Saudi Aramco 2616-ENG (10/2002)

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
SAUDI ARABIAN OIL COMPANY
ENGG CERT PMT OPRNS

REVISION SHEET
G. C. M. C.

SHEET REVISION DESCRIPTION


FS1 A COVER
1 A INDEX
2 A GENERAL NOTES
3 A STREAM COMPOSITION
4 A B40-AIT-5410
5 A B40-AIT-5410
6 A B40-AIT-5410
ISSUE FOR REVIEW

7 A B40-AIT-5411
DESCRIPTION

8 A B40-AIT-5411
9 A B40-AIT-5411
10 A B40-AIT-6410
11 A B40-AIT-6410
12 A B40-AIT-6410
13 A B40-AIT-6411
14 A B40-AIT-6411
15 A B40-AIT-6411
16 A B40-AIT-7410
17 A B40-AIT-7410
B40-AIT-7410
JO/EWO

18 A
01506-
B-10-

19 A B40-AIT-7411
20 A B40-AIT-7411
21 A B40-AIT-7411
20/04/15
DATE
REV.
NO.

DISCIPLINE
ENGINEER
G. CONTARDI
DATE: 20/04/2015

PROJECT
ENGINEER

DATE:
CERTIFIED

M. CALLEGARO
DATE: 20/04/2015

CONSTRUCTION
AGENCY

DATE:
OPERATIONS

DATE:
CONTROL NUMBER
VERIFICATION
EDSD

DATE:
BY:
REVISION CERTIFICATION

OF THIS DRAWING IS COVERED, FOR ALL

Notes:
1
THIS INDICATES THAT REV. NO.

APPROVAL/CERTIFICATION

JO
REQUIREMENTS

JO ISS FOR DWG. TYPE PLANT NO. INDEX DRAWING NO. SHT NO. REV NO.

EW CEMS ANALYZER ISS 1


B40 J BE-126165
(DCC) NO.

KHURAIS FACILITIES EXPANSION & SATELLITE GOSP of A


KHURAIS SAUDI ARABIA JO / EWO B-10-01506-001 21
SAIPEM JOB 032184 DOC. NO. B40-SA-E-051154
Saudi Aramco 2616-ENG(10/2002)
PMT OPRNS

SAUDI ARABIAN OIL COMPANY


GENERAL NOTES:

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
ENGG CERT
M. C.

1. Vendor will provide utility consumption for each anlytical system.


G. C.

2. For analytical systems tag B40-AIT-5410 and 5411, Vendor has to propose one analytical system with a

suitable manual switching system to select the sample take-off point considering the Stack in operation

between "MAIN STACK" and "BYPASS STACK".

3. For analytical systems tag B40-AIT-6410 and 6411, Vendor has to propose one analytical system with a
ISSUE FOR REVIEW
DESCRIPTION

suitable manual switching system to select the sample take-off point considering the Stack in operation

between "MAIN STACK" and "BYPASS STACK".

4. For analytical systems tag B40-AIT-7410 and 7411, Vendor has to propose one analytical system with a

suitable manual switching system to select the sample take-off point considering the Stack in operation
01506-001
JO/EWO
B-10-

between "MAIN STACK" and "BYPASS STACK".


20/04/2015
REV.
NO. DATE
A

DISCIPLINE
ENGINEER
G. CONTARDI

DATE: 20/04/2015

PROJECT
ENGINEER

DATE:

CERTIFIED
M. CALLEGARO
DATE:
20/04/2015
CONSTRUCTION
AGENCY

DATE:

OPERATIONS
DATE:
CONTROL NUMBER
VERIFICATION
EDSD

DATE
BY:
REVISION CERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,

(DCC) NO. ______________________________


THIS INDICATES THAT REV. NO.__________
OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE

ISS FOR GENERAL NOTES DRAWING NO.


DWG. TYPE PLANT NO. INDEX SHT.NO. REV.NO.
CEMS ANALYZER ISS 2
B40 J BE- 126165
KHURAIS FACILITIES EXPANSION & SATELLITE GOSP of A
KHURAIS SAUDI ARABIA JO / EWO: B- 10-01506-001 21
SAIPEM JOB 032184 DOC. NO. B40-SA-E-051154 EDSD/2616-1002.XLS
EDSD REV.
REVISION CERTIFICATION VERIFICATION NO. DATE JO/EWO DESCRIPTION ENGG CERTPMT OPRNS

DATE:
DATE:
DATE:
THIS INDICATES THAT REV. NO.__________ B-10-
A 20/04/2015 ISSUE FOR REVIEW G. C. M. C.
OF THIS DRAWING IS COVERED, FOR ALL 01506-001
CONTROL NUMBER
APPROVAL/CERTIFICATION REQUIREMENTS,

AGENCY
BY:

PROJECT
ENGINEER
ENGINEER
DISCIPLINE

CERTIFIED
BY DRAWING COMPLETION CERTIFICATE

G. CONTARDI

OPERATIONS
DATE: 20/04/2015

M. CALLEGARO

DATE: 20/04/2015
CONSTRUCTION
(DCC) NO. ______________________________ DATE

Waste gas composition

KHURAIS
Saudi Aramco 2616-ENG(10/2002)

CEMS ANALYZERS
ISS FOR STREAM COMPOSITION

SAIPEM JOB 032184 DOC. NO. B40-SA-E-051154


INSTRUMENT SPECIFICATION SHEET

KHURAIS FACILITIES EXPANSION & SATELLITE GOSP


SAUDI ARABIA
ISS
DWG. TYPE

B40
SAUDI ARABIAN OIL COMPANY

J
PLANT NO. INDEX

JO / EWO: B-10-01506-001
DRAWING NO.

3
of
B E -126165
21
A

EDSD/2616-1002.XLS
SHT.NO. REV.NO.
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
Saudi Aramco 2616-ENG(10/2002)

SAUDI ARABIAN OIL COMPANY


PMT OPRNS

INSTRUMENT SPECIFICATION SHEET - CONTINUOS EMISSIONS MONITORING


1 INSTRUMENT TAG NUMBER B40-AIT-5410
2

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
SERVICE Waste gas from Heater B40-E-5000 Main stack NO. OF STREAMS: ONE
ENGG CERT
M. C.

3 MANUFACTURER
4 MODEL NUMBER*
G. C.

5 MATERIAL REQUISITION NO.


6 SOURCE AMS STOCK NO.
7 ANALYZER / PROGRAMMER DISTANCE CONTROL UNIT BUILT IN ANALYZER UNIT
8 ELECTRICAL AREA CLASSIFICATION ANALYZER PROGRAMMER RECORDER SAMPLING SYSTEM
GENERAL

9 CLASS, DIVISION, GROUP CL1- Z2-IIB CL1- Z2-IIB ---- CL1- Z2-IIB
10 GENERAL PURPOSE
11 CSA OR OTHER APPROVAL IECEx Exd IIB T3
12 "T" RATING T3 T3 T3
ISSUE FOR REVIEW
DESCRIPTION

13 ENCLOSURE TYPE* NEMA 4X WITH X - PURGE (NOTE 1, 2)

14 LOCATION (INDOOR OR OUTDOOR) IN OUT IN OUT INDOOR


15 MOUNTING A.SHELTER B40-AS-0001 A.SHELTER B40-AS-0001

16 MAXIMUM TEST PRESSURE* kPa(ga)(PSIG)


HOLD
17 (RELIEF VALVE SETTINGS)
18 P&ID NUMBER BA-220957.001
19 POWER SUPPLY 120 VOLTS 60 Hz AMPERES
SERVICES / UTILITIES

20 INSTRUMENT AIR SUPPLY* 75 MIN 125 MAX PSIG CU.METERS / MIN


21 COOLING WATER* PRESSURE kPa(ga)(PSIG) TEMPERATURE OC (OF)

22 STEAM* PRESSURE kPa(ga)(PSIG) TEMPERATURE


OC (OF)

23 CARRIER GAS* CYL / REG. TYPE* CONSUMPTION*


01506-001
REV. D20/0 JO/EWO
B-10-

24 HYDROGEN GAS* CYL / REG. TYPE* CONSUMPTION*


25
26 ANALOG (VALUE)
SIGNAL OUTPUT

FF BUS for each component DIGITAL (TYPE)


27 LOCAL SIGNAL(S) FOR MAINTENANCE USER SELECTABLE
28 ALARMS (NOTE 3) ALARM (1) ALARM (2) ALARM (3) ALARM (4)
NO.
A

29 ALARM (5) ALARM (6)


DISCIPLINE
ENGINEER 30
G. CONTARDI
31 STREAM COMP. (COMMON NAMES) TYPICAL CONCENTRATIONS DESIRED COMPONENTS TREND
DATE: 20/04/2015 32 OR CHEMICAL FORMULAS) MIN. NORM. MAX. (UNITS) [/] [//] SPAN [/]
PROJECT 33 NOx 60 108 ppm vol 0200
ENGINEER (SEE NOTE 4)
34 CO (SEE NOTE 5) 20 ppm vol 0200
35 O2 13,23 13,90 17,97 % vol 020
STREAM COMPOSITION ( 1-SHEET / STREAM )

DATE:
CERTIFIED 36
M. CALLEGARO 37
DATE: MAR. 15 38 NOTE: COMPONENTS TO BE READ OUT OR TRENDED ARE INDICATED BY PURCHASER [/]
CONSTRUCTION
AGENCY 39 COMPONENTS TO BE TESTED AT MID-SCALE VALUES ARE INDICATED BY PURCHASER [//]
40 STREAM WASTE GAS
DATE: 41 TEMPERATURE: INLET OC (OF)
MAX. (416) NORMAL MIN.
OPERATIONS 42 PRESSURE: INLET kPa(ga)(PSIG) MAX. NORMAL MIN.
43 OUTLET kPa(ga)(PSIG) MAX. NORMAL MIN.
DATE:
44 PHASE LIQUID VAPOR 2-PHASE (DESCRIBE)
CONTROL NUMBER

45 CORROSIVE COMPONENTS SEE COMPOSITION


VERIFICATION

46 SOUR SERVICE (PER NACE-MR-01-75) YES NO


EDSD

47 SOLIDS: PERCENT & PARTICLE SIZE PERCENT MICROMETERS


DATE:

48 STABILITY (POLYMERIZES, DECOMPOSES)


BY:

49 OTHER STREAM DATA (SG. VISCOSITY)


REVISION CERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,

50 OTHER CONTAMINANTS (OIL DISSOLVED)


THIS INDICATES THAT REV. NO.__________
OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE

51

NOTES:

ISS FOR B40-AIT-5410 DWG. TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.

WASTE GAS FROM HEATER B40-E-5000 MAIN STACK ISS


B40 J BE-126165 4 of
(DCC) NO.

KHURAIS FACILITIES EXPANSION & SATELLITE GOSP


21 A
KHURAIS SAUDI ARABIA JO / EWO: B-10-01506-001
SAIPEM JOB 032184 DOC. NO. B40-SA-E-051154 EDSD/2616-1002.XLS
Saudi Aramco 2616-ENG(10/2002)
PMT OPRNS

SAUDI ARABIAN OIL COMPANY


INSTRUMENT SPECIFICATION SHEET - CONTINUOS EMISSIONS MONITORING
52 DETECTOR TYPE VENDOR LOCATION PART OF ANALYZER
53 NO. OF VALVES

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
N.A. NO. OF COLUMNS N.A.
ENGG CERT
M. C.

54 COLUMN CONFIGURATION N.A.


ANALYZER

55 CYCLE TIME min. CONTINUOUS


G. C.

56 MATERIALS CONTACTING STREAM VITON


57 SIZE * mm (in.) WIDE HIGH DEEP WEIGHT kg(lb)
58
59
60 AUTO ZERO YES NO BEFORE EACH PEAK YES NO
61 ANALYSIS REPORTS N.A.
62 TYPE N.A.
PROGRAMMER

63 MEMORY PROTECTION YES


ISSUE FOR REVIEW
DESCRIPTION

64 SIZE mm (in.) WIDE HIGH DEEP WEIGHT KG kg(lb)


65
66
67 SUPPLIED BY PURCHASER VENDOR
68 PREFERRED MATERIALS
69 SAMPLE RETURN TO
SAMPLE CONDITIONING

AMBIENT YES FLARE PROCESS PRESS kPa(ga) (PSIG)


70 CONNECTION SIZES INLET 1/4"NPT OUTLET 1/4"NPT
71 REQUIREMENTS (NOTE4) PUMP YES ASPIRATION AS REQUIRED
72 VAPORIZER AS REQUIRED REDUCERS YES
73 SAMPLE PROBE / SIZE / RATING 6", 150# WITH HASTELLOY C276 PROBE TUBE
74 DISTANCE TAKE-OFF / ANALYZER m HOLD
JO/EWO

01506-
B-10-

75
76
20/04/2015
REV.
NO. DATE
A

NOTES:
DISCIPLINE 1. PROGRAMMER/CONTROL UNIT ARE BUILT-IN WITH THE ANALYZER.
ENGINEER
G. CONTARDI
2. ANALYZER & NOX CONVERTER MOUNTED IN NEMA 4X STAINLESS STELL ENCLOSURE WITH X PURGE TO SUITABLE THE SPECIFIED AREA
DATE: 20/04/2015 CLASSIFICATION.
PROJECT
ENGINEER 3. ANALYZER COMMON FAULT & CALIB/MAINT ALARMS WILL BE WIRED AS REQUIRED.

4. @ 15% O2 DRY.
DATE:
CERTIFIED 5. AT BASE LOAD.
M. CALLEGARO 6. FOR STREAM COMPOSITION ONLY SEE STREAM COMPOSITION SHEET ON SHEET 3 OF 21
DATE: 20/04/2015
CONSTRUCTION
AGENCY
* INFORMATION TO BE SUPPLIED BY VENDOR.

DATE:
OPERATIONS

DATE:
CONTROL NUMBER
VERIFICATION
EDSD

DATE:
BY:
REVISION CERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE

ISS FOR B40-AIT-5410 DWG. TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.

WASTE GAS FROM HEATER B40-E-5000 MAIN STACK ISS


B40 J BE-126165 5 of
(DCC) NO.

KHURAIS FACILITIES EXPANSION & SATELLITE GOSP


21 A
KHURAIS SAUDI ARABIA JO / EWO: B-10-01506-001
SAIPEM JOB 032184 DOC. NO. B40-SA-E-051154 EDSD/2616-1002.XLS
Saudi Aramco 8020-512-ENG (09/2000)
SAUDI ARABIAN OIL COMPANY
PMT OPRNS
INSTRUMENT SPECIFICATION SHEET - OXYGEN ANALYZER
TAG NO. SERVICE:

GENERAL CONTROL UNIT


ENGG CERT

M. C.

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
1. TAG NO. B40-AIT-5410 24. NUMBER OF CHANNELS: ONE
G. C.

2. SERVICE Waste gas from Heater B40-E-5000 Main stack 25. METER SCALE RANGE: 0-20% Vol
3. P & ID NUMBER BA-220957.001 26. LOCATION: INDOORS OUTDOORS
4. MANUFACTURER 27. CONSTRUCTION:GENERAL PURPOSE
5. MODEL NUMBER CLASS I GROUP D DIV. I
6. MATERIAL SOURCE CLASS I GROUP D DIV. II
7. TYPE: FUEL GAS TRACE O2 28. ENCLOUSE (NEMA): NEMA 4X / IP66

DISSOLVED O2 29. OUTPUT SIGNAL: 4-20mA OTHER FF BUS


8. INSTALLATION: PERMANENT PORTABLE 30. RELAY CONTACT ARRANGEMENT DPDT OTHER
9. SENSOR LOCATION: INDOORS OUTDOORS 31. RELAY CONTACT RATING:Amps VOLTS 24VDC
ISSUE FOR REVIEW

10. CONTROL UNIT: INTEGRAL REMOTE 32. ALARM SET POINTS:


DESCRIPTION

LOW HIGH
DISTANCE: m. 33. LATCHING ALARMS:YES NO
11. RANGE: 0-20% Vol 34. POWER SUPPLY REQUIREMENTS:
12. CONSTRUCTION: GENERAL PURPOSE 117 V 60 HZ OTHER 120 V 60 Hz
CLASS I GROUP D DIV. I 35. MFR. MODEL NO.:
CLASS I GROUP D DIV. II 36.
13. NUMBER OF STREAMS MONITORED 37.
SINGLE MULTIPLE NUMBER: 38.
39.
SENSOR (PROBE) 40.
41.
14. NUMBER OF SENSORS: ONE
JO/EWO

15. SENSOR LENGTH: *


01506-
B-10-

OPTIONS
16. SENSOR TYPE: Z2O2 ELECTROCHEMICAL
17. OTHER PARAMGNETIC
20/04/15
DATE

18. CONDUIT CONNECTION SIZE: * 42. BATTERY CHARGER: YES NO


19. ENCLOSURE (NEMA): NEMA 4X / IP66 43. RECORDER: 100 mm strip 300 mm circular
REV.

20. MFR. MODEL NO.:


NO.

4" strip 12" circular


A

DISCIPLINE 21. CHART SPEED:


ENGINEER
22. SCALE:
G. CONTARDI
23. 44. RECORDER POWER SUPPLY:
DATE: 20/04/2015
45. SIGNAL AMPLIFIER: YES NO
PROJECT
ENGINEER 46. PRESSURE REGULATOR:
YES NO

PROCESS DATA MIN. FLOW NORMAL FLOW MAX. FLOW


DATE:
CERTIFIED No.1 No.2 No.3 No.4 No.1 No.2 No.3 No.4 No.1 No.2 No.3 No.4
M. CALLEGARO
47. STREAMS:
DATE: 20/04/2015
48. FLUID:
CONSTRUCTION
AGENCY 49. OXYGEN CONCENTRATION ppb. % O2
50. CONDUCTANCE, MICROSEIMENS (mho)
DATE:
51. DISSOLVED SOLIDS, ppm:
OPERATIONS
52. Ph:
53. SAMPLE PRESSURE, kPa(ga) (PSIG) see notes
DATE:
54. SAMPLE TEMPERATURE, OC (OF)
CONTROL NUMBER

55. DEW POINT, OC (OF)


VERIFICATION

56. SAMPLE FLOW RATE: L/m (ft3/m)


EDSD

57. CORROSIVES:
DATE:

58.
59.
BY:
REVISION CERTIFICATION

60.
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE

NOTES: THIS SPECIFICATION SHEET IS TO BE USED IN CONJUNCTION WITH 34-SAMSS 512.


FOR STREAM COMPOSITION SEE STREAM COMPOSITION SHEET ON SHEET 3 OF 21.

ISS FOR B40-AIT-5410 DWG. TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.

WASTE GAS FROM HEATER B40-E-5000 MAIN STACK ISS


B40 J B E -126165 6 of
(DCC) NO.

KHURAIS FACILITIES EXPANSION & SATELLITE GOSP


26 A
KHURAIS SAUDI ARABIA JO / EWO: B- 10-1506-001
EDSD/8020-512-0900.XLS
Saudi Aramco 2616-ENG(10/2002)

SAUDI ARABIAN OIL COMPANY


PMT OPRNS

INSTRUMENT SPECIFICATION SHEET - CONTINUOS EMISSIONS MONITORING


1 INSTRUMENT TAG NUMBER B40-AIT-5411
2

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
SERVICE Waste gas from heater B40-E-5000 bypass stack NO. OF STREAMS: ONE
ENGG CERT
M. C.

3 MANUFACTURER
4 MODEL NUMBER*
G. C.

5 MATERIAL REQUISITION NO.


6 SOURCE AMS STOCK NO.
7 ANALYZER / PROGRAMMER DISTANCE CONTROL UNIT BUILT IN ANALYZER UNIT
8 ELECTRICAL AREA CLASSIFICATION ANALYZER PROGRAMMER RECORDER SAMPLING SYSTEM
GENERAL

9 CLASS, DIVISION, GROUP CL1- Z2-IIB CL1- Z2-IIB ---- CL1- Z2-IIB
10 GENERAL PURPOSE
11 CSA OR OTHER APPROVAL IECEx Exd IIB T3
12 "T" RATING T3 T3 T3
ISSUE FOR REVIEW
DESCRIPTION

13 ENCLOSURE TYPE* NEMA 4X WITH X - PURGE (NOTE 1, 2)

14 LOCATION (INDOOR OR OUTDOOR) IN OUT IN OUT INDOOR


15 MOUNTING A.SHELTER B40-AS-0002 A.SHELTER B40-AS-0002

16 MAXIMUM TEST PRESSURE* kPa(ga)(PSIG)


HOLD
17 (RELIEF VALVE SETTINGS)
18 P&ID NUMBER BA-220957.001
19 POWER SUPPLY 120 VOLTS 60 Hz AMPERES
SERVICES / UTILITIES

20 INSTRUMENT AIR SUPPLY* 75 MIN 125 MAX PSIG CU.METERS / MIN


21 COOLING WATER* PRESSURE kPa(ga)(PSIG) TEMPERATURE OC (OF)

22 STEAM* PRESSURE kPa(ga)(PSIG) TEMPERATURE


OC (OF)

23 CARRIER GAS* CYL / REG. TYPE* CONSUMPTION*


JO/EWO

01506-001
20/04/2015 B-10-

24 HYDROGEN GAS* CYL / REG. TYPE* CONSUMPTION*


25
26 ANALOG (VALUE)
SIGNAL OUTPUT

FF BUS for each component DIGITAL (TYPE)


DATE

27 LOCAL SIGNAL(S) FOR MAINTENANCE USER SELECTABLE


28 ALARMS (NOTE 3) ALARM (1) ALARM (2) ALARM (3) ALARM (4)
REV.
NO.
A

29 ALARM (5) ALARM (6)


DISCIPLINE
ENGINEER 30
G. CONTARDI 31 STREAM COMP. (COMMON NAMES) TYPICAL CONCENTRATIONS DESIRED COMPONENTS TREND
DATE: 20/04/2015 32 OR CHEMICAL FORMULAS) MIN. NORM. MAX. (UNITS) [/] [//] SPAN [/]
PROJECT 33 NOx (SEE NOTE 4) 60 108 ppm vol 0200
ENGINEER
34 CO (SEE NOTE 5) 20 ppm vol 0200
35 O2 13,23 13,90 17,97 % vol 020
STREAM COMPOSITION ( 1-SHEET / STREAM )

DATE:
CERTIFIED 36
M. CALLEGARO 37
DATE: 20/04/2015 38 NOTE: COMPONENTS TO BE READ OUT OR TRENDED ARE INDICATED BY PURCHASER [/]
CONSTRUCTION
AGENCY 39 COMPONENTS TO BE TESTED AT MID-SCALE VALUES ARE INDICATED BY PURCHASER [//]
40 STREAM WASTE GAS
DATE: 41 TEMPERATURE: INLET OC (OF)
MAX. (1023) NORMAL MIN.
OPERATIONS 42 PRESSURE: INLET kPa(ga)(PSIG) MAX. NORMAL MIN.
43 OUTLET kPa(ga)(PSIG) MAX. NORMAL MIN.
DATE: 44 PHASE LIQUID VAPOR 2-PHASE (DESCRIBE)
CONTROL NUMBER

45 CORROSIVE COMPONENTS SEE COMPOSITION


VERIFICATION

46 SOUR SERVICE (PER NACE-MR-01-75) YES NO


EDSD

47 SOLIDS: PERCENT & PARTICLE SIZE PERCENT MICROMETERS


DATE:

48 STABILITY (POLYMERIZES, DECOMPOSES)


49 OTHER STREAM DATA (SG. VISCOSITY)
BY:
REVISION CERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,

50 OTHER CONTAMINANTS (OIL DISSOLVED)


THIS INDICATES THAT REV. NO.__________
OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE

51

NOTES:

ISS FOR B40-AIT-5411 DWG. TYPE PLANT NO. INDE DRAWING NO. SHT.NO. REV.NO.

WASTE GAS FROM HEATER B40-E-5000 BYPASS STACK ISS


B40 J BE-126165 7 of
(DCC) NO.

KHURAIS FACILITIES EXPANSION & SATELLITE GOSP


21 A
KHURAIS SAUDI ARABIA JO / EWO: 10-03452
SAIPEM JOB 032184 DOC. NO. B40-SA-E-051154 EDSD/2616-1002.XLS
Saudi Aramco 2616-ENG(10/2002)
PMT OPRNS

SAUDI ARABIAN OIL COMPANY


INSTRUMENT SPECIFICATION SHEET - CONTINUOS EMISSIONS MONITORING
52 DETECTOR TYPE IR LOCATION PART OF ANALYZER
53 NO. OF VALVES

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
N.A. NO. OF COLUMNS N.A.
ENGG CERT
M. C.

54 COLUMN CONFIGURATION N.A.


ANALYZER

55 CYCLE TIME min. CONTINUOUS


G. C.

56 MATERIALS CONTACTING STREAM VITON


57 SIZE * mm (in.) WIDE HIGH DEEP WEIGHT kg(lb)
58
59
60 AUTO ZERO YES NO BEFORE EACH PEAK YES NO
61 ANALYSIS REPORTS N.A.
62 TYPE N.A.
PROGRAMMER

63 MEMORY PROTECTION YES


ISSUE FOR REVIEW
DESCRIPTION

64 SIZE mm (in.) WIDE HIGH DEEP WEIGHT KG kg(lb)


65
66
67 SUPPLIED BY PURCHASER VENDOR
68 PREFERRED MATERIALS
69 SAMPLE RETURN TO
SAMPLE CONDITIONING

AMBIENT YES FLARE PROCESS PRESS kPa(ga) (PSIG)


70 CONNECTION SIZES INLET 1/4"NPT OUTLET 1/4"NPT
71 REQUIREMENTS (NOTE4) PUMP YES ASPIRATION AS REQUIRED
72 VAPORIZER AS REQUIRED REDUCERS YES
73 SAMPLE PROBE / SIZE / RATING 6", 150# WITH HASTELLOY C276 PROBE TUBE
74 DISTANCE TAKE-OFF / ANALYZER m HOLD
01506-001
JO/EWO
B-10-

75
76
20/04/2015
REV. DATE

NOTES:
NO.
A

1. PROGRAMMER/CONTROL UNIT ARE BUILT-IN WITH THE ANALYZER.


DISCIPLINE
ENGINEER 2. ANALYZER & NOX CONVERTER MOUNTED IN NEMA 4X STAINLESS STELL ENCLOSURE WITH X PURGE TO SUIT THE SPECIFIED AREA
CLASSIFICATION.
G. CONTARDI
3. ANALYZER COMMON FAULT & CALIB/MAINT ALARMS WILL BE WIRED AS REQUIRED.
20/04/2015
DATE:
4. @ 15% O2 DRY.
PROJECT
ENGINEER 5. AT BASE LOAD.
6. FOR STREAM COMPOSITION ONLY SEE STREAM COMPOSITION SHEET ON SHEET 3 OF 21

CERTIFIED
DATE:
M. CALLEGARO
20/04/2015
DATE:
CONSTRUCTION * INFORMATION TO BE SUPPLIED BY VENDOR.
AGENCY

OPERATIONS
DATE:
CONTROL NUMBER

DATE:
VERIFICATION
EDSD

DATE:
BY:
REVISION CERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE

ISS FOR B40-AIT-5411 DWG. TYPE PLANT NO. INDE DRAWING NO. SHT.NO. REV.NO.

WASTE GAS FROM HEATER B40-E-5000 BYPASS STACK ISS


B40 J BE-126165 8 of
(DCC) NO.

KHURAIS FACILITIES EXPANSION & SATELLITE GOSP


21 A
KHURAIS SAUDI ARABIA JO / EWO: B-10-01506-001
SAIPEM JOB 032184 DOC. NO. B40-SA-E-051154 EDSD/2616-1002.XLS
Saudi Aramco 8020-512-ENG (09/2000)
SAUDI ARABIAN OIL COMPANY
PMT OPRNS
INSTRUMENT SPECIFICATION SHEET - OXYGEN ANALYZER
TAG NO. SERVICE:
ENGG CERT

GENERAL CONTROL UNIT


M. C.

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
1. TAG NO. B40-AIT-5411 24. NUMBER OF CHANNELS: ONE
G. C.

2. SERVICE Waste gas from boiler B40-E-5000 bypass stack 25. METER SCALE RANGE: 0-20% Vol
3. P & ID NUMBER BA-220957.001 26. LOCATION: INDOORS OUTDOORS
4. MANUFACTURER 27. CONSTRUCTION:GENERAL PURPOSE
5. MODEL NUMBER CLASS I GROUP D DIV. I
6. MATERIAL SOURCE CLASS I GROUP D DIV. II
7. TYPE: FUEL GAS TRACE O2 28. ENCLOUSE (NEMA): NEMA 4X / IP66

DISSOLVED O2 29. OUTPUT SIGNAL: 4-20mA OTHER FF BUS


8. INSTALLATION: PERMANENT PORTABLE 30. RELAY CONTACT ARRANGEMENT DPDT OTHER
9. SENSOR LOCATION: INDOORS OUTDOORS 31. RELAY CONTACT RATING:Amps VOLTS 24VDC
ISSUE FOR REVIEW

10. CONTROL UNIT: INTEGRAL 32. ALARM SET POINTS:


DESCRIPTION

REMOTE LOW HIGH


DISTANCE: m. 33. LATCHING ALARMS:YES NO
11. RANGE: 0-20% Vol 34. POWER SUPPLY REQUIREMENTS:
12. CONSTRUCTION: GENERAL PURPOSE 117 V 60 HZ OTHER 120 V 60 Hz
CLASS I GROUP D DIV. I 35. MFR. MODEL NO.:
CLASS I GROUP D DIV. II 36.
13. NUMBER OF STREAMS MONITORED 37.
SINGLE MULTIPLE NUMBER: 38.
39.
SENSOR (PROBE) 40.
41.
14. NUMBER OF SENSORS: ONE
JO/EWO

15. SENSOR LENGTH: *


01506-
B-10-

OPTIONS
16. SENSOR TYPE: Z2O2 ELECTROCHEMICAL
17. OTHER PARAMGNETIC
20/04/15
DATE

18. CONDUIT CONNECTION SIZE: * 42. BATTERY CHARGER: YES NO


19. ENCLOSURE (NEMA): NEMA 4X / IP66 43. RECORDER: 100 mm strip 300 mm circular
REV.

20. MFR. MODEL NO.:


NO.

4" strip 12" circular


A

DISCIPLINE
21. CHART SPEED:
ENGINEER
22. SCALE:
G. CONTARDI
23. 44. RECORDER POWER SUPPLY:
DATE: 20/04/2015
45. SIGNAL AMPLIFIER: YES NO
PROJECT
ENGINEER 46. PRESSURE REGULATOR:
YES NO

DATE: PROCESS DATA MIN. FLOW NORMAL FLOW MAX. FLOW


CERTIFIED No.1 No.2 No.3 No.4 No.1 No.2 No.3 No.4 No.1 No.2 No.3 No.4
M. CALLEGARO
DATE: 47. STREAMS:
20/04/2015
48. FLUID:
CONSTRUCTION
AGENCY 49. OXYGEN CONCENTRATION ppb. % O2
DATE: 50. CONDUCTANCE, MICROSEIMENS (mho)
51. DISSOLVED SOLIDS, ppm:
OPERATIONS
52. Ph:
DATE: 53. SAMPLE PRESSURE, kPa(ga) (PSIG) see notes
54. SAMPLE TEMPERATURE, OC (OF)
CONTROL NUMBER

55. DEW POINT, OC (OF)


VERIFICATION

56. SAMPLE FLOW RATE: L/m (ft3/m)


EDSD

57. CORROSIVES:
DATE:

58.
59.
BY:

60.
REVISION CERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE

NOTES: THIS SPECIFICATION SHEET IS TO BE USED IN CONJUNCTION WITH 34-SAMSS 512.


FOR STREAM SEE STREAM COMPOSITION SHEET ON SHEET 3 OF 21.

ISS FOR B40-AIT-5411 DWG. TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.

WASTE GAS FROM HEATER B40-E-5000 BYPASS STACK ISS


B40 J B E -126165 9 of
(DCC) NO.

KHURAIS FACILITIES EXPANSION & SATELLITE GOSP


21 A
KHURAIS SAUDI ARABIA JO / EWO: B- 10-1506-001
EDSD/8020-512-0900.XLS

SAIPEM JOB 032184 DOC. NO. B40-SA-E-051154


Saudi Aramco 2616-ENG(10/2002)

SAUDI ARABIAN OIL COMPANY


PMT OPRNS

INSTRUMENT SPECIFICATION SHEET - CONTINUOS EMISSIONS MONITORING


1 INSTRUMENT TAG NUMBER B40-AIT-6410
2

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
SERVICE Waste gas from Heater B40-E-6000 Main stack NO. OF STREAMS: ONE
ENGG CERT
M. C.

3 MANUFACTURER
4 MODEL NUMBER*
G. C.

5 MATERIAL REQUISITION NO.


6 SOURCE AMS STOCK NO.
7 ANALYZER / PROGRAMMER DISTANCE CONTROL UNIT BUILT IN ANALYZER UNIT
8 ELECTRICAL AREA CLASSIFICATION ANALYZER PROGRAMMER RECORDER SAMPLING SYSTEM
GENERAL

9 CLASS, DIVISION, GROUP CL1- Z2-IIB CL1- Z2-IIB ---- CL1- Z2-IIB
10 GENERAL PURPOSE
11 CSA OR OTHER APPROVAL IECEx Exd IIB T3
12 "T" RATING T3 T3 T3
ISSUE FOR REVIEW
DESCRIPTION

13 ENCLOSURE TYPE* NEMA 4X WITH X - PURGE (NOTE 1, 2)

14 LOCATION (INDOOR OR OUTDOOR) IN OUT IN OUT INDOOR


15 MOUNTING A.SHELTER B40-AS-0001 A.SHELTER B40-AS-0001

16 MAXIMUM TEST PRESSURE* kPa(ga)(PSIG)


HOLD
17 (RELIEF VALVE SETTINGS)
18 P&ID NUMBER BA-220958.001
19 POWER SUPPLY 120 VOLTS 60 Hz AMPERES
SERVICES / UTILITIES

20 INSTRUMENT AIR SUPPLY* 75 MIN 125 MAX PSIG CU.METERS / MIN


21 COOLING WATER* PRESSURE kPa(ga)(PSIG) TEMPERATURE OC (OF)

22 STEAM* PRESSURE kPa(ga)(PSIG) TEMPERATURE


OC (OF)

23 CARRIER GAS* CYL / REG. TYPE* CONSUMPTION*


01506-001
JO/EWO
B-10-

24 HYDROGEN GAS* CYL / REG. TYPE* CONSUMPTION*


25
20/04/2015

26 ANALOG (VALUE)
SIGNAL OUTPUT

FF BUS for each component DIGITAL (TYPE)


DATE

27 LOCAL SIGNAL(S) FOR MAINTENANCE USER SELECTABLE


28 ALARMS (NOTE 3) ALARM (1) ALARM (2) ALARM (3) ALARM (4)
REV.
NO.
A

29 ALARM (5) ALARM (6)


DISCIPLINE
ENGINEER 30
G. CONTARDI 31 STREAM COMP. (COMMON NAMES) TYPICAL CONCENTRATIONS DESIRED COMPONENTS TREND
DATE: 20/04/2015 32 OR CHEMICAL FORMULAS) MIN. NORM. MAX. (UNITS) [/] [//] SPAN [/]
PROJECT 33 NOx 60 108 ppm vol 0200
ENGINEER (SEE NOTE 4)
34 CO (SEE NOTE 5) 20 ppm vol 0200
35 O2 13,23 13,90 17,97 % vol 020
STREAM COMPOSITION ( 1-SHEET / STREAM )

DATE:
CERTIFIED 36
M. CALLEGARO 37
20/04/2015
DATE: 38 NOTE: COMPONENTS TO BE READ OUT OR TRENDED ARE INDICATED BY PURCHASER [/]
CONSTRUCTION
AGENCY 39 COMPONENTS TO BE TESTED AT MID-SCALE VALUES ARE INDICATED BY PURCHASER [//]
40 STREAM WASTE GAS
DATE: 41 TEMPERATURE: INLET OC (OF)
MAX. (416) NORMAL MIN.
OPERATIONS 42 PRESSURE: INLET kPa(ga)(PSIG) MAX. NORMAL MIN.
43 OUTLET kPa(ga)(PSIG) MAX. NORMAL MIN.
DATE: 44 PHASE LIQUID VAPOR 2-PHASE (DESCRIBE)
CONTROL NUMBER

45 CORROSIVE COMPONENTS SEE COMPOSITION


VERIFICATION

46 SOUR SERVICE (PER NACE-MR-01-75) YES NO


EDSD

47 SOLIDS: PERCENT & PARTICLE SIZE PERCENT MICROMETERS


DATE:

48 STABILITY (POLYMERIZES, DECOMPOSES)


BY:

49 OTHER STREAM DATA (SG. VISCOSITY)


REVISION CERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,

50 OTHER CONTAMINANTS (OIL DISSOLVED)


THIS INDICATES THAT REV. NO.__________
OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE

51

NOTES:

ISS FOR B40-AIT-6410 DWG. TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.

WASTE GAS FROM HEATER B40-E-6000 MAIN STACK ISS


B40 J BE-126165 10 of
(DCC) NO.

KHURAIS FACILITIES EXPANSION & SATELLITE GOSP


21 A
KHURAIS SAUDI ARABIA JO / EWO: B-10-01506-001
SAIPEM JOB 032184 DOC. NO. B40-SA-E-051154 EDSD/2616-1002.XLS
Saudi Aramco 2616-ENG(10/2002)
PMT OPRNS

SAUDI ARABIAN OIL COMPANY


INSTRUMENT SPECIFICATION SHEET - CONTINUOS EMISSIONS MONITORING
52 DETECTOR TYPE VENDOR LOCATION PART OF ANALYZER
53 NO. OF VALVES

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
N.A. NO. OF COLUMNS N.A.
ENGG CERT
M. C.

54 COLUMN CONFIGURATION N.A.


ANALYZER

55 CYCLE TIME min. CONTINUOUS


G. C.

56 MATERIALS CONTACTING STREAM VITON


57 SIZE * mm (in.) WIDE HIGH DEEP WEIGHT kg(lb)
58
59
60 AUTO ZERO YES NO BEFORE EACH PEAK YES NO
61 ANALYSIS REPORTS N.A.
62 TYPE N.A.
PROGRAMMER

63 MEMORY PROTECTION YES


ISSUE FOR REVIEW
DESCRIPTION

64 SIZE mm (in.) WIDE HIGH DEEP WEIGHT KG kg(lb)


65
66
67 SUPPLIED BY PURCHASER VENDOR
68 PREFERRED MATERIALS
69 SAMPLE RETURN TO
SAMPLE CONDITIONING

AMBIENT YES FLARE PROCESS PRESS kPa(ga) (PSIG)


70 CONNECTION SIZES INLET 1/4"NPT OUTLET 1/4"NPT
71 REQUIREMENTS (NOTE4) PUMP YES ASPIRATION AS REQUIRED
72 VAPORIZER AS REQUIRED REDUCERS YES
73 SAMPLE PROBE / SIZE / RATING 6", 150# WITH HASTELLOY C276 PROBE TUBE
74 DISTANCE TAKE-OFF / ANALYZER m HOLD
JO/EWO

01506-001
B-10-

75
76
20/04/2015
REV.
NO. DATE
A

NOTES:
DISCIPLINE 1. PROGRAMMER/CONTROL UNIT ARE BUILT-IN WITH THE ANALYZER.
ENGINEER
G. CONTARDI
2. ANALYZER & NOX CONVERTER MOUNTED IN NEMA 4X STAINLESS STELL ENCLOSURE WITH X PURGE TO SUITABLE THE SPECIFIED AREA
20/04/2015 CLASSIFICATION.
DATE:
PROJECT
ENGINEER 3. ANALYZER COMMON FAULT & CALIB/MAINT ALARMS WILL BE WIRED AS REQUIRED.

4. @ 15% O2 DRY.
DATE:
CERTIFIED 5. AT BASE LOAD.
M. CALLEGARO 6. FOR STREAM COMPOSITION ONLY SEE STREAM COMPOSITION SHEET ON SHEET 3 OF 21
20/04/2015
DATE:
CONSTRUCTION
AGENCY
* INFORMATION TO BE SUPPLIED BY VENDOR.

DATE:
OPERATIONS

DATE:
CONTROL NUMBER
VERIFICATION
EDSD

DATE:
BY:
REVISION CERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE

ISS FOR B40-AIT-6410 DWG. TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.

WASTE GAS FROM HEATER B40-E-6000 MAIN STACK ISS


B40 J BE-126165 11 of
(DCC) NO.

KHURAIS FACILITIES EXPANSION & SATELLITE GOSP


21 A
KHURAIS SAUDI ARABIA JO / EWO: B-10-01506-001
SAIPEM JOB 032184 DOC. NO. B40-SA-E-051154 EDSD/2616-1002.XLS
Saudi Aramco 8020-512-ENG (09/2000)
SAUDI ARABIAN OIL COMPANY
PMT OPRNS
INSTRUMENT SPECIFICATION SHEET - OXYGEN ANALYZER
TAG NO. SERVICE:
ENGG CERT

GENERAL CONTROL UNIT


M. C.

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
1. TAG NO. B40-AIT-6410 24. NUMBER OF CHANNELS: ONE
G. C.

2. SERVICE Waste gas from Heater B40-E-6000 Main stack 25. METER SCALE RANGE: 0-20% Vol
3. P & ID NUMBER BA-220958.001 26. LOCATION: INDOORS OUTDOORS
4. MANUFACTURER 27. CONSTRUCTION:GENERAL PURPOSE
5. MODEL NUMBER CLASS I GROUP D DIV. I
6. MATERIAL SOURCE CLASS I GROUP D DIV. II
7. TYPE: FUEL GAS TRACE O2 28. ENCLOUSE (NEMA): NEMA 4X / IP66

DISSOLVED O2 29. OUTPUT SIGNAL: 4-20mA OTHER FF BUS


8. INSTALLATION: PERMANENT PORTABLE 30. RELAY CONTACT ARRANGEMENT DPDT OTHER
9. SENSOR LOCATION: INDOORS OUTDOORS 31. RELAY CONTACT RATING:Amps VOLTS 24VDC
ISSUE FOR REVIEW

10. CONTROL UNIT: INTEGRAL 32. ALARM SET POINTS:


DESCRIPTION

REMOTE LOW HIGH


DISTANCE: m. 33. LATCHING ALARMS:YES NO
11. RANGE: 0-20% Vol 34. POWER SUPPLY REQUIREMENTS:
12. CONSTRUCTION: GENERAL PURPOSE 117 V 60 HZ OTHER 120 V 60 Hz
CLASS I GROUP D DIV. I 35. MFR. MODEL NO.:
CLASS I GROUP D DIV. II 36.
13. NUMBER OF STREAMS MONITORED 37.
SINGLE MULTIPLE NUMBER: 38.
39.
SENSOR (PROBE) 40.
41.
14. NUMBER OF SENSORS: ONE
JO/EWO

15. SENSOR LENGTH: *


01506-
B-10-

OPTIONS
16. SENSOR TYPE: Z2O2 ELECTROCHEMICAL
17. OTHER PARAMAGNETIC
20/04/15
DATE

18. CONDUIT CONNECTION SIZE: * 42. BATTERY CHARGER: YES NO


19. ENCLOSURE (NEMA): NEMA 4X / IP66 43. RECORDER: 100 mm strip 300 mm circular
REV.

20. MFR. MODEL NO.:


NO.

4" strip 12" circular


A

DISCIPLINE
21. CHART SPEED:
ENGINEER
22. SCALE:
G. CONTARDI
23. 44. RECORDER POWER SUPPLY:
DATE: 20/04/2015
45. SIGNAL AMPLIFIER: YES NO
PROJECT
ENGINEER 46. PRESSURE REGULATOR:
YES NO

PROCESS DATA MIN. FLOW NORMAL FLOW MAX. FLOW


DATE:
CERTIFIED No.1 No.2 No.3 No.4 No.1 No.2 No.3 No.4 No.1 No.2 No.3 No.4
M. CALLEGARO
47. STREAMS:
DATE: 20/04/2015
48. FLUID:
CONSTRUCTION
AGENCY 49. OXYGEN CONCENTRATION ppb. % O2
50. CONDUCTANCE, MICROSEIMENS (mho)
DATE: 51. DISSOLVED SOLIDS, ppm:
OPERATIONS
52. Ph:
53. SAMPLE PRESSURE, kPa(ga) (PSIG) see notes
DATE: 54. SAMPLE TEMPERATURE, OC (OF)
CONTROL NUMBER

55. DEW POINT, OC (OF)


VERIFICATION

56. SAMPLE FLOW RATE: L/m (ft3/m)


EDSD

57. CORROSIVES:
DATE:

58.
59.
BY:

60.
REVISION CERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE

NOTES: THIS SPECIFICATION SHEET IS TO BE USED IN CONJUNCTION WITH 34-SAMSS 512.


FOR STREAM COMPOSITION SEE STREAM COMPOSITION SHEET ON SHEET 3 OF 21.

ISS FOR B40-AIT-6410 DWG. TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.

WASTE GAS FROM HEATER B40-E-6000 MAIN STACK ISS


B40 J B E -126165 12 of
(DCC) NO.

KHURAIS FACILITIES EXPANSION & SATELLITE GOSP


21 A
KHURAIS SAUDI ARABIA JO / EWO: B- 10-1506-001
EDSD/8020-512-0900.XLS
Saudi Aramco 2616-ENG(10/2002)

SAUDI ARABIAN OIL COMPANY


PMT OPRNS

INSTRUMENT SPECIFICATION SHEET - CONTINUOS EMISSIONS MONITORING


1 INSTRUMENT TAG NUMBER B40-AIT-6411
2

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
SERVICE Waste gas from heater B40-E-6000 bypass stack NO. OF STREAMS: ONE
ENGG CERT
M. C.

3 MANUFACTURER
4 MODEL NUMBER*
G. C.

5 MATERIAL REQUISITION NO.


6 SOURCE AMS STOCK NO.
7 ANALYZER / PROGRAMMER DISTANCE CONTROL UNIT BUILT IN ANALYZER UNIT
8 ELECTRICAL AREA CLASSIFICATION ANALYZER PROGRAMMER RECORDER SAMPLING SYSTEM
GENERAL

9 CLASS, DIVISION, GROUP CL1- Z2-IIB CL1- Z2-IIB ---- CL1- Z2-IIB
10 GENERAL PURPOSE
11 CSA OR OTHER APPROVAL IECEx Exd IIB T3
12 "T" RATING T3 T3 T3
ISSUE FOR REVIEW
DESCRIPTION

13 ENCLOSURE TYPE* NEMA 4X WITH X - PURGE (NOTE 1, 2)

14 LOCATION (INDOOR OR OUTDOOR) IN OUT IN OUT INDOOR


15 MOUNTING A.SHELTER B40-AS-0002 A.SHELTER B40-AS-0002

16 MAXIMUM TEST PRESSURE* kPa(ga)(PSIG)


HOLD
17 (RELIEF VALVE SETTINGS)
18 P&ID NUMBER BA-220958.001
19 POWER SUPPLY 120 VOLTS 60 Hz AMPERES
SERVICES / UTILITIES

20 INSTRUMENT AIR SUPPLY* 75 MIN 125 MAX PSIG CU.METERS / MIN


21 COOLING WATER* PRESSURE kPa(ga)(PSIG) TEMPERATURE OC (OF)

22 STEAM* PRESSURE kPa(ga)(PSIG) TEMPERATURE


OC (OF)

23 CARRIER GAS* CYL / REG. TYPE* CONSUMPTION*


01506-001
JO/EWO
B-10-

24 HYDROGEN GAS* CYL / REG. TYPE* CONSUMPTION*


25
20/04/2015

26 ANALOG (VALUE)
SIGNAL OUTPUT

FF BUS for each component DIGITAL (TYPE)


DATE

27 LOCAL SIGNAL(S) FOR MAINTENANCE USER SELECTABLE


28 ALARMS (NOTE 3) ALARM (1) ALARM (2) ALARM (3) ALARM (4)
REV.
NO.
A

29 ALARM (5) ALARM (6)


DISCIPLINE
ENGINEER 30
G. CONTARDI 31 STREAM COMP. (COMMON NAMES) TYPICAL CONCENTRATIONS DESIRED COMPONENTS TREND

DATE:
20/04/2015 32 OR CHEMICAL FORMULAS) MIN. NORM. MAX. (UNITS) [/] [//] SPAN [/]
PROJECT 33 NOx (SEE NOTE 4) 60 108 ppm vol 0200
ENGINEER
34 CO (SEE NOTE 5) 20 ppm vol 0200
35 O2 13,23 13,90 17,97 % vol 020
STREAM COMPOSITION ( 1-SHEET / STREAM )

DATE:
CERTIFIED 36
M. CALLEGARO 37
20/04/2015
DATE: 38 NOTE: COMPONENTS TO BE READ OUT OR TRENDED ARE INDICATED BY PURCHASER [/]
CONSTRUCTION
AGENCY 39 COMPONENTS TO BE TESTED AT MID-SCALE VALUES ARE INDICATED BY PURCHASER [//]
40 STREAM WASTE GAS

DATE:
41 TEMPERATURE: INLET OC (OF)
MAX. (1023) NORMAL MIN.
OPERATIONS 42 PRESSURE: INLET kPa(ga)(PSIG) MAX. NORMAL MIN.
43 OUTLET kPa(ga)(PSIG) MAX. NORMAL MIN.
44 PHASE LIQUID VAPOR 2-PHASE (DESCRIBE)
DATE:
CONTROL NUMBER

45 CORROSIVE COMPONENTS SEE COMPOSITION


VERIFICATION

46 SOUR SERVICE (PER NACE-MR-01-75) YES NO


EDSD

47 SOLIDS: PERCENT & PARTICLE SIZE PERCENT MICROMETERS


DATE:

48 STABILITY (POLYMERIZES, DECOMPOSES)


BY:

49 OTHER STREAM DATA (SG. VISCOSITY)


REVISION CERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,

50 OTHER CONTAMINANTS (OIL DISSOLVED)


THIS INDICATES THAT REV. NO.__________
OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE

51

NOTES:

ISS FOR B40-AIT-6411 DWG. TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.

WASTE GAS FROM HEATER B40-E-6000 BYPASS STACK ISS


B40 J BE-126165 13 of
(DCC) NO.

KHURAIS FACILITIES EXPANSION & SATELLITE GOSP


21 A
KHURAIS SAUDI ARABIA JO / EWO: 10-03452
SAIPEM JOB 032184 DOC. NO. B40-SA-E-051154 EDSD/2616-1002.XLS
Saudi Aramco 2616-ENG(10/2002)
PMT OPRNS

SAUDI ARABIAN OIL COMPANY


INSTRUMENT SPECIFICATION SHEET - CONTINUOS EMISSIONS MONITORING
52 DETECTOR TYPE IR LOCATION PART OF ANALYZER
53 NO. OF VALVES

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
N.A. NO. OF COLUMNS N.A.
ENGG CERT
M. C.

54 COLUMN CONFIGURATION N.A.


ANALYZER

55 CYCLE TIME min. CONTINUOUS


G. C.

56 MATERIALS CONTACTING STREAM VITON


57 SIZE * mm (in.) WIDE HIGH DEEP WEIGHT kg(lb)
58
59
60 AUTO ZERO YES NO BEFORE EACH PEAK YES NO
61 ANALYSIS REPORTS N.A.
62 TYPE N.A.
PROGRAMMER

63 MEMORY PROTECTION YES


ISSUE FOR REVIEW
DESCRIPTION

64 SIZE mm (in.) WIDE HIGH DEEP WEIGHT KG kg(lb)


65
66
67 SUPPLIED BY PURCHASER VENDOR
68 PREFERRED MATERIALS
69 SAMPLE RETURN TO
SAMPLE CONDITIONING

AMBIENT YES FLARE PROCESS PRESS kPa(ga) (PSIG)


70 CONNECTION SIZES INLET 1/4"NPT OUTLET 1/4"NPT
71 REQUIREMENTS (NOTE4) PUMP YES ASPIRATION AS REQUIRED
72 VAPORIZER AS REQUIRED REDUCERS YES
73 SAMPLE PROBE / SIZE / RATING 6", 150# WITH HASTELLOY C276 PROBE TUBE
74 DISTANCE TAKE-OFF / ANALYZER m HOLD
01506-001
JO/EWO
B-10-

75
76
20/04/2015
DATE

NOTES:
REV.
NO.
A

1. PROGRAMMER/CONTROL UNIT ARE BUILT-IN WITH THE ANALYZER.


DISCIPLINE
ENGINEER
2. ANALYZER & NOX CONVERTER MOUNTED IN NEMA 4X STAINLESS STELL ENCLOSURE WITH X PURGE TO SUITABLE THE SPECIFIED AREA
G. CONTARDI
CLASSIFICATION.
20/04/2015
DATE:
3. ANALYZER COMMON FAULT & CALIB/MAINT ALARMS WILL BE WIRED IAS REQUIRED.
PROJECT
ENGINEER
4. @ 15% O2 DRY.

DATE: 5. AT BASE LOAD.


CERTIFIED
6. FOR STREAM COMPOSITION ONLY SEE STREAM COMPOSITION SHEET ON SHEET 3 OF 21
M. CALLEGARO
20/04/2015
DATE:
CONSTRUCTION
AGENCY * INFORMATION TO BE SUPPLIED BY VENDOR.

DATE:
OPERATIONS

DATE:
CONTROL NUMBER
VERIFICATION
EDSD

DATE:
BY:
REVISION CERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE

ISS FOR B40-AIT-6411 DWG. TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.

WASTE GAS FROM HEATER B40-E-6000 BYPASS STACK ISS


B40 J BE-126165 14 of
(DCC) NO.

KHURAIS FACILITIES EXPANSION & SATELLITE GOSP


21 A
KHURAIS SAUDI ARABIA JO / EWO: B-10-01506-001
SAIPEM JOB 032184 DOC. NO. B40-SA-E-051154 EDSD/2616-1002.XLS
Saudi Aramco 8020-512-ENG (09/2000)
SAUDI ARABIAN OIL COMPANY
PMT OPRNS
INSTRUMENT SPECIFICATION SHEET - OXYGEN ANALYZER
TAG NO. SERVICE:
ENGG CERT

GENERAL CONTROL UNIT


M. C.

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
1. TAG NO. B40-AIT-6411 24. NUMBER OF CHANNELS: ONE
G. C.

2. SERVICE Waste gas from boiler B40-E-6000 bypass stack 25. METER SCALE RANGE: 0-20% Vol
3. P & ID NUMBER BA-220958.001 26. LOCATION: INDOORS OUTDOORS
4. MANUFACTURER 27. CONSTRUCTION:GENERAL PURPOSE
5. MODEL NUMBER CLASS I GROUP D DIV. I
6. MATERIAL SOURCE CLASS I GROUP D DIV. II
7. TYPE: FUEL GAS TRACE O2 28. ENCLOUSE (NEMA): NEMA 4X / IP66

DISSOLVED O2 29. OUTPUT SIGNAL: 4-20mA OTHER FF BUS


8. INSTALLATION: PERMANENT PORTABLE 30. RELAY CONTACT ARRANGEMENT DPDT OTHER
9. SENSOR LOCATION: INDOORS OUTDOORS 31. RELAY CONTACT RATING:Amps VOLTS 24VDC
ISSUE FOR REVIEW

10. CONTROL UNIT: INTEGRAL 32. ALARM SET POINTS:


DESCRIPTION

REMOTE LOW HIGH


DISTANCE: m. 33. LATCHING ALARMS:YES NO
11. RANGE: 0-20% Vol 34. POWER SUPPLY REQUIREMENTS:
12. CONSTRUCTION: GENERAL PURPOSE 117 V 60 HZ OTHER 120 V 60 Hz
CLASS I GROUP D DIV. I 35. MFR. MODEL NO.:
CLASS I GROUP D DIV. II 36.
13. NUMBER OF STREAMS MONITORED 37.
SINGLE MULTIPLE NUMBER: 38.
39.
SENSOR (PROBE) 40.
41.
14. NUMBER OF SENSORS: ONE
JO/EWO

15. SENSOR LENGTH: *


01506-
B-10-

OPTIONS
16. SENSOR TYPE: Z2O2 ELECTROCHEMICAL
17. OTHER PARAMAGNETIC
20/04/15
DATE

18. CONDUIT CONNECTION SIZE: * 42. BATTERY CHARGER: YES NO


19. ENCLOSURE (NEMA): NEMA 4X / IP66 43. RECORDER: 100 mm strip 300 mm circular
REV.

20. MFR. MODEL NO.:


NO.

4" strip 12" circular


A

DISCIPLINE
21. CHART SPEED:
ENGINEER
22. SCALE:
G. CONTARDI
23. 44. RECORDER POWER SUPPLY:
DATE: 20/04/2015
45. SIGNAL AMPLIFIER: YES NO
PROJECT
ENGINEER 46. PRESSURE REGULATOR:
YES NO

PROCESS DATA MIN. FLOW NORMAL FLOW MAX. FLOW


DATE:
CERTIFIED No.1 No.2 No.3 No.4 No.1 No.2 No.3 No.4 No.1 No.2 No.3 No.4
M. CALLEGARO
47. STREAMS:
DATE: 20/04/2015
48. FLUID:
CONSTRUCTION
AGENCY 49. OXYGEN CONCENTRATION ppb. % O2
50. CONDUCTANCE, MICROSEIMENS (mho)
DATE:
51. DISSOLVED SOLIDS, ppm:
OPERATIONS
52. Ph:
53. SAMPLE PRESSURE, kPa(ga) (PSIG) see notes
DATE:
54. SAMPLE TEMPERATURE, OC (OF)
CONTROL NUMBER

55. DEW POINT, OC (OF)


VERIFICATION

56. SAMPLE FLOW RATE: L/m (ft3/m)


EDSD

57. CORROSIVES:
DATE:

58.
59.
BY:

60.
REVISION CERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE

NOTES: THIS SPECIFICATION SHEET IS TO BE USED IN CONJUNCTION WITH 34-SAMSS 512.


FOR STREAM COMPOSITION SEE STREAM COMPOSITION SHEET ON SHEET 3 OF 21.

ISS FOR B40-AIT-6411 DWG. TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.

WASTE GAS FROM HEATER B40-E-6000 BYPASS STACK ISS


B40 J B E -126165 15 of
(DCC) NO.

KHURAIS FACILITIES EXPANSION & SATELLITE GOSP


21 A
KHURAIS SAUDI ARABIA JO / EWO: B- 10-1506-001
EDSD/8020-512-0900.XLS
Saudi Aramco 2616-ENG(10/2002)

SAUDI ARABIAN OIL COMPANY


PMT OPRNS

INSTRUMENT SPECIFICATION SHEET - CONTINUOS EMISSIONS MONITORING


1 INSTRUMENT TAG NUMBER B40-AIT-7410
2

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
SERVICE Waste gas from Heater B40-E-7000 Main stack NO. OF STREAMS: ONE
ENGG CERT
M. C.

3 MANUFACTURER
4 MODEL NUMBER*
G. C.

5 MATERIAL REQUISITION NO.


6 SOURCE AMS STOCK NO.
7 ANALYZER / PROGRAMMER DISTANCE CONTROL UNIT BUILT IN ANALYZER UNIT
8 ELECTRICAL AREA CLASSIFICATION ANALYZER PROGRAMMER RECORDER SAMPLING SYSTEM
GENERAL

9 CLASS, DIVISION, GROUP CL1- Z2-IIB CL1- Z2-IIB ---- CL1- Z2-IIB
10 GENERAL PURPOSE
11 CSA OR OTHER APPROVAL IECEx Exd IIB T3
12 "T" RATING T3 T3 T3
ISSUE FOR REVIEW
DESCRIPTION

13 ENCLOSURE TYPE* NEMA 4X WITH X - PURGE (NOTE 1, 2)

14 LOCATION (INDOOR OR OUTDOOR) IN OUT IN OUT INDOOR


15 MOUNTING A.SHELTER B40-AS-0001 A.SHELTER B40-AS-0001

16 MAXIMUM TEST PRESSURE* kPa(ga)(PSIG)


HOLD
17 (RELIEF VALVE SETTINGS)
18 P&ID NUMBER BA-220959.001
19 POWER SUPPLY 120 VOLTS 60 Hz AMPERES
SERVICES / UTILITIES

20 INSTRUMENT AIR SUPPLY* 75 MIN 125 MAX PSIG CU.METERS / MIN


21 COOLING WATER* PRESSURE . kPa(ga)(PSIG) TEMPERATURE OC (OF)

22 STEAM* PRESSURE kPa(ga)(PSIG) TEMPERATURE


OC (OF)

23 CARRIER GAS* CYL / REG. TYPE* CONSUMPTION*


01506-001
JO/EWO
B-10-

24 HYDROGEN GAS* CYL / REG. TYPE* CONSUMPTION*


25
20/04/2015

26 ANALOG (VALUE)
SIGNAL OUTPUT

FF BUS for each component DIGITAL (TYPE)


DATE

27 LOCAL SIGNAL(S) FOR MAINTENANCE USER SELECTABLE


28 ALARMS (NOTE 3) ALARM (1) ALARM (2) ALARM (3) ALARM (4)
REV.
NO.
A

29 ALARM (5) ALARM (6)


DISCIPLINE
ENGINEER 30
G. CONTARDI 31 STREAM COMP. (COMMON NAMES) TYPICAL CONCENTRATIONS DESIRED COMPONENTS TREND

DATE: 20/04/2015 32 OR CHEMICAL FORMULAS) MIN. NORM. MAX. (UNITS) [/] [//] SPAN [/]
PROJECT 33 NOx 60 108 ppm vol 0200
ENGINEER
34 CO 20 ppm vol 0200
35 O2 13,23 13,90 17,97 % vol 020
STREAM COMPOSITION ( 1-SHEET / STREAM )

DATE:
CERTIFIED 36
M. CALLEGARO 37
20/04/2015
DATE: 38 NOTE: COMPONENTS TO BE READ OUT OR TRENDED ARE INDICATED BY PURCHASER [/]
CONSTRUCTION
AGENCY 39 COMPONENTS TO BE TESTED AT MID-SCALE VALUES ARE INDICATED BY PURCHASER [//]
40 STREAM WASTE GAS
DATE: 41 TEMPERATURE: INLET OC (OF)
MAX. (351) NORMAL MIN.
OPERATIONS 42 PRESSURE: INLET kPa(ga)(PSIG) MAX. NORMAL MIN.
43 OUTLET kPa(ga)(PSIG) MAX. NORMAL MIN.
DATE: 44 PHASE LIQUID VAPOR 2-PHASE (DESCRIBE)
CONTROL NUMBER

45 CORROSIVE COMPONENTS SEE COMPOSITION


VERIFICATION

46 SOUR SERVICE (PER NACE-MR-01-75) YES NO


EDSD

47 SOLIDS: PERCENT & PARTICLE SIZE PERCENT MICROMETERS


DATE:

48 STABILITY (POLYMERIZES, DECOMPOSES)


BY:

49 OTHER STREAM DATA (SG. VISCOSITY)


REVISION CERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,

50 OTHER CONTAMINANTS (OIL DISSOLVED)


THIS INDICATES THAT REV. NO.__________
OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE

51

NOTES:

ISS FOR B40-AIT-7410 DWG. TYPE PLANT NO. INDE DRAWING NO. SHT.NO. REV.NO.

WASTE GAS FROM HEATER B40-E-7000 MAIN STACK ISS


B40 J BE-126165 16 of
(DCC) NO.

KHURAIS FACILITIES EXPANSION & SATELLITE GOSP


21 A
KHURAIS SAUDI ARABIA JO / EWO: B-10-01506-001
SAIPEM JOB 032184 DOC. NO. B40-SA-E-051154 EDSD/2616-1002.XLS
Saudi Aramco 2616-ENG(10/2002)
PMT OPRNS

SAUDI ARABIAN OIL COMPANY


INSTRUMENT SPECIFICATION SHEET - CONTINUOS EMISSIONS MONITORING
52 DETECTOR TYPE VENDOR LOCATION PART OF ANALYZER
53 NO. OF VALVES

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
N.A. NO. OF COLUMNS N.A.
ENGG CERT
M. C.

54 COLUMN CONFIGURATION N.A.


ANALYZER

55 CYCLE TIME min. CONTINUOUS


G. C.

56 MATERIALS CONTACTING STREAM VITON


57 SIZE * mm (in.) WIDE HIGH DEEP WEIGHT kg(lb)
58
59
60 AUTO ZERO YES NO BEFORE EACH PEAK YES NO
61 ANALYSIS REPORTS N.A.
62 TYPE N.A.
PROGRAMMER

63 MEMORY PROTECTION YES


ISSUE FOR REVIEW
DESCRIPTION

64 SIZE mm (in.) WIDE HIGH DEEP WEIGHT KG kg(lb)


65
66
67 SUPPLIED BY PURCHASER VENDOR
68 PREFERRED MATERIALS
69 SAMPLE RETURN TO
SAMPLE CONDITIONING

AMBIENT YES FLARE PROCESS PRESS kPa(ga) (PSIG)


70 CONNECTION SIZES INLET 1/4"NPT OUTLET 1/4"NPT
71 REQUIREMENTS (NOTE4) PUMP YES ASPIRATION AS REQUIRED
72 VAPORIZER AS REQUIRED REDUCERS YES
73 SAMPLE PROBE / SIZE / RATING 6", 150# WITH HASTELLOY C276 PROBE TUBE
74 DISTANCE TAKE-OFF / ANALYZER m HOLD
01506-001
JO/EWO
B-10-

75
76
20/04/2015
REV.
NO. DATE
A

NOTES:
DISCIPLINE 1. PROGRAMMER/CONTROL UNIT ARE BUILT-IN WITH THE ANALYZER.
ENGINEER
G. CONTARDI
2. ANALYZER & NOX CONVERTER MOUNTED IN NEMA 4X STAINLESS STELL ENCLOSURE WITH X PURGE TO SUITABLE THE SPECIFIED AREA
20/04/2015 CLASSIFICATION.
DATE:
PROJECT
ENGINEER 3. ANALYZER COMMON FAULT & CALIB/MAINT ALARMS WILL BE WIRED AS REQUIRED.

4. @ 15% O2 DRY.
DATE:
CERTIFIED 5. AT BASE LOAD.
M. CALLEGARO 6. FOR STREAM COMPOSITION ONLY SEE STREAM COMPOSITION SHEET ON SHEET 3 OF 21
20/04/2015
DATE:
CONSTRUCTION
AGENCY
* INFORMATION TO BE SUPPLIED BY VENDOR.

DATE:
OPERATIONS

DATE:
CONTROL NUMBER
VERIFICATION
EDSD

DATE:
BY:
REVISION CERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE

ISS FOR B40-AIT-7410 DWG. TYPE PLANT NO. INDE DRAWING NO. SHT.NO. REV.NO.

WASTE GAS FROM HEATER B40-E-7000 MAIN STACK ISS


B40 J BE-126165 17 of
(DCC) NO.

KHURAIS FACILITIES EXPANSION & SATELLITE GOSP


21 A
KHURAIS SAUDI ARABIA JO / EWO: B-10-01506-001
SAIPEM JOB 032184 DOC. NO. B40-SA-E-051154 EDSD/2616-1002.XLS
Saudi Aramco 8020-512-ENG (09/2000)
SAUDI ARABIAN OIL COMPANY
PMT OPRNS
INSTRUMENT SPECIFICATION SHEET - OXYGEN ANALYZER
TAG NO. SERVICE:
ENGG CERT

GENERAL CONTROL UNIT


M. C.

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
1. TAG NO. B40-AIT-7410 24. NUMBER OF CHANNELS: ONE
G. C.

2. SERVICE Waste gas from Heater B40-E-5000 Main stack 25. METER SCALE RANGE: 0-20% Vol
3. P & ID NUMBER BA-220959.001 26. LOCATION: INDOORS OUTDOORS
4. MANUFACTURER 27. CONSTRUCTION:GENERAL PURPOSE
5. MODEL NUMBER CLASS I GROUP D DIV. I
6. MATERIAL SOURCE CLASS I GROUP D DIV. II
7. TYPE: FUEL GAS TRACE O2 28. ENCLOUSE (NEMA): NEMA 4X / IP66

DISSOLVED O2 29. OUTPUT SIGNAL: 4-20mA OTHER FF BUS


8. INSTALLATION: PERMANENT PORTABLE 30. RELAY CONTACT ARRANGEMENT DPDT OTHER
9. SENSOR LOCATION: INDOORS OUTDOORS 31. RELAY CONTACT RATING:Amps VOLTS 24VDC
ISSUE FOR REVIEW

10. CONTROL UNIT: INTEGRAL 32. ALARM SET POINTS:


DESCRIPTION

REMOTE LOW HIGH


DISTANCE: m. 33. LATCHING ALARMS:YES NO
11. RANGE: 0-20% Vol 34. POWER SUPPLY REQUIREMENTS:
12. CONSTRUCTION: GENERAL PURPOSE 117 V 60 HZ OTHER 120 V 60 Hz
CLASS I GROUP D DIV. I 35. MFR. MODEL NO.:
CLASS I GROUP D DIV. II 36.
13. NUMBER OF STREAMS MONITORED 37.
SINGLE MULTIPLE NUMBER: 38.
39.
SENSOR (PROBE) 40.
41.
14. NUMBER OF SENSORS: ONE
JO/EWO

15. SENSOR LENGTH: *


01506-
B-10-

OPTIONS
16. SENSOR TYPE: Z2O2 ELECTROCHEMICAL
17. OTHER PARAMAGNETIC
20/04/15
DATE

18. CONDUIT CONNECTION SIZE: * 42. BATTERY CHARGER: YES NO


19. ENCLOSURE (NEMA): NEMA 4X / IP66 43. RECORDER: 100 mm strip 300 mm circular
REV.

20. MFR. MODEL NO.:


NO.

4" strip 12" circular


A

DISCIPLINE
21. CHART SPEED:
ENGINEER
22. SCALE:
G. CONTARDI
23. 44. RECORDER POWER SUPPLY:
DATE: 20/04/2015
45. SIGNAL AMPLIFIER: YES NO
PROJECT
ENGINEER 46. PRESSURE REGULATOR:
YES NO

PROCESS DATA MIN. FLOW NORMAL FLOW MAX. FLOW


DATE:
CERTIFIED No.1 No.2 No.3 No.4 No.1 No.2 No.3 No.4 No.1 No.2 No.3 No.4
M. CALLEGARO
47. STREAMS:
DATE: 20/04/2015
48. FLUID:
CONSTRUCTION
AGENCY 49. OXYGEN CONCENTRATION ppb. % O2
50. CONDUCTANCE, MICROSEIMENS (mho)
DATE:
51. DISSOLVED SOLIDS, ppm:
OPERATIONS
52. Ph:
53. SAMPLE PRESSURE, kPa(ga) (PSIG) see notes
DATE:
54. SAMPLE TEMPERATURE, OC (OF)
CONTROL NUMBER

55. DEW POINT, OC (OF)


VERIFICATION

56. SAMPLE FLOW RATE: L/m (ft3/m)


EDSD

57. CORROSIVES:
DATE:

58.
59.
BY:

60.
REVISION CERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE

NOTES: THIS SPECIFICATION SHEET IS TO BE USED IN CONJUNCTION WITH 34-SAMSS 512.


FOR STREAM COMPOSITION SEE STREAM COMPOSITION SHEET ON SHEET 3 OF 21.

ISS FOR B40-AIT-7410 DWG. TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.

WASTE GAS FROM HEATER B40-E-7000 MAIN STACK ISS


B40 J B E -126165 18 of
(DCC) NO.

KHURAIS FACILITIES EXPANSION & SATELLITE GOSP


21 A
KHURAIS SAUDI ARABIA JO / EWO: B- 10-1506-001
EDSD/8020-512-0900.XLS
Saudi Aramco 2616-ENG(10/2002)

SAUDI ARABIAN OIL COMPANY


PMT OPRNS

INSTRUMENT SPECIFICATION SHEET - CONTINUOS EMISSIONS MONITORING


1 INSTRUMENT TAG NUMBER B40-AIT-7411
2

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
SERVICE Waste gas from heater B40-E-7000 bypass stack NO. OF STREAMS: ONE
ENGG CERT
M. C.

3 MANUFACTURER
4 MODEL NUMBER*
G. C.

5 MATERIAL REQUISITION NO.


6 SOURCE AMS STOCK NO.
7 ANALYZER / PROGRAMMER DISTANCE CONTROL UNIT BUILT IN ANALYZER UNIT
8 ELECTRICAL AREA CLASSIFICATION ANALYZER PROGRAMMER RECORDER SAMPLING SYSTEM
GENERAL

9 CLASS, DIVISION, GROUP CL1- Z2-IIB CL1- Z2-IIB ---- CL1- Z2-IIB
10 GENERAL PURPOSE
11 CSA OR OTHER APPROVAL IECEx Exd IIB T3
12 "T" RATING T3 T3 T3
ISSUE FOR REVIEW
DESCRIPTION

13 ENCLOSURE TYPE* NEMA 4X WITH X - PURGE (NOTE 1, 2)

14 LOCATION (INDOOR OR OUTDOOR) IN OUT IN OUT INDOOR


15 MOUNTING A.SHELTER B40-AS-0002 A.SHELTER B40-AS-0002

16 MAXIMUM TEST PRESSURE* kPa(ga)(PSIG)


HOLD
17 (RELIEF VALVE SETTINGS)
18 P&ID NUMBER BA-220959.001
19 POWER SUPPLY 120 VOLTS 60 Hz AMPERES
SERVICES / UTILITIES

20 INSTRUMENT AIR SUPPLY* 75 MIN 125 MAX PSIG CU.METERS / MIN


21 COOLING WATER* PRESSURE kPa(ga)(PSIG) TEMPERATURE OC (OF)

22 STEAM* PRESSURE kPa(ga)(PSIG) TEMPERATURE


OC (OF)

23 CARRIER GAS* CYL / REG. TYPE* CONSUMPTION*


01506-001
JO/EWO
B-10-

24 HYDROGEN GAS* CYL / REG. TYPE* CONSUMPTION*


25
20/04/2015

26 ANALOG (VALUE)
SIGNAL OUTPUT

FF BUS for each component DIGITAL (TYPE)


DATE

27 LOCAL SIGNAL(S) FOR MAINTENANCE USER SELECTABLE


28 ALARMS (NOTE 3) ALARM (1) ALARM (2) ALARM (3) ALARM (4)
REV.
NO.
A

29 ALARM (5) ALARM (6)


DISCIPLINE
ENGINEER 30
G. CONTARDI 31 STREAM COMP. (COMMON NAMES) TYPICAL CONCENTRATIONS DESIRED COMPONENTS TREND
DATE: 20/04/2015 32 OR CHEMICAL FORMULAS) MIN. NORM. MAX. (UNITS) [/] [//] SPAN [/]
PROJECT 33 NOx (SE NOTE 4) 60 108 ppm vol 0200
ENGINEER
34 CO (SEE NOTE 5) 20 ppm vol 0200
35 O2 13,23 13,90 17,97 % vol 020
STREAM COMPOSITION ( 1-SHEET / STREAM )

DATE:
CERTIFIED 36
M. CALLEGARO 37
DATE: 20/04/2015 38 NOTE: COMPONENTS TO BE READ OUT OR TRENDED ARE INDICATED BY PURCHASER [/]
CONSTRUCTION
AGENCY 39 COMPONENTS TO BE TESTED AT MID-SCALE VALUES ARE INDICATED BY PURCHASER [//]
40 STREAM WASTE GAS
DATE: 41 TEMPERATURE: INLET OC (OF)
MAX. (1023) NORMAL MIN.
OPERATIONS 42 PRESSURE: INLET kPa(ga)(PSIG) MAX. NORMAL MIN.
43 OUTLET kPa(ga)(PSIG) MAX. NORMAL MIN.
DATE: 44 PHASE LIQUID VAPOR 2-PHASE (DESCRIBE)
CONTROL NUMBER

45 CORROSIVE COMPONENTS SEE COMPOSITION


VERIFICATION

46 SOUR SERVICE (PER NACE-MR-01-75) YES NO


EDSD

47 SOLIDS: PERCENT & PARTICLE SIZE PERCENT MICROMETERS


DATE:

48 STABILITY (POLYMERIZES, DECOMPOSES) STABLE


BY:

49 OTHER STREAM DATA (SG. VISCOSITY)


REVISION CERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,

50 OTHER CONTAMINANTS (OIL DISSOLVED)


THIS INDICATES THAT REV. NO.__________
OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE

51

NOTES:

ISS FOR B40-AIT-7411 DWG. TYPE PLANT NO. INDE DRAWING NO. SHT.NO. REV.NO.

WASTE GAS FROM HEATER B40-E-7000 BYPASS STACK ISS


B40 J BE-126165 19 of
(DCC) NO.

KHURAIS FACILITIES EXPANSION & SATELLITE GOSP


21 A
KHURAIS SAUDI ARABIA JO / EWO: 10-03452
SAIPEM JOB 032184 DOC. NO. B40-SA-E-051154 EDSD/2616-1002.XLS
Saudi Aramco 2616-ENG(10/2002)
PMT OPRNS

SAUDI ARABIAN OIL COMPANY


INSTRUMENT SPECIFICATION SHEET - CONTINUOS EMISSIONS MONITORING
52 DETECTOR TYPE IR LOCATION PART OF ANALYZER
53 NO. OF VALVES

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
N.A. NO. OF COLUMNS N.A.
ENGG CERT
M. C.

54 COLUMN CONFIGURATION N.A.


ANALYZER

55 CYCLE TIME min. CONTINUOUS


G. C.

56 MATERIALS CONTACTING STREAM VITON


57 SIZE * mm (in.) WIDE HIGH DEEP WEIGHT kg(lb)
58
59
60 AUTO ZERO YES NO BEFORE EACH PEAK YES NO
61 ANALYSIS REPORTS N.A.
62 TYPE N.A.
PROGRAMMER

63 MEMORY PROTECTION YES


ISSUE FOR REVIEW
DESCRIPTION

64 SIZE mm (in.) WIDE HIGH DEEP WEIGHT KG kg(lb)


65
66
67 SUPPLIED BY PURCHASER VENDOR
68 PREFERRED MATERIALS
69 SAMPLE RETURN TO
SAMPLE CONDITIONING

AMBIENT YES FLARE PROCESS PRESS kPa(ga) (PSIG)


70 CONNECTION SIZES INLET 1/4"NPT OUTLET 1/4"NPT
71 REQUIREMENTS (NOTE4) PUMP YES ASPIRATION AS REQUIRED
72 VAPORIZER AS REQUIRED REDUCERS YES
73 SAMPLE PROBE / SIZE / RATING 6", 150# WITH HASTELLOY C276 PROBE TUBE
74 DISTANCE TAKE-OFF / ANALYZER m HOLD
20/04/2015 01506-001
JO/EWO
B-10-

75
76
DATE

NOTES:
REV.
NO.
A

1. PROGRAMMER/CONTROL UNIT ARE BUILT-IN WITH THE ANALYZER.


DISCIPLINE
ENGINEER
2. ANALYZER & NOX CONVERTER MOUNTED IN NEMA 4X STAINLESS STELL ENCLOSURE WITH X PURGE TO SUITABLE THE SPECIFIED AREA
G. CONTARDI
CLASSIFICATION.
20/04/2015
DATE:
3. ANALYZER COMMON FAULT & CALIB/MAINT ALARMS WILL BE WIRED AS REQUIRED.
PROJECT
ENGINEER
4. @ 15% O2 DRY.

DATE:
5. AT BASE LOAD.
CERTIFIED
6. FOR STREAM COMPOSITION ONLY SEE STREAM COMPOSITION SHEET ON SHEET 3 OF 21
M. CALLEGARO
20/04/2015
DATE:
CONSTRUCTION
AGENCY * INFORMATION TO BE SUPPLIED BY VENDOR.

DATE:
OPERATIONS

DATE:
CONTROL NUMBER
VERIFICATION
EDSD

DATE:
BY:
REVISION CERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE

ISS FOR B40-AIT-7411 DWG. TYPE PLANT NO. INDE DRAWING NO. SHT.NO. REV.NO.

WASTE GAS FROM HEATER B40-E-7000 BYPASS STACK ISS


B40 J BE-126165 20 of
(DCC) NO.

KHURAIS FACILITIES EXPANSION & SATELLITE GOSP


21 A
KHURAIS SAUDI ARABIA JO / EWO: B-10-01506-001
SAIPEM JOB 032184 DOC. NO. B40-SA-E-051154 EDSD/2616-1002.XLS
Saudi Aramco 8020-512-ENG (09/2000)
SAUDI ARABIAN OIL COMPANY
PMT OPRNS
INSTRUMENT SPECIFICATION SHEET - OXYGEN ANALYZER
TAG NO. SERVICE:
ENGG CERT

GENERAL CONTROL UNIT


M. C.

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
1. TAG NO. B40-AIT-7411 24. NUMBER OF CHANNELS: ONE
G. C.

2. SERVICE Waste gas from boiler B40-E-7000 bypass stack 25. METER SCALE RANGE: 0-20% Vol
3. P & ID NUMBER BA-220959.001 26. LOCATION: INDOORS OUTDOORS
4. MANUFACTURER 27. CONSTRUCTION:GENERAL PURPOSE
5. MODEL NUMBER CLASS I GROUP D DIV. I
6. MATERIAL SOURCE CLASS I GROUP D DIV. II
7. TYPE: FUEL GAS TRACE O2 28. ENCLOUSE (NEMA): NEMA 4X / IP66

DISSOLVED O2 29. OUTPUT SIGNAL: 4-20mA OTHER FF BUS


8. INSTALLATION: PERMANENT PORTABLE 30. RELAY CONTACT ARRANGEMENT DPDT OTHER
9. SENSOR LOCATION: INDOORS OUTDOORS 31. RELAY CONTACT RATING:Amps VOLTS 24VDC
ISSUE FOR REVIEW

10. CONTROL UNIT: INTEGRAL 32. ALARM SET POINTS:


DESCRIPTION

REMOTE LOW HIGH


DISTANCE: m. 33. LATCHING ALARMS:YES NO
11. RANGE: 0-20% Vol 34. POWER SUPPLY REQUIREMENTS:
12. CONSTRUCTION: GENERAL PURPOSE 117 V 60 HZ OTHER 120 V 60 Hz
CLASS I GROUP D DIV. I 35. MFR. MODEL NO.:
CLASS I GROUP D DIV. II 36.
13. NUMBER OF STREAMS MONITORED 37.
SINGLE MULTIPLE NUMBER: 38.
39.
SENSOR (PROBE) 40.
41.
14. NUMBER OF SENSORS: ONE
JO/EWO

15. SENSOR LENGTH: *


01506-
B-10-

OPTIONS
16. SENSOR TYPE: Z2O2 ELECTROCHEMICAL
17. OTHER PARAMAGNETIC
20/04/15
DATE

18. CONDUIT CONNECTION SIZE: * 42. BATTERY CHARGER: YES NO


19. ENCLOSURE (NEMA): NEMA 4X / IP66 43. RECORDER: 100 mm strip 300 mm circular
REV.

20. MFR. MODEL NO.:


NO.

4" strip 12" circular


A

DISCIPLINE
21. CHART SPEED:
ENGINEER
22. SCALE:
G. CONTARDI
23. 44. RECORDER POWER SUPPLY:
MAR. 15
DATE:
45. SIGNAL AMPLIFIER: YES NO
PROJECT
ENGINEER 46. PRESSURE REGULATOR:
YES NO

PROCESS DATA MIN. FLOW NORMAL FLOW MAX. FLOW


DATE:
CERTIFIED No.1 No.2 No.3 No.4 No.1 No.2 No.3 No.4 No.1 No.2 No.3 No.4
M. CALLEGARO
47. STREAMS:
20/04/2015
DATE: 48. FLUID:
CONSTRUCTION
AGENCY 49. OXYGEN CONCENTRATION ppb. % O2
50. CONDUCTANCE, MICROSEIMENS (mho)
DATE: 51. DISSOLVED SOLIDS, ppm:
OPERATIONS
52. Ph:
53. SAMPLE PRESSURE, kPa(ga) (PSIG) see notes
DATE: 54. SAMPLE TEMPERATURE, OC (OF)
CONTROL NUMBER

55. DEW POINT, OC (OF)


VERIFICATION

56. SAMPLE FLOW RATE: L/m (ft3/m)


EDSD

57. CORROSIVES:
DATE:

58.
59.
BY:

60.
REVISION CERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE

NOTES: THIS SPECIFICATION SHEET IS TO BE USED IN CONJUNCTION WITH 34-SAMSS 512.


FOR STREAM COMPOSITION SEE STREAM COMPOSITION SHEET ON SHEET 3 OF 21.

ISS FOR B40-AIT-7411 DWG. TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.

WASTE GAS FROM HEATER B40-E-7000 BYPASS STACK ISS


B40 J B E -126165 21 of
(DCC) NO.

KHURAIS FACILITIES EXPANSION & SATELLITE GOSP


21 A
KHURAIS SAUDI ARABIA JO / EWO: B- 10-1506-001