Engineering Data
Motor Selection .............................................................................................. 3
Maximum Motor Horsepower and Frame Sizes ........................................... 3
Motor Starting Torque ..................................................................................... 4
Wheel Moments of Inertia ............................................................................... 4
V-Belt Drives ................................................................................................... 4
High Temperature RPM Derating Factors ...................................................... 4
High Temperature Operating Limits ............................................................... 4
Effects of Air Density ...................................................................................... 5
Minimum Transport Velocities for Material Conveying .................................. 6
Direct Drive Arrangements .............................................................................. 7
Sample Fan Selection .................................................................................8-9
Dimensional Data
Sizes 5-19 Arrangement 1 ........................................................................... 100
Sizes 5-19 Arrangement 9 ........................................................................... 101
Sizes 5-19 Arrangement 10 ......................................................................... 102
Sizes 21-41 Arrangement 1 and 9 ............................................................. 103
2
Engineering Data
Motor Selection
Greenheck industrial process fans can be supplied with any motor that is commercially available and is appropriate for the
fan size and performance required. The table shows motor frame sizes corresponding to those motors readily available. See
the maximum motor frame size chart below if motor is for arrangement 9 or 10 fans.
Notes: 1. Fractional horsepower motor frame sizes shown may change due to variations in voltage, special features and
manufacturer.
2. Motors shown are ball bearing, continuous duty. Two speed motors are two winding, 1/3 reduction in RPM.
3. Single phase motors are capacitor start.
4. Open frame motors have a 1.15 service factor. TE motors have a 1.0 service factor.
*Single speed three phase motors of 200 volts are available up to 100 horsepower, 230 volts up to 125 horsepower
and 460 or 575 volts up to 150 horsepower.
**Two speed three phase motors of 200 volts are available up to 10 horsepower, 230 volts up to 10 horsepower and
460 or 575 volts up to 25 horsepower.
3
Engineering Data
( )
2
2 2 FRPM 26 333 757 607 672 745 841
WR M = WR F x x (1.1)
MRPM 29 521 1186 949 1048 1304 1304
2
33 877 1995 2017 2342 2455 2455
WR M = The moment of inertia that the motor must2 be 37 1652 3145 3172 3698 3831 3831
capable of turning at the motor shaft, lb-ft
41 2477 4707 4749 5523 5807 5807
2
WR F = The moment of inertia of the fan wheel, lb-ft2
Heat Slinger
501
Steel Shaft Seal
to 1 and 8
Stainless Steel High Temperature Grease
800F
High Temperature Paint
801
Consult the factory for
to Stainless Steel 1 and 8
specific application
1000F
4
Engineering Data
The accompanying table gives air density correction factors for non-standard temperatures and elevations.
The example below shows the relationship of fan performance at sea level and at 2000 ft. elevation and 400F.
Example:
The following example shows how to properly select the fan described above:
1. Since the air volume delivered by the fan is not affected by density, airflow Sea Level Density Correction Factor = 1.0
26-IPO
Density equals 0.075 lb. per cubic foot 1560 RPM
remains 15,000 cfm. 2,000 ft. Density Correction Factor = 0.573
Density equals 0.043 lb per cubic foot
2. Determine correction factor from chart for an elevation of 2000 feet and air 35.0
temperature of 400F. The correction factor is 0.573.
3. Divide the specified operating static pressure by the correction factor to 30.0
l7
Sea Leve 0F 28 inch SP
300
4. Refer to the fan performance table for a 26 IPO. At 15,000 cfm and 28 in.
20.0 200
static pressure: Fan RPM = 1560, BHP = 111.
Bhp
6. Since the horsepower selected refers to standard air density, this must be
corrected to reflect actual BHP at the lighter operating air. 10.0
111 Bhp
100
F
l
ve
Le
a
Se F 63 Bhp
00 50
If a fan is selected to operate at high temperatures, the motor must be of 5.0
200
0 ft
. 4
sufficient horsepower to handle the increased load at any lower operating 15,000 cfm
0
temperature where the air is more dense. Assume the air entering the 26 IPO fan 0.0
0 1 2 3 4 5 6
at start-up is 0F. For 0F and 2000 feet elevation the air density correction factor cfm x 10,000
is 1.071. BHP at 0F = 111 x 1.071 = 118.9, therefore, a 125 HP motor is required.
5
Conveying Velocities
6
Direct Drive Arrangements
Arrangement 4
Arrangement 8
7
Sample Fan Selection
The purpose of these two pages is to demonstrate The following example explains the model number code for
the manual industrial process fan selection process. industrial process fans.
These pages also contain helpful tips to check your fan
selection as well as a step by step set of instructions on 21 - IPA - HD
how to use this manual to properly select an industrial
process fan.
Fan Size
An important point to remember when manually selecting 5 thru 41 Construction
an industrial fan is that more than one fan is available to SD Standard Duty
Wheel Type HD Heavy Duty
meet the desired performance (cfm and static pressure). IPO - Open Radial
Selection criteria such as unit size, efficiency, speed, IPW - Wool (Backplated)
outlet velocity, horsepower, or construction material may IPA - Air Handling
also dictate which fan is chosen.
Performance certified is for model IPA arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
8
Fan Selection Procedure
STEP 1 STEP 2
Enter the performance table with the desired CFM and Enter the fan curve with the desired CFM and static
static pressure. Obtain the fan RPM, operating BHP pressure. Obtain the fan operating point, % WOV, operating
and duty. HP, free air HP and verify fan duty using the curve shading.
EXAMPLE: For this example we will use 8600 CFM at EXAMPLE: For this example the fan operating point is at
9.0 in. wg. This gives us a fan RPM of 1153 requiring 41% WOV using a 20 HP motor. The free air HP is 30 and can
17.6 BHP, in standard duty construction. be found by following the fan RPM curve down to 0 in. static
NOTE: The motor size can be compared to the pressure.
maximum motor frame size table found at the top of the NOTE: The free air HP for industrial fans must be considered
performance table. Motor frame sizes are based on fan because the wheels have overloading characteristics. This
arrangement. means the required motor horsepower increases as static
pressure decreases.
21 IPA
STEP 3
G Enter the fan sound table with the
fan RPM from the performance table
and the % WOV from the fan curve.
Obtain the eight octave ratings for
inlet (Lwi) and outlet (Lwi) sound
power.
EXAMPLE: For this example, the
eight octave ratings are circled in the
fan sound table.
Step 2 NOTE: The exact % WOV for your
desired performance point can be
found using the equation at the top
of the fan sound table if it is not
published. The eight octave ratings
can then be found using interpolation.
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
9
5 IPO
Wheel Diameter = 834 in.
Maximum Max. Motor Frame Size
Outlet Area = 0.12 ft2
RPM MHP Arr. 9 Arr. 10
Tip Speed = 2.29 x RPM
Minimum Starting HP = 5000 2 145T 145T
Performance certified is for model IPO arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
10
5 IPO
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
11
7 IPO
Wheel Diameter = 1218 in.
Maximum Max. Motor Frame Size
Outlet Area = 0.26 ft2
RPM MHP Arr. 9 Arr. 10
Tip Speed = 3.17 x RPM
Minimum Starting HP = 5000 10 215T 184T
12
7 IPO
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
13
9 IPO
Wheel Diameter = 1558 in.
Maximum Max. Motor Frame Size
Outlet Area = 0.44 ft2
RPM MHP Arr. 9 Arr. 10
Tip Speed = 4.09 x RPM
Minimum Starting HP = 4156 20 256T 215T
Performance certified is for model IPO arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
14
9 IPO
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
15
11 IPO
Maximum Max. Motor Frame Size
Wheel Diameter = 1918 in.
Duty RPM MHP Arr. 9 Arr. 10
Outlet Area = 0.66 ft2
Standard 3395 30 256T 254T
Tip Speed = 5.01 x RPM
Minimum Starting HP = 13 Heavy 3994 50 256T NA
Performance certified is for model IPO arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
16
11 IPO
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
17
13 IPO
Maximum Max. Motor Frame Size
Wheel Diameter = 2258 in.
Duty RPM MHP Arr. 9 Arr. 10
Outlet Area = 0.92 ft2
Standard 2870 50 286T 284T
Tip Speed = 5.92 x RPM
Minimum Starting HP = 12 Heavy 3377 75 286T NA
Performance certified is for model IPO arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
18
13 IPO
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
19
15 IPO
Maximum Max. Motor Frame Size
Wheel Diameter = 2618 in.
Duty RPM MHP Arr. 9 Arr. 10
Outlet Area = 1.23 ft2
Standard 2486 60 286T 284T
Tip Speed = 6.84 x RPM
Minimum Starting HP = 12 Heavy 2924 100 286T NA
Performance certified is for model IPO arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
20
15 IPO
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
21
17 IPO
Maximum Max. Motor Frame Size
Wheel Diameter = 2958 in.
Duty RPM MHP Arr. 9 Arr. 10
Outlet Area = 1.56 ft2
Standard 2192 75 326T 324T
Tip Speed = 7.76 x RPM
Minimum Starting HP = 34 Heavy 2579 125 326T NA
Performance certified is for model IPO arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
22
17 IPO
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
23
19 IPO
Maximum Max. Motor Frame Size
Wheel Diameter = 33 in.
Duty RPM MHP Arr. 9 Arr. 10
Outlet Area = 1.94 ft2
Standard 1968 100 365T 326T
Tip Speed = 8.64 x RPM
Minimum Starting HP = 1 Heavy 2315 150 365T NA
Performance certified is for model IPO arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
24
19 IPO
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
25
21 IPO
Maximum Max. Motor Frame Size
Wheel Diameter = 3612 in.
Duty RPM MHP Arr. 9 Arr. 10
Outlet Area = 2.34 ft2
Standard 1779 125 365T NA
Tip Speed = 9.56 x RPM
Minimum Starting HP = 1 Heavy 2093 200 365T NA
Performance certified is for model IPO arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
26
21 IPO
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
27
23 IPO
Maximum Max. Motor Frame Size
Wheel Diameter = 40 in.
Duty RPM MHP Arr. 9 Arr. 10
Outlet Area = 2.8 ft2
Standard 1623 150 365T NA
Tip Speed = 10.47 x RPM
Minimum Starting HP = 2 Heavy 1910 200 365T NA
Performance certified is for model IPO arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
28
23 IPO
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
29
26 IPO
Maximum Max. Motor Frame Size
Wheel Diameter = 4518 in.
Duty RPM MHP Arr. 9 Arr. 10
Outlet Area = 3.58 ft2
Standard 1439 200 405T NA
Tip Speed = 11.81 x RPM
Minimum Starting HP = 5 Heavy 1693 300 405T NA
Performance certified is for model IPO arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
30
26 IPO
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
31
29 IPO
Maximum Max. Motor Frame Size
Wheel Diameter = 5012 in.
Duty RPM MHP Arr. 9 Arr. 10
Outlet Area = 4.54 ft2
Standard 1286 200 405T NA
Tip Speed = 13.22 x RPM
Minimum Starting HP = 10 Heavy 1513 350 405T NA
Performance certified is for model IPO arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
32
29 IPO
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
33
33 IPO
Maximum Max. Motor Frame Size
Wheel Diameter = 5712 in.
Duty RPM MHP Arr. 9 Arr. 10
Outlet Area = 5.87 ft2
Standard 1129 300 405T NA
Tip Speed = 15.05 x RPM
Minimum Starting HP = 20 Heavy 1329 450 405T NA
Performance certified is for model IPO arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
34
33 IPO
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
35
37 IPO
Maximum Max. Motor Frame Size
Wheel Diameter = 6438 in.
Duty RPM MHP Arr. 9 Arr. 10
Outlet Area = 7.36 ft2
Standard 1009 350 405T NA
Tip Speed = 16.85 x RPM
Minimum Starting HP = 25 Heavy 1187 550 405T NA
Performance certified is for model IPO arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
36
37 IPO
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
37
41 IPO
Maximum Max. Motor Frame Size
Wheel Diameter = 7114 in.
Duty RPM MHP Arr. 9 Arr. 10
Outlet Area = 9.09 ft2
Standard 911 400 405T NA
Tip Speed = 18.65 x RPM
Minimum Starting HP = 40 Heavy 1072 700 405T NA
Performance certified is for model IPO arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
38
41 IPO
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
39
5 IPW
Wheel Diameter = 834 in.
Maximum Max. Motor Frame Size
Outlet Area = 0.12 ft2
RPM MHP Arr. 9 Arr. 10
Tip Speed = 2.29 x RPM
Minimum Starting HP = 5000 2 145T 145T
Performance certified is for model IPW arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
40
5 IPW
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
41
7 IPW
Wheel Diameter = 1218 in.
Maximum Max. Motor Frame Size
Outlet Area = 0.26 ft2
RPM MHP Arr. 9 Arr. 10
Tip Speed = 3.17 x RPM
Minimum Starting HP = 5000 10 215T 184T
Performance certified is for model IPW arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
42
7 IPW
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
43
9 IPW
Wheel Diameter = 1558 in.
Maximum Max. Motor Frame Size
Outlet Area = 0.44 ft2
RPM MHP Arr. 9 Arr. 10
Tip Speed = 4.09 x RPM
Minimum Starting HP = 13 4156 20 256T 215T
Performance certified is for model IPW arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
44
9 IPW
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
45
11 IPW
Maximum Max. Motor Frame Size
Wheel Diameter = 1918 in.
Duty RPM MHP Arr. 9 Arr. 10
Outlet Area = 0.66 ft2
Standard 3395 30 256T 254T
Tip Speed = 5.01 x RPM
Minimum Starting HP = Heavy 3994 50 256T NA
46
11 IPW
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
47
13 IPW
Maximum Max. Motor Frame Size
Wheel Diameter = 2258 in.
Duty RPM MHP Arr. 9 Arr. 10
Outlet Area = 0.92 ft2
Standard 2870 50 286T 284T
Tip Speed = 5.92 x RPM
Minimum Starting HP = Heavy 3377 75 286T NA
Performance certified is for model IPW arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
48
13 IPW
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
49
15 IPW
Maximum Max. Motor Frame Size
Wheel Diameter = 2618 in.
Duty RPM MHP Arr. 9 Arr. 10
Outlet Area = 1.23 ft2
Standard 2486 60 286T 284T
Tip Speed = 6.84 x RPM
Minimum Starting HP = Heavy 2924 100 286T NA
Performance certified is for model IPW arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
50
15 IPW
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
51
17 IPW
Maximum Max. Motor Frame Size
Wheel Diameter = 2958 in.
Duty RPM MHP Arr. 9 Arr. 10
Outlet Area = 1.56 ft2
Standard 2192 75 326T 324T
Tip Speed = 7.76 x RPM
Minimum Starting HP = 1 Heavy 2579 125 326T NA
Performance certified is for model IPW arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
52
17 IPW
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
53
19 IPW
Maximum Max. Motor Frame Size
Wheel Diameter = 33 in.
Duty RPM MHP Arr. 9 Arr. 10
Outlet Area = 1.94 ft2
Standard 1968 100 365T 326T
Tip Speed = 8.64 x RPM
Minimum Starting HP = 2 Heavy 2315 150 365T NA
Performance certified is for model IPW arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
54
19 IPW
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
55
21 IPW
Maximum Max. Motor Frame Size
Wheel Diameter = 3612 in.
Duty RPM MHP Arr. 9 Arr. 10
Outlet Area = 2.34 ft2
Standard 1779 125 365T NA
Tip Speed = 9.56 x RPM
Minimum Starting HP = 2 Heavy 2093 200 365T NA
Performance certified is for model IPW arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
56
21 IPW
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
57
23 IPW
Maximum Max. Motor Frame Size
Wheel Diameter = 40 in.
Duty RPM MHP Arr. 9 Arr. 10
Outlet Area = 2.8 ft2
Standard 1623 150 365T NA
Tip Speed = 10.47 x RPM
Minimum Starting HP = 3 Heavy 1910 200 365T NA
Performance certified is for model IPW arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
58
23 IPW
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
59
26 IPW
Maximum Max. Motor Frame Size
Wheel Diameter = 4518 in.
Duty RPM MHP Arr. 9 Arr. 10
Outlet Area = 3.58 ft2
Standard 1439 200 405T NA
Tip Speed = 11.81 x RPM
Minimum Starting HP = 712 Heavy 1693 300 405T NA
Performance certified is for model IPW arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
60
26 IPW
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
61
29 IPW
Maximum Max. Motor Frame Size
Wheel Diameter = 5012 in.
Duty RPM MHP Arr. 9 Arr. 10
Outlet Area = 4.54 ft2
Standard 1286 200 405T NA
Tip Speed = 13.22 x RPM
Minimum Starting HP = 15 Heavy 1513 350 405T NA
Performance certified is for model IPW arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
62
29 IPW
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
63
33 IPW
Maximum Max. Motor Frame Size
Wheel Diameter = 5712 in.
Duty RPM MHP Arr. 9 Arr. 10
Outlet Area = 5.87 ft2
Standard 1129 300 405T NA
Tip Speed = 15.05 x RPM
Minimum Starting HP = 25 Heavy 1329 450 405T NA
Performance certified is for model IPW arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
64
33 IPW
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
65
37 IPW
Maximum Max. Motor Frame Size
Wheel Diameter = 6438 in.
Duty RPM MHP Arr. 9 Arr. 10
Outlet Area = 7.36 ft2
Standard 1009 350 405T NA
Tip Speed = 16.85 x RPM
Minimum Starting HP = 40 Heavy 1187 550 405T NA
Performance certified is for model IPW arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
66
37 IPW
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
67
41 IPW
Maximum Max. Motor Frame Size
Wheel Diameter = 7114 in.
Duty RPM MHP Arr. 9 Arr. 10
Outlet Area = 9.09 ft2
Standard 911 400 405T NA
Tip Speed = 18.65 x RPM
Minimum Starting HP = 50 Heavy 1072 700 405T NA
Performance certified is for model IPW arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
68
41 IPW
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
69
5 IPA
Wheel Diameter = 834 in.
Maximum Max. Motor Frame Size
Outlet Area = 0.12 ft2
RPM MHP Arr. 9 Arr. 10
Tip Speed = 2.29 x RPM
Minimum Starting HP = 5000 2 145T 145T
Performance certified is for model IPA arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
70
5 IPA
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
71
7 IPA
Wheel Diameter = 1218 in.
Maximum Max. Motor Frame Size
Outlet Area = 0.26 ft2
RPM MHP Arr. 9 Arr. 10
Tip Speed = 3.17 x RPM
Minimum Starting HP = 5000 10 215T 184T
Performance certified is for model IPA arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
72
7 IPA
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
73
9 IPA
Wheel Diameter = 1558 in.
Maximum Max. Motor Frame Size
Outlet Area = 0.44 ft2
RPM MHP Arr. 9 Arr. 10
Tip Speed = 4.09 x RPM
Minimum Starting HP = 13 4156 20 256T 215T
Performance certified is for model IPA arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
74
9 IPA
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
75
11 IPA
Maximum Max. Motor Frame Size
Wheel Diameter = 1918 in.
Duty RPM MHP Arr. 9 Arr. 10
Outlet Area = 0.66 ft2
Standard 3395 30 256T 254T
Tip Speed = 5.01 x RPM
Minimum Starting HP = 12 Heavy 3994 50 256T NA
Performance certified is for model IPA arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
76
11 IPA
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
77
13 IPA
Maximum Max. Motor Frame Size
Wheel Diameter = 2258 in.
Duty RPM MHP Arr. 9 Arr. 10
Outlet Area = 0.92 ft2
Standard 2870 50 286T 284T
Tip Speed = 5.92 x RPM
Minimum Starting HP = Heavy 3377 75 286T NA
Performance certified is for model IPA arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
78
13 IPA
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
79
15 IPA
Maximum Max. Motor Frame Size
Wheel Diameter = 2618 in.
Duty RPM MHP Arr. 9 Arr. 10
Outlet Area = 1.23 ft2
Standard 2486 60 286T 284T
Tip Speed = 6.84 x RPM
Minimum Starting HP = 34 Heavy 2924 100 286T NA
Performance certified is for model IPA arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
80
15 IPA
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
81
17 IPA
Maximum Max. Motor Frame Size
Wheel Diameter = 2958 in.
Duty RPM MHP Arr. 9 Arr. 10
Outlet Area = 1.56 ft2
Standard 2192 75 326T 324T
Tip Speed = 7.76 x RPM
Minimum Starting HP = 1 Heavy 2579 125 326T NA
Performance certified is for model IPA arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
82
17 IPA
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
83
19 IPA
Maximum Max. Motor Frame Size
Wheel Diameter = 33 in.
Duty RPM MHP Arr. 9 Arr. 10
Outlet Area = 1.94 ft2
Standard 1968 100 365T 326T
Tip Speed = 8.64 x RPM
Minimum Starting HP = 2 Heavy 2315 150 365T NA
Performance certified is for model IPA arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
84
19 IPA
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
85
21 IPA
Maximum Max. Motor Frame Size
Wheel Diameter = 3612 in.
Duty RPM MHP Arr. 9 Arr. 10
Outlet Area = 2.34 ft2
Standard 1779 125 365T NA
Tip Speed = 9.56 x RPM
Minimum Starting HP = 2 Heavy 2093 200 365T NA
Performance certified is for model IPA arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
86
21 IPA
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
87
23 IPA
Maximum Max. Motor Frame Size
Wheel Diameter = 40 in.
Duty RPM MHP Arr. 9 Arr. 10
Outlet Area = 2.8 ft2
Standard 1623 150 365T NA
Tip Speed = 10.47 x RPM
Minimum Starting HP = 3 Heavy 1910 200 365T NA
Performance certified is for model IPA arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
88
23 IPA
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
89
26 IPA
Maximum Max. Motor Frame Size
Wheel Diameter = 4518 in.
Duty RPM MHP Arr. 9 Arr. 10
Outlet Area = 3.58 ft2
Standard 1439 200 405T NA
Tip Speed = 11.81 x RPM
Minimum Starting HP = 712 Heavy 1693 300 405T NA
Performance certified is for model IPA arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
90
26 IPA
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
91
29 IPA
Maximum Max. Motor Frame Size
Wheel Diameter = 5012 in.
Duty RPM MHP Arr. 9 Arr. 10
Outlet Area = 4.54 ft2
Standard 1286 200 405T NA
Tip Speed = 13.22 x RPM
Minimum Starting HP = 15 Heavy 1513 350 405T NA
Performance certified is for model IPA arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
92
29 IPA
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
93
33 IPA
Maximum Max. Motor Frame Size
Wheel Diameter = 5712 in.
Duty RPM MHP Arr. 9 Arr. 10
Outlet Area = 5.87 ft2
Standard 1129 300 405T NA
Tip Speed = 15.05 x RPM
Minimum Starting HP = 25 Heavy 1329 450 405T NA
Performance certified is for model IPA arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
94
33 IPA
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
95
37 IPA
Maximum Max. Motor Frame Size
Wheel Diameter = 6438 in.
Duty RPM MHP Arr. 9 Arr. 10
Outlet Area = 7.36 ft2
Standard 1009 350 405T NA
Tip Speed = 16.85 x RPM
Minimum Starting HP = 40 Heavy 1187 550 405T NA
Performance certified is for model IPA arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
96
37 IPA
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
97
41 IPA
Maximum Max. Motor Frame Size
Wheel Diameter = 7114 in.
Duty RPM MHP Arr. 9 Arr. 10
Outlet Area = 9.09 ft2
Standard 911 400 405T NA
Tip Speed = 18.65 x RPM
Minimum Starting HP = 50 Heavy 1072 700 405T NA
Performance certified is for model IPA arrangement 1, installation type D - ducted inlet, ducted outlet. Power rating (Bhp) does not include
transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
98
41 IPA
The sound power level ratings shown are in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet
Lwi, Lwi A and outlet Lwo, Lwo A sound power levels for installation type D: ducted inlet, ducted outlet. Ratings include the effects of duct
end correction. The AMCA Certified Ratings Seal applies to air performance ratings only.
99
Dimensional Data
Data shown on these pages is for general information only and should not be used for exact installation dimensions. All
columns are rounded to the nearest 1/8 inch. For detailed dimensional data refer to the appropriate submittal drawing.
All dimensional drawings represent clockwise rotation. Counterclockwise would be a mirror image and would not affect
dimensions. Rotation is determined from the drive side of the unit.
Arrangement 1
Standard Duty Sizes 5 - 19
Heavy Duty Sizes 11 - 19
G
J A
C B
Clockwise Top Horizontal (TH) discharge shown above
A B
G G
Size TH UB TAU BAU C D Standard Heavy J
TH BH UB DB TAU BAU TAD BAD Duty Duty
BH DB BAD TAU
5 19 1778 1914 1812 2214 1712 1858 18 1434 1378 1318 1714 1812 1112 434 NA 514
7 2414 2278 2234 2358 2712 2238 24 2318 1838 1918 1838 2258 2334 14 612 NA 714
9 3078 2878 2814 2978 3412 2838 3038 2938 2318 2434 2334 2878 2812 1712 814 NA 914
11 3714 3434 3334 36 4112 3418 3658 3538 2734 30 2834 3478 3334 21 10 1018 1114
13 48 8
5
45 4
3
44 21
47 4
1
53 4
3
44 8
7
48 46 8
3
32 43
35 8 3
33 8
7
41 81
44 4
1
29 21
11 8
7
12 1338
15 5134 4814 4634 50 5712 4738 5078 49 3734 41 3914 4712 4612 2912 1358 1334 1538
17 5734 5378 5214 5578 6438 5234 5678 5434 4318 4658 4458 5418 5134 3212 1538 1512 1738
19 64 8
5
60 8
1
58 41
62 8
3
71 4
3
59 63 2 1
61 4
1
47 85
51 4 3
49 2
1
60 57 8
1
36 21
17 8
1
17 4
1
1938
Due to Greenhecks policy of continuous product improvement, dimensions are subject to change.
For complete dimensional information refer to the applicable CAPS submittal drawing.
A
A A A
D D D D
BH BAU UB TAU
B B B
A
A
D D D
TAD DB BAD
100
Dimensional Data
Data shown on these pages is for general information only and should not be used for exact installation dimensions. All
columns are rounded to the nearest 1/8 inch. For detailed dimensional data refer to the appropriate submittal drawing.
All dimensional drawings represent clockwise rotation. Counterclockwise would be a mirror image and would not affect
dimensions. Rotation is determined from the drive side of the unit.
Arrangement 9
Standard Duty Sizes 5 - 19
Heavy Duty Sizes 11 - 19 G
J
A
C B
Clockwise Top Horizontal (TH) discharge shown above
A B
G G
Size TH UB TAU TAU C D Standard Heavy J
TH BH UB DB TAU BAU TAD BAD Duty Duty
BH DB BAD TAD
5 2312 2238 2334 23 2634 22 2318 2212 1434 1378 1318 1714 2412 16 434 NA 514
7 3014 2878 2838 2958 3312 2838 30 2918 1838 1918 1838 2258 3134 20 612 NA 714
9 3638 3438 3334 3538 40 3378 3578 3478 2318 2434 2334 2878 39 23 814 NA 914
11 4034 3814 3714 3912 45 3758 4018 3878 2734 30 2834 3478 4114 2412 10 1018 1114
13 48 8
5
45 4
3
44 2
1
47 4
1
53 43
44 87
48 46 8
3
32 4
3
35 8
3
33 8 7
41 8
1
48 4
1
29 21
11 8
7
12 1338
15 5134 4814 4634 50 5712 4738 5078 49 3734 41 3914 4712 5012 2912 1358 1334 1538
17 6114 5738 5534 5938 6778 5614 6038 5814 4318 4658 4458 5418 5434 36 1538 1512 1738
19 68 8
1
63 8
5
61 4
3
65 8
7
75 41
62 21
67 64 4
3
47 8
5
51 4
3
49 2 1
60 60 8
1
40 17 8
1
17 4
1
1938
Due to Greenhecks policy of continuous product improvement, dimensions are subject to change.
For complete dimensional information refer to the applicable CAPS submittal drawing.
A
A A A
D D D D
BH BAU UB TAU
B B B
A
A
D D D
TAD DB BAD
101
Dimensional Data
Data shown on these pages is for general information only and should not be used for exact installation dimensions. All
columns are rounded to the nearest 1/8 inch. For detailed dimensional data refer to the appropriate submittal drawing.
All dimensional drawings represent clockwise rotation. Counterclockwise would be a mirror image and would not affect
dimensions. Rotation is determined from the drive side of the unit.
Arrangement 10
Standard Duty Sizes 5 - 19
G
J
A
C B
Clockwise Top Horizontal (TH) discharge shown above
A B
Size TH UB TAU BAU C D G J
TH BH UB DB TAU BAU TAD BAD
BH DB BAD TAD
5 2312 2238 2334 23 2634 22 2318 2212 1434 1378 1318 1714 2518 16 434 514
7 28 4
3
27 8
3
27 4
1
28 8
1
32 26 8
7
28 2
1
27 8
5
18 8
3
19 81
18 83
22 8
5
29 8
3
18 2
1
6 2
1
714
9 3438 3238 3134 3338 38 3178 3378 3278 2318 2434 2334 2878 3458 21 814 914
11 4034 3814 3714 3912 45 3758 4018 3878 2734 30 2834 3478 3978 2412 10 1114
13 48 8
5
45 4
3
44 2
1
47 4
1
53 4
3
44 8
7
48 46 8
3
32 4
3
35 83
33 87
41 8
1
47 8
7
29 2
1
11 8
7
1338
15 5134 4814 4634 50 5712 4738 5078 49 3734 41 3914 4712 5018 2912 1358 1538
17 6114 5738 5534 5938 6778 5614 6038 5814 4318 4658 4458 5418 55 36 1538 1738
19 68 8
1
63 8
5
61 4
3
65 8
7
75 4
1
62 2
1
67 64 4
3
47 8
5
51 43
49 21
60 61 4
1
40 17 8
1
1938
Due to Greenhecks policy of continuous product improvement, dimensions are subject to change.
For complete dimensional information refer to the applicable CAPS submittal drawing.
A
A A A
D D D D
BH BAU UB TAU
B B B
A
A
D D D
TAD DB BAD
102
Dimensional Data
Data shown on these pages is for general information only and should not be used for exact installation dimensions. All
columns are rounded to the nearest 1/8 inch. For detailed dimensional data refer to the appropriate submittal drawing.
All dimensional drawings represent clockwise rotation. Counterclockwise would be a mirror image and would not affect
dimensions. Rotation is determined from the drive side of the unit.
Arrangement 1 and 9
Standard Duty Sizes 21 - 41
Heavy Duty Sizes 21 - 41
G
J A
C B
Clockwise Top Horizontal (TH) discharge shown above
A B D
G G
Size TH UB C BH UB, DB Standard Heavy J
TH BH UB DB TAU BAU TAU BAU TH Duty Duty
BH DB BAU TAU
21 6714 6214 6012 6434 7634 61 5314 5938 5478 6814 6338 36 36 36 1878 19 2138
23 70 4
1
67 4
3
63 67 2
1
80 4
3
66 8
3
58 21
65 60 4
1
74 87
65 83
36 39 36 20 8
7
21 2338
26 7712 77 69 7412 8918 7512 6512 7338 6778 8418 7258 39 4412 39 2312 2358 2612
29 8638 8538 7614 8278 9878 8358 7318 8218 7618 94 7512 43 49 43 2618 2614 2912
33 93 2
1
96 2
1
86 4
1
93 2
1
111 4
3
94 2
1
83 43
93 8
3
86 8
7
107 4
1
80 44 55 48 29 4
3
29 8
7
3312
37 10414 10814 9534 10414 12412 106 93 10438 9678 11912 8434 49 62 5312 3314 3338 3712
41 115 119 106 115 13712 11612 103 11478 10678 13178 8814 54 68 59 3634 3678 4112
Due to Greenhecks policy of continuous product improvement, dimensions are subject to change.
For complete dimensional information refer to the applicable CAPS submittal drawing.
B
B B B B
A
A A A A
D D D D D
BH BAU UB TAU UB
103
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change
specifications without notice.
Specific Greenheck product warranties are located on greenheck.com within the product
area tabs and in the Library under Warranties. Prepared to Support
Green Building Efforts
00.CVI.1005 R5 2-2013
P.O. Box 410 Schofield, WI 54476-0410 Phone (715) 359-6171 greenheck.com Copyright 2013 Greenheck Fan Corp.