of bags, causing the bags to flex and dislodging the dust cake from
the outside of the bag, the dust falls under gravity into the hopper where it is evacuated
by dust discharge system (by others).
There is access doors for each compartment to allow maintenance staff enter to carry out
maintenance work inside the compartment. The access doors have internal thermal
insulation and gasket for gas sealing. The gasket is pressed on the door frame by negative
pressure inside the collector, this provide an air-tight design and reduce false air entering
into filter which decrease the suction capability of the downstream exhaust fan..
In each compartment, there are bags mounted on split wire cages and suspended from a
tube sheet. The cage is galvanized for corrosion protection and more durable in high
temperature condition.
The filter bag is made of Fiberglass felt with PTFE membrane material. To ensure
effective cleaning of filter bag, diaphragm valve is selected to clean filter bags in a single
pulse pipe. Each pulse pipe is locked at the end with lock pin and the other end is
connected with quick release connection.
Compressed air manifolds runs along every compartments to supply compressed air. All
the manifolds are connected to a common compressed air pipe header, which provides
bigger compressed air reservoir and to ensure bag cleaning effectiveness.
The combined inlet and outlet plenum located at the center section of the collector, which
constitute an integral part of the filter would ensure a uniform distribution of gas to the
compartmented filter. The inclined plate inside the inlet and outlet plenum acts as a
separation wall between dirty gas chamber and clean gas chamber. There are steel walls
at two sides of this separation wall with the same height as the filter bag to prevent the
dusty gas going directly to filter bag before entering the bottom hopper.
4
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
The collector has been designed with adequate stiffening to withstand the high internal
negative pressure produced by the induced draft fan located downstream of the bagfilter.
A penthouse is installed at the top of the collector for weather protection of the collector.
The penthouse is a steel structure covered with corrugated plate and water drainage
system.
The collector is insulated with a layer of thermal insulation material made of mineral
rockwool to maintain the gas temperature inside the collector above the gas dew point to
avoid condensation and thus prevent any possible corrosion to the filter housing and
blinding of the filter bags.
Access by staircase.is provided from ground level to the top of the filter and
penthouse which require regular maintenance/inspection. Service platform and
access also provide at the filter gas inlet.
5
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
CONSTRUCTION
Insulation thickness mm 100
Cladding type - galvanized steel sheet / aluminum
G
sheet G/A
6
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
thickness mm 5
Hopper:
material type Mild Steel
thickness mm 5
Tubesheet:
material type Mild Steel
thickness mm 6
Inlet manifold:
material type Mild Steel
thickness mm 5
Outlet manifold:
material type Mild Steel
thickness mm 5
FILTER ELEMENTS
Supplier Needlefelt
Type of bag fixation * Snap Ring
Superfine
Antistatic PAN
Fabric quality fiber
Membrane quality (if applicable)
Fabric weight g/m2 600
Dimensions of bag:
length mm 3,600
diameter mm 130
Admissible temperature:
operation (continuous) C 120
maximum (peak) C 135
Bag cages
Single piece cages / number of pieces S/ # S
Cage finish SS304
Diam of longitudinal wire mm 3.2
No.of longitudinal wires # 12
Bag to cage size difference - circunferential mm 15-20
10
- longitudinal mm
Cage size 3600x125
CLEANING SYSTEM
Pulse pressure at header bar 4~6
Air consumption Nm3/h 340 On
Air quality class acc. To ISO 8573-1 2.2.1
(solids.moisture.oil)
Pulse air control by timer yes / no yes By PLC
Pulse air control by pressure difference yes / no yes By PLC
1 DP
Differential pressure gauge/switch type Transmitter
Transmitter
Solenoid valve size mm 1-1/2"
Blow pipe design - injector / double injector /
I
other I / DI / O
Number of bags per blow pipe # 14,16
7
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
CONTROL - ELEMENTS
Pulse air control by timer yes / no yes by PLC
Pulse air control by pressure difference yes / no yes by PLC
Temperature control - (in/out) yes / no yes by T/T
Full-hopper level sensor yes / no yes by LS
Broken-Bag detector yes / no No
ACCESSORIES
Compressor / vessel / pipe included yes / no no
Exhaust air silencer yes / no
8
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
Equipment No : 53BF02
Dept : KILN & RAW MILL
GENERAL
Quantity # 1
Supplier AAF
Type / Design * XLC 8-5376
Housing dimensions:
width m 19.7
length m 22.96
height m 23.6
Number of compartments # 8
Compartment size (l x w) mxm 5.74*7.35
Number of Filter elements # 5376
Filtering area - gross m2 21618 On
- net (during
20942 of
cleaning) m2
Center distance of bags - lengthwise / crosswise mm / mm ~230
Minimum distance between bag and compartm. wall mm 75
Hopper design - trough / inverse pyramidal T/P P
Hopper valley angle, outside against horizontal deg 60
No. of access doors/hopper 1
Access door dimensions mm x mm 610x610
Heated hopper discharge section yes / no NO
CONSTRUCTION
Insulation thickness mm 100
Cladding type - galvanized steel sheet / aluminum sheet G/A G
Corrosion protection in clean gas plenum: yes
yes / no
Painting type -
Steel quality type/code -
Compartment housing:
material type Mild steel
thickness mm 4
Hopper:
material type Mild steel
thickness mm 5
Tubesheet:
material type Mild steel
thickness mm 6
Inlet manifold:
material type Mild steel
thickness mm 4
Outlet manifold:
material type Mild steel
thickness mm 4
FILTER ELEMENTS
Supplier
9
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
SPECIAL-DESIGN
Drop-out chamber Type / Design *
Type of plenum
Static pressure range bar - bar
10
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
CONTROL - ELEMENTS
Pulse air control by timer yes / no yes by PLC
Pulse air control by pressure difference yes / no yes by PLC
Temperature control - (in/out) yes / no yes by T/T
Full-hopper level sensor yes / no yes by LS
Broken-Bag detector yes / no No
CONSTRUCTION
Insulation thickness mm 100
Cladding type - galvanized steel sheet / aluminum sheet G/A G
Corrosion protection in clean gas plenum: yes
yes / no
Painting type -
Steel quality type/code -
Compartment housing:
material type Mild steel
thickness mm 4
11
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
Hopper:
material type Mild steel
thickness mm 5
Tubesheet:
material type Mild steel
thickness mm 6
Inlet manifold:
material type Mild steel
thickness mm 4
Outlet manifold:
material type Mild steel
thickness mm 4
FILTER ELEMENTS
Supplier
Type of bag fixation * snap ring
Superfine
PE+PAN
Fabric quality fiber
Membrane quality (if applicable)
Fabric weight g/m2 600
Dimensions of bag:
length mm 8000
diameter mm 160
Admissible temperature:
operation (continuous) C 120
maximum (peak) C 135
Bag cages
Single piece cages / number of pieces S/ # 2
Cage finish galvanized
Diam of longitudinal wire mm 3.5
No.of longitudinal wires # 12
Bag to cage size difference - circonferencial mm 15-20
- longitudinal mm 10
Cage Size 8000x155
CLEANING SYSTEM
Pulse pressure at header bar ~2
Air consumption Nm3/h 650
Air quality class acc. To ISO 8573-1 (solids.moisture.oil)
Pulse air control by timer yes / no yes by PLC
Pulse air control by pressure difference yes / no yes by PLC
DP
Differential pressure gauge/switch type
transmitter
Solenoid valve size mm 2.5 inch
Blow pipe design - injector / double injector / other I / DI / O I
Number of bags per blow pipe # 16
Qty of pulse valve 180
Air consumption per bag per hour Nm3/h 0.225
COMPRESSOR
Compressed air -from network / dedicated N/C by others
12
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
compressor
Type
Power installed kW
Air volume Nm3/h
Compressed air tank volume l
Static pressure bar
SPECIAL-DESIGN
Drop-out chamber Type / Design *
CONTROL - ELEMENTS
Pulse air control by timer yes / no yes by PLC
Pulse air control by pressure difference yes / no yes by PLC
Temperature control - (in/out) yes / no yes by T/T
Full-hopper level sensor yes / no yes by LS
Broken-Bag detector yes / no No
AAF have supplied electrical control instruments and PLC in a control panel.
13
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
The purpose of the installation is to collect the kiln and raw mill dust and control the dust
emission less than 10 mg/m3 to achieve environmental friendly cement process.
Pulsejet bagfilters are the most universally applied dust collectors for the removal of dry
particulate from process and ventilation air, and for the recovery of product from
manufacturing processes.
The Fabri-Pulse XLC on-line cleaning bagfilter is based on a downflow air principle
pioneered by AAF and proven in hundreds of installations world-wide. An understanding
of the design and operating principle of the Fabri-Pulse is essential for effective operation
and maintenance. Knowledge of the collector nomenclature is necessary so that parts can
be easily identified and located.
Principle of Operation
1. Dust laden air is drawn against the inlet inclined separation plate and changing
direction enter into hopper and allowing the heavier dust fall directly into hopper result
of gravity force.
2. The air is drawn through the fabric tubes with the dust collecting on the outside of the
bags. The collected dust forms a cake which enhances filtering efficiency.
3. Cleaned air flows upwards from the bags to the clean air plenum and is discharged.
The unique cleaning system has been designed to minimize compressed air
consumption for any given application, but with enough cleaning reserve for the most
challenging applications.
4. The filter bags are periodically clean with pulses of compressed air initiated by the
PLC based on differential pressure across filter bags. This low volume pulse of high
pressure air is directed from the manifold via the pulse pipe to a venturi located at the
top of the bag. The pulse induces an additional large volume of clean air through the
venturi into the bag, expanding the fabric rapidly. When the bag reaches its maximum
extension, it stop abruptly and the filter cake is thrown clear and the dislodged dust
falls to the hopper below.
14
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
5. Hoppers are designed to receive the dust and not for the storage. The
recommended pratice is to continuously empty the hopper by means of a
conveyor and/or rotary air lock valve, or by some other discharge device to
attain a seal. Any dust reintrainment will decrease collector efficiency,
reduce bag life and result in increased operation pressure.
Note: PLC will keep in its memory the last compartment cleaned and it will
begin the cleaning cycle with the next output in the preset sequence when the
preset CLEANING START value reached.
15
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
16
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
Mode of Cleaning
Mode 1 DP Mode
SPPT = 1000Pa
Send confirmation to PLC
Compartment Compartment
(1, 2, 3, 10) (11, 12, 13, 20)
> 800Pa
Row 7 & 10 Row 7 & 10
<800Pa+10s delay
STOP CLEANING
17
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
18
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
Mode of Cleaning
Mode 1 TM Mode
START
Send confirmation to PLC
Compartment Compartment
(1, 2, 3, 10) (11, 12, 13, 20)
NO
Row 7 & 10 Row 7 & 10
STOP CLEANING
19
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
20
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
This mode is selected only for checking of the functionality of solenoid valve and
diaphragm valve. Each compartment shall be able to be selected and test individually by
OP Panel install on the PLC Control Panel.
21
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
STARTING UP
2.4.1 GENERAL
22
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
An essential knowledge of the filter and its operation will be useful for the person
responsible for its operation and maintenance.
We recommend that this person familiarizes himself with the description of the
filter in such a way that he can identify and locate its different parts without
difficulty.
THE PURPOSE OF DUST HOPPERS ARE NOT FOR DUST STORAGE. ONLY
IN THE CASE OF AN EMERGENCY IN THE DISCHARGE CONVEYOR MAY
THEY BE USED FOR THIS PURPOSE.
The hoppers will be emptied continuosly through the rotary valve and discharge
conveyor.
A final inspection must be made for the interior and exterior of the filter before
start up.
a) Power supply is healthy to the PLC control system. When PLC power on, a
signal will be to DCS system.
b) Compressed air supply is available at <3.5 barg at the compressed air
manifolds on the filter. Check and make sure no leaks at all the joints of the
valves and connectors.
c) Press test mode button and check that all solenoid valves is operates correctly.
d) No fault signals are present.
e) Dust discharge system is required to run
f) Fan starter is ready to run with isolator on, stop released and fault free.
The PLC can be start and put on run operation. Once the fan has started the
differential pressure across the filter bags will begin to rise after a period of time.
The differential pressure across the filter bag will be measured at field and
feedback to PLC . The DCS can obtain the reading of differential pressure across
the filter bag via PLCs Profibus DP. The pulse cleaning system will be started
after the differential pressure reach the preset value.
23
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
Whenever the filter put in stop operation, the pulse cleaning system shall be
stopped before the stop of dust discharge system, this is to ensure the dust in
hopper is empty.
The system designed to provide two (2) Emergency stops signals, executed by
the users system, to protect the XLC Filter.
When the air flow, at the inlet of the filter, reach a VERY HIGH temperature,
which could damage the filter bags.
When the filter reaches a VERY HIGH pressure drop, which could damage the
filter bags.
24
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
2.6.1HMI Operation
Operators can control the coal mill filter on KTP1000 operator panel, such as
Operators logon/logoff, cleaning mode selection, cleaning operation, system alarm,
trends, ect.
KTP1000 panel has 1 group for authorization level. When the power on, the LOGON
screen display. 1 authorized level:Admin. The operator who not logon cannot operate
and change the parameter.
Button Exit: softkey: exit runtime;
Button Status: Turn to Status screen;
Button Parameter: Turn to Paremeter screen;
Button Alarm: Turn to Alarm screen;
Button DP trends: Turn to DP trends screen;
Button Next: Turn to next screen;
Authorization:
Admin: change the running parameter/start & stop filter/exit runtime/
When logon, the username and password would display, administrator can change the
username and password.
25
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
Filter status screen display the status of the filter: running parameter, actual
cleaning mode, status of blowing valves.
Button Logon: Turn to Logon screen;
Button Parameter Turn to Parameter screen;
Button Test: Turn to Test screen;
Button Alarmr Turn to Alarm screen;
Button Trends Turn to Trends screen;
Button Next Turn to next screen;
Local operation:
Switch the LOCAL/REMOTE selector on the door to the LOCAL position, the
operation button will enabled, select the mode you needed in Symbolic IO Field,
and the mode name will show in the field when the mode had been selected,
then depress the START button to start cleaning filter. The status of SPV
groups will display by changing the colour of corresponding compartment and
block.
Remote operation:
Switch the LOCAL/REMOTE selector on the door to the REMOTE position,
the operation button will disabled, the filter will be controlled by DCS.
26
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
27
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
28
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
29
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
30
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
3 - MAINTENANCE PROCEDURES
3.1. GENERAL
CAUTION
All necessary steps have been taken to ensure, as far as is practical, that
equipment is designed and manufactured to be safe when used properly.
These instructions are however, general and it is important that the user observes
all statutory plant and other safety requirements.
Maintenance Personnel
Equipment must be isolated from its source and a notice which states the
equipment is NOT to be made live because someone is working on it must be
secured to the Isolated Switch.
31
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
When lowering equipment from its operating position always ensure that there are
no projections which will prevent the item being rested in a safe position. If items
are being lowered onto the floor ensire that the floor areas are clear and that
equipment can be released from the lifting-gear without danger to personnel.
The collector is designed to handle dust from kiln and raw mill and must be
checked prior to personnel entry via any access door.
It cannot be stressed too strongly that only qualified personnel, familiar with the
construction, operation and the hazards involved, should be permitted to have
access to machines and equipment, especially for inspection and maintenance, or
for adjustments to control and protective equipment.
Electricity
32
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
Compressed Air
Certain equipment on the plant is operated by means of compressed air and prior
to undertaking any maintenance on equipment so operated it is essential that the
compressed air pressure is either relieved or isolated by closing upstream valves
and draining where applicable by opening intermediate drainage valves.
Hot Surfaces
Access ladders and platforms are provided to certain areas of plant to gain access
to certain ares/items of equipment.
33
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
The filter cleaning cycle is automatically controlled from the control panel with either the
pressure switching points or the interval between pulses being set to maintain a steady
pressure drop across the filter in the range 100 to 150 mm W.G.
Do not be alarmed if cleaning pulses cause momentary spikes in the pressure readings.
NOTE:
The interval between pulses is set during commissioning and is very much dependent
upon the application and reliant upon pulse pressure to ensure effective cleaning.
The pulse duration is pre-set and should not be altered without first consulting an AAF
Ltd. Representative.
The access doors should be open for a monthly inspection of the filter bags.
Any faulty or worn tubes must be replaced to prevent damage to the collector.
The compressed air line regulator, dryer and filter should be checked for proper
operation.
Also inspect the dust discharge device on the hopper outlet for proper operation.
NOTE:
Before entering a compartment ensure that the compartment pulse sequence is inhibited.
34
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
a) Obtain a Permit to Work on the plant ensuring that the Permit states the
identification number of the equipment which is being worked upon.
b) Ensure that protective clothing is not worn, i.e. Overalls, Anti-Dust Masks,
Headgear, Gloves and ensure that a sufficient quantity of polythene sacks is
available at the Access Door Level.
35
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
c) Isolate the collector and attach a Warning Notice to the isolation switch which
warns personnel that the system is not to be switched on.
d) Close the outlet hopper outlet valve if fitted and attach a warning notice.
e) Climb access ladder to top of the Fabri Pulse. Open and secure the plenum access
door this gives access to the pulse pipes in the clean air plenum.
f) Check the internal atmosphere.
g) Remove the Pulse Pipes by loosening the retaining peg and withdrawing the pulse
pipe from its bulkhead fitting, lifting the Pulse Pipes clear of the compartment.
Lay the Pulse Pipes out in the sequence in which they are re removed.
h) Remove the Filter Sleeve Cage. The cage may be of split construction so that it
can be removed within a limited headroom.
Note: Take care not to damage or bend filter cages.
i) Remove the Filter Sleeve from the Tube Plate and allow it to drop into Hopper.
j) Remove and allow six Filter Sleeves to drop. Allow one minute for any dust
displaced from the Filer Sleeves to settle.
k) Open the Hopper Access Door and check the internal atmosphere. Reach inside
the Hopper and pull a Filter Sleeve towards the door so that it can be put into a
Polythene Sack in such a manner that the Sleeve does not come outside of the
Hopper and the sack does not go inside the Hopper and thus become
contaminated with dust on its external surfaces. It may be necessary to use a rod
to pull Filter Sleeves to the Access Door if they are too far away. It is not
necessary to climb inside the Hopper to carry out any of the activities described
above.
Ensure that a good foothold in maintained whilst carrying out all of the Filter
Sleeve removal, and packing into polythene bags, activities.
l) Tie off the top of the polythene bags and lower it to ground level for removal
from site
m) Repeat activities j to m inclusive until the required number of filter sleeves
have been removed from the compartment.
Note: Inspect new bags and cages for damage from shipping, storage or handling
prior to installation. ONLY SMOOTH CAGES MUST BE USED DO NOT USE
DAMAGED BAGS OR CAGES.
n) Insert closed end of the bag through tube sheet hole until bag cuff is near tube
sheet.
o) Collapse bag cuff into half moon shape and insert as shown.
p) Snap bag cuff into position making sure centre groove of cuff seals properly at the
tube sheet.
q) Insert cage assembly into the installed bag ensuring that the cage top fits snugly
on top of the bag cuff.
36
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
NOTE: It may be necessary to take a dye test or or pre-coating of the filter bags as
previously identified.
Proprietary Equipment
For details of any necessary maintenance on proprietary equipment for example
diaphragm and pilot valves, instrumentetc please refer to manufacturers standard
literature.
37
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
Cause Solution
Improper pulse cleaning Check the wiring, fuses, and setting of pulse duration
operation and interval. DO NOT ADJUST THE PULSE
DURATION WITHOUT CONSULTING AN AAF
REPRESENTATIVE
Solenoid pilot valve Listen to be sure the solenoid are firing. Check for
malfunction momentary air venting each time it fire. Clean or replace
if necessary.
38
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
Cause Solution
Too much air or too much dust will create high pressure
Collector overloads drops across the collector. Check the fan speed, system
design, pre-cleaners and the damper position. Also be
sure the dust load and air volume are those the system
was designed to handle by undertaking a volumetric
check immediately up or down stream of the collector
39
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
Cause Solution
Incorrect installation or Check for holes or rips in bags. Replace damaged bags.
damaged bags Reseal bags as necessary.
Insufficient dusk cake The unit could be pulsing too often resulting in over
cleaning. Check to see if the pressure drop is at least
100mm. Increase pulse interval until the unit is operating
stably at 100mm pressure drop minimun.
DO NOT ADJUST PULSE DURATION WITHOUT
CONSULTING AN AAF REPRESENTATIVE.
40
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
Cause Solution
41
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
Cause Solution
Incorrect fan rotation The incorrect rotation of the fan will mean that the
system will not provide the system static pressure or air
volume required.
Check fan rotation and correct as appropriate.
42
XLC SERIES FILTER
OPERATION & MAINTENANCE MANUAL
Cause Solution
Undersize ducts Undersize ducts will create excessive pressure losses for
which the fan may not have been sized. Duct size should
be reviewed considering the design specifications and
fan selections.
43
EWEKORO NIGERIA BAGFILTERS
OPERATION & MAINTENANCE MANUAL
Cause Solution
Dirt on the clean side of bags will wear the bags out from
the inside. This could be the result of a broken bag, or
incorrect bag installation or an improper tube sheet seal.
Bag wear on the inside Vacuum the clean air side and replace the bag. Do not
blow dirt inside the bags. If the bags have dust inside
them, vacuum them out.
44
EWEKORO NIGERIA BAGFILTERS
OPERATION & MAINTENANCE MANUAL
Bags are designed for a maximum temperature 280 deg C in short period of time.
Intake gas temperature into the filter must be always below the maximum
temperature in order to avoid bag damage.
Operator must make sure no gases will enter into the filter exceed maximum design
temperature, the solution will be considered to install some injection of dilution air or
some inlet gases cooling tower etc.
If filter intake gases goes up the maximum design temperature, bag guarantees will
extinguish automatically.
45
EWEKORO NIGERIA BAGFILTERS
OPERATION & MAINTENANCE MANUAL
If gas intake chemical conditions are going to be changed, customer must report to
AAF about the new conditions. In that case AAF will reconsider a new bag life
performance guarantee, or even may recommend to change to a different bag quality
material to suit the new condition.
1) Tubesheet
46
EWEKORO NIGERIA BAGFILTERS
OPERATION & MAINTENANCE MANUAL
47
EWEKORO NIGERIA BAGFILTERS
OPERATION & MAINTENANCE MANUAL
GENERAL CONDITIONS
1. This guarantee offering is good if signed at the same time the contract is signed.
2. The collector shall be operated in accordance with the specifications and conditions
contained herein. Deviations from the conditions will void the guarantee only if
such deviation causes bag failure.
Remedy for bag failure in the event of emission in excess of guaranteed level is
for AAF to supply replacement bags on a bag-by-bag basis until the emission
level is met.
Remedy for bag failure in the event of differential pressure in excess of the
guaranteed level is for AAF to supply replacement bags on a bag-by-bag basis
until the pressure drop guarantee is met.
Supply replacement bags on a bag-by-bag basis until the emission level is met.
If bag defect found >5% of total bags in a compartment, all the bags of the entire
compartment shall be replaced free of charge; if bag defect found <5% of total
bags in a compartment, the bag shall be replaced on one to one basis free of
charge.
In the event that AAF supplied filter bags are not suitable for the application in
the environment and condition specified in this contract (as determined by AAF),
AAF will supply replacement bags of conventional material.
48
EWEKORO NIGERIA BAGFILTERS
OPERATION & MAINTENANCE MANUAL
During the bag warranty period, bag replacement shall be on a full basis.
5. The Purchaser shall notify AAF immediately should bags fail to perform as specified.
The Purchaser shall allow 36 hours for AAF to respond.
6. Failed bags must only be replaced with AAF supplied filter bags unless otherwise
agreed to by AAF.
7. AAF shall not, under any circumstances, be liable for any incidental, consequential,
or special damages, including but not limited to the loss of business or profits based
on any alleged negligence, breach of warranty, strict liability, or any other theory,
arising out of the use and/or handling of these products and any replacements or
reorders. The maximum liability of AAF shall not exceed the purchase order price.
8. Terms and conditions on the quotation form apply to this sale. If conflict with terms
and conditions and general conditions exist, the general conditions shall apply.
11. The Purchaser shall make all test results pertaining to or affecting the performance
of the AAF supplied filter bags available to AAF when such results are obtained.
49
EWEKORO NIGERIA BAGFILTERS
OPERATION & MAINTENANCE MANUAL
TECHNICAL CONDITIONS
1. Prior to installation:
b. AAF shall be allowed to conduct an inspection to ensure that the collector meets
the specified design criteria.
c. All extraneous material (i.e., welding slag, rust, dirt, etc.) must be removed from
the collector.
2. AAF shall be allowed to witness the bag installation and to specify reasonable
procedures.
3. The Purchaser shall conduct a fluorescent dust leakage test prior to start-up and
properly seal all leaks that are identified. A second test shall be conducted if
necessary. AAF shall be allowed to witness the test and specify reasonable
corrective procedures.
4. The Purchaser shall cooperate with and assist AAF in determining the optimum
cleaning cycle and any other reasonable adjustments or corrections which may be
necessary to optimize the performance of the AAF supplied filter bags.
5. Temperature excursions shall not exceed 260oC for more than 10 minutes per day as
measured at the collector inlet and shall never exceed 288oC.
7. Purchaser shall ensure the bags are not subjected to external mechanical damage
(i.e., bag-to-bag or bag-to-collector abrasion, impingement by high velocity dust; lift
velocity <1.2 m/sec, inlet velocity < 10 m/sec).
8. Pulse pressure shall be regulated to 2 - 4bar. The pulsing air must be dry and free of
contaminants and pulse pipes properly aligned.
9. The backing material selected must be compatible with the application with regard
to temperature rating and chemical resistance. The collector must be operated
50
EWEKORO NIGERIA BAGFILTERS
OPERATION & MAINTENANCE MANUAL
11. Purchaser shall be responsible for replacing bags damaged as a result of sparks or
fires.
13. The baghouse shall be bypassed or pre-coated during start-up and during oil firing.
14. Purchaser shall be responsible for vacuuming any/all dust which accumulates on
tube sheet due to any potential failed bags, leaking welds on tube sheet, and/or bags
removed for routine analysis.
TESTING
2. Particulate matter is defined as front half catch obtained during EPA methods 5 or
17 emission testing or VDI2066 methods.
4. Recording of the heated probe temperatures throughout each emission test run is
required.
51
-1-
1
-2-
30-50%
33-50% 50%
MT600
MT800MT1000MT1200MT1400MT1600MT1800MT2000
-3-
-4-
-5-
1.
2.
3.
-6-
2 MOBIL630
4 1L 0.9KG
2#
-20-----120
15-25
-7-
100012001400
632628013058
160018002000
633234016068
38
-8-
CONTENTS
1Structure outlined1
2Technical performance
4Installation
6Wearing parts
-9-
1Structure outlined
1This rotation unloader is specifically for vertical
structure, the fixed shell and the drive devices, most of the
- 10 -
the impeller and the casing uniformly, leaving a gap between the
and replacement.
affect feeding capacity, when not in use hot air to the inlet
situation. When the impeller using six months or more, open the
small access door on the impeller end plate repair welding fray
can not cause impeller card material. Also in the top with
normal operation of the feeder, you can open the access door to
unloader fill rate is generally between 30-50%, can not feed too
- 11 -
much, if there is the phenomenon of sticky material can be
2Technical performance
We rotation unloader vertical mill is designed with the
- 12 -
actual situation, time is usually once a week for maintenance,
- 13 -
3Schematic and Type Selection
- 14 -
- 15 -
4, the installation instructions
This machine is the overall structure, the upper case under
flanges are installed, you can directly and non-standard items
direct related the composition of a closed unloading or Feed System,
in order to strengthen the seal sealant can be applied in the the
docking flanges surface or add asbestos rubber mat seal.
Please note that when installing the Rotation unloader read the
installation requirements:
1) Note that materials flow direction and the direction of
rotation of the rotor to be consistent, use of such best use of
blanking, as shown below.
(2) when adjusting the transmission, the machine can move the
situation then start to look to see whether the the steering is
consistent with our starting marked direction, the direction
indicator device end plate cards.
- 16 -
(3) When the unloader constrained installation position can be
adjusted by yummy treats the tube; If the material flow direction
of the rotor in the opposite direction, the impeller blades and
the shell will soon be worn, which affects the productioncaused
heavy economic losses.
- 17 -
pass hot air, but it must always back gear overhaul connection with
the shaft.) Open manhole door conducted maintenance workers
cleaning up the bottom of the impeller every 15-25 days .
6Wearing parts
(1), Oil asbestos packing or graphite packing.
(2), bearing
1000, 1200, 1400 unloader: (6326) 280 130
58
1600, 1800, 2000 unloader: (6332) 340 160
68
(3), the impeller and shell antiwear plates with antiwear
plates: 8 months should repair and replacement, different
environments very different use of time, but will causing excessive
wear throughout the equipment can not be repaired, one of the most
important spare, back after the plant maintenance equipment as new.
Alternate use for a long time will not be scrapped.
- 18 -
---------------------------------------1
---------------------------------------------1
-------------------------------------1
---------------------------------2
-------------------------------------------------2
-------------------------------------------3
Contents
The scope of work
Adjustment
Operating process
Lubrication
Maintenance
2.1 20
2.2
2.3
2.4
3.1
3.2
A
B 40
C
D 85dB
E 0.05DkwD
m
3.3
A
B 50
C
4.1
4.2
4.3
4.4
5.1
90 150 SY1172-77S
60 80
5.2
ZL1SY141275
2/3
6.1
A
B
C
D
6.2
A
B
6.3
A
B 0.5M
2
C
D
3
1.Features and Applications
two parts, as part of the drive, the corresponding dimensions shown in Figure.
Conduct on-site inspections in accordance with the appropriate size for the
2.Installation Requirements
2.1 20 days before the screw conveyor installation, you should pour a good
2.2 Screw conveyor should install all parts before inventory is complete, and
2.4 Dust port inlet, the discharge port should avoid housing flange and cover
3.Adjustment
prepare commissioning.
3.2 first start the application jog mode, jog for a few test to observe the part
of the action that can be carried out after the normal load test run. Load test
run should be continued for more than two hours, if found not to comply with
4
B, each bearing temperature of not more than 40 , lubrication, sealing
well.
3.3 load test run after passing can load test run. Commissioning of the
material should be required to transport materials, and shall comply with the
following conditions:
A, the actual motor power should not exceed the rated power.
B, each bearing temperature is not greater than the ambient temperature plus
50 .
C, load test run should be carried out after eight hours, during operation if
forcibly run.
4.1 load start screw conveyor, after stable operation can only feed.
4.2 stop off before feeding device, material handling has finished before
4.4 abnormal situation, immediately turn off the feeder, then stop, can
5
5.Lubricating
pressure gear oil. New reducer twenty days after use, to be replaced with new
oil. For long-term continuous work reducer must change the oil once a month,
for the daily working time does not exceed eight hours reducer, the first oil
for about two-thirds of the amount injected into the bearing housing space is
appropriate.
B, tighten fasteners.
6.2 a maintenance
After three months of continuous use of the screw conveyor, level should be
maintained.
6
Mounting for Level Switch
Please make sure the socket thread size the same as level switch thread
size.
Welding the socket with the side wall as per drawings required.