PRODUCT DATA SHEET

Nynas TR-DT 11
PROPERTY UNIT TEST METHOD SPECIFICATION LIMITS TYPICAL DATA
MIN MAX
1 - Function
2
Viscosity, 40C mm /s ISO 3104 12.0 11.6
2
Viscosity, -20C mm /s ISO 3104 1800 750
Pour point C ISO 3016 -30 -51
Water content mg/kg IEC 60814 30 <20
Breakdown voltage
- Before treatment kV IEC 60156 30 40-60
- After treatment kV IEC 60296 70 >70
3
Density, 20C kg/dm ISO 12185 0.895 0.887
DDF at 90C IEC 60247 0.005 <0.001
2 - Refining/stability
Appearance IEC 60296 Clear, free from sediment complies
Acidity mg KOH/g IEC 62021 0.01 <0.01
Interfacial tension mN/m EN 14210 40 >40
Corrosive sulphur DIN 51353 non-corrosive non-corrosive
Potentially corrosive sulphur IEC 62535 non-corrosive non-corrosive
Corrosive sulphur ASTM D 1275 B non-corrosive non-corrosive
DBDS mg/kg IEC 62697-1 not detectable not detectable
Antioxidant wt % IEC 60666 not detectable not detectable
Metal passivator additives mg/kg IEC 60666 not detectable not detectable
2-Furfural and related compounds content mg/kg IEC 61198 0.05 <0.05
3 - Performance
Oxidation stability at 120C,164 h IEC 61125 C
Total acidity mg KOH/g 1.2 0.9
Sludge wt % 0.8 0.3
DDF at 90C 0.500 0.100
4 - Health, safety and environment (HSE)
Flash point, PM C ISO 2719 135 140
PCA wt % IP 346 3 <3
PCB mg/kg IEC 61619 not detectable not detectable

Nynas TR-DT 11 is an uninhibited insulating oil, meeting IEC 60296 Ed.4 (2012) Severely Hydrotreated Insulating Oil
General specifications, LCSET -20C. This transformer oil is developed for distribution Issuing date: 2014-04-08
transformers, and should only be used in applications with a nominal voltage level less
than 72 kV.