Sie sind auf Seite 1von 8

226 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 23, NO.

1, MARCH 2008

STATCOM Impact Study on the Integration of a


Large Wind Farm into a Weak Loop Power System
Chong Han, Member, IEEE, Alex Q. Huang, Fellow, IEEE, Mesut E. Baran, Member, IEEE,
Subhashish Bhattacharya, Member, IEEE, Wayne Litzenberger, Senior Member, IEEE, Loren Anderson,
Anders L. Johnson, Member, IEEE, and Abdel-Aty Edris, Senior Member, IEEE

AbstractRecently, renewable wind energy is enjoying a rapid However, with wind being a geographically and climatically
growth globally to become an important green electricity source to uncontrollable resource and the nature of distributed wind in-
replace polluting and exhausting fossil fuel. However, with wind be- duction generators, the stability and power quality issues of inte-
ing an uncontrollable resource and the nature of distributed wind
induction generators, integrating a large-scale wind-farm into a grating large wind farm (WF) in grid may become pronounced,
power system poses challenges, particularly in a weak power sys- particularly into a weak power system.
tem. In the paper, the impact of static synchronous compensator Conventionally, the low-cost mechanical switched cap (MSC)
(STATCOM) to facilitate the integration of a large wind farm (WF) banks and transformer tap changers (TCs) are used to address
into a weak power system is studied. First, an actual weak power these issues related to stability and power quality. However, al-
system with two nearby large WFs is introduced. Based on the field
SCADA data analysis, the power quality issues are highlighted and though these devices help improve the power factor of WF and
a centralized STATCOM is proposed to solve them, particularly steady-state voltage regulation, the power quality issues, such as
the short-term (seconds to minutes) voltage fluctuations. Second, power fluctuations, voltage fluctuations, and harmonics, cannot
a model of the system, WF, and STATCOM for steady state and be solved satisfactorily by them because these devices are not
dynamic impact study is presented, and the model is validated by fast enough [3]. Moreover, the frequent switching of MSC and
comparing with the actual field data. Using simulated PV and QV
curves, voltage control and stability issues are analyzed, and the size TC to deal with power quality issues may even cause resonance
and location of STATCOM are assessed. Finally, a STATCOM con- and transient overvoltage, add additional stress on wind tur-
trol strategy for voltage fluctuation suppression is presented and bine gearbox and shaft, make themselves and turbines wear out
dynamic simulations verify the performance of proposed STAT- quickly and, hence, increase the maintenance and replacement
COM and its control strategy. cost [4]. Therefore, a fast shunt VAR compensator is needed to
Index TermsImpact study, static synchronous compensator address these issues more effectively, as has been pointed out in
(STATCOM), voltage fluctuation, voltage stability, wind farm many literatures [2], [4][7].
(WF). The static synchronous compensator (STATCOM) is consid-
ered for this application, because it provides many advantages, in
I. INTRODUCTION particular the fast response time (12 cycles) and superior volt-
age support capability with its nature of voltage source [8]. With
ECENTLY, mainly due to the technology innovation and
R cost reduction, renewable wind energy is enjoying a rapid
growth globally to become an important green electricity source
the recent innovations in high-power semiconductor switch,
converter topology, and digital control technology, faster STAT-
COM (quarter cycle) with low cost is emerging [9], which is
to replace polluting and exhausting fossil fuel. The wind turbines
promising to help integrate wind energy into the grid to achieve
with 23-MW capability have already been commercially avail-
a more cost-effective and reliable renewable wind energy.
able and a 5-MW wind turbine also will be available in a few
In this paper, the effectiveness of a STATCOM in facilitat-
years. Moreover, the cost of wind energy has been reduced to
ing the integration of a large WF into a weak power system
4.5 cents/kWh and is very competitive against conventional fu-
is presented. Firstly, an actual weak power system with two
els, and will be further reduced to 3 cents/kWh for utility-scale
nearby large WFs is introduced. Based on the field supervisory
wind energy onshore and 5 cents/kWh offshore by 2012 [1], [2].
control and data acquisition (SCADA) data analysis, the issues
Additionally, public policy is fostering further integration of
are highlighted, and steady state and dynamic voltage controls
wind energy into the power system.
are needed to solve these issues. A STATCOM is proposed for
dynamic voltage control, particularly to suppress the short-term
Manuscript received July 12, 2006; revised June 30, 2006. This work was (seconds to minutes) voltage fluctuations. Secondly, a model of
supported in part by the U.S. Electric Power Research Institute, in part by the
Tennessee Valley Authority, in part by the U.S. Department of Energy, and in the system, WF and STATCOM for steady state and dynamic
part by the Bonneville Power Administration. Paper no. TEC-00241-2006. impact study is developed in the PSCAD/EMTDC simulation
C. Han, A. Q. Huang, M. Baran, and S. Bhattacharya are with the Semi- environment. The developed model is validated by using the
conductor Power Electronics Center (SPEC), North Carolina State University,
Raleigh, NC 27695 USA (e-mail: chhan@ieee.org). field data. Moreover, based on the real powervoltage (PV) and
W. Litzenberger, L. Anderson, and A. Johnson are with Bonneville Power voltagereactive power (VQ) curves obtained from the simula-
Administration (BPA), Portland, OR 97208-3621 USA. tion, the system voltage control and stability issues are analyzed,
A.-A. Edris is with the Electric Power Research Institute (EPRI), Palo Alto,
CA 94304 USA. and the size and location of STATCOM are assessed. Finally, a
Digital Object Identifier 10.1109/TEC.2006.888031 STATCOM control strategy for voltage fluctuation suppression

0885-8969/$25.00 2008 IEEE


HAN et al.: STATCOM IMPACT STUDY ON THE INTEGRATION OF A LARGE WIND FARM 227

is presented, and the dynamic simulations are used to verify the cables connecting individual wind turbines to the common bus
performance of the proposed STATCOM and its control strategy. 6. Fig. 2(c) indicates that the voltage fluctuation at bus 5 is about
1.4% during this period. The year-round monitored data indi-
cates that this is the case most of the time, although 5% voltage
II. SYSTEM DESCRIPTION fluctuation sporadically happens from time to time. There is also
Fig. 1 shows the diagram of the system investigated in this voltage fluctuation even without any WF1 generation, which
paper. The two WFs, WF1 and WF2, are connected to the ex- means that the voltage fluctuations of local system are not only
isting 69-kV loop system at bus 3 and 5. The system is supplied caused by generated power fluctuation of WF1, but they are
by the two main substations, which are represented by three also contributed by WF2 and voltage fluctuations at the remote
remote boundary equivalent sources at bus 1, 2, and 12. Among boundary buses. Therefore, a single STATCOM using emitter
them, bus 1 is a strong bus with a short-circuit capacity of about turn-off (ETO) thyristor [10] and cascaded-multilevel converter
4000 MVA. The WF2 at bus 3 is a large WF with a total rating (CMC) [11] is proposed to suppress the voltage fluctuations of
of 100 MVA. It is a type C WF [2] with variable-speed double the weak loop system.
fed induction generators (DFIGs) and partial back-to-back con-
verters. The WF1 at bus 5 is located at the middle of the weak
III. MODELING AND CONTROL
69-kV subtransmission system, and the short-circuit capacity at
the bus 5 is about 152 MVA. The WF1, with a total rating of 50 In this section, the modeling, PSCAD implementation and
MVA, is a type A WF [2] using fix-speed squirrel-cage induction validation of the studied 12-bus power system, WF, and STAT-
generators (SCIGs). The six loads tapped on the 69-kV weak COM are presented.
loop system are mostly rural radial loads. The loop network is
normally kept closed to improve the reliability of power supply.
A. Twelve-Bus System Model
The integration of WF2 into the grid is facilitated by the
power-converter-based interface as it provides VAR compen- The system shown in Fig. 1 is modeled using PSCAD/
sation capability and, hence, voltage control capability. On the EMTDC. Since only balanced operation is considered for this
other hand, the WF1 poses a challenge, as the SCIGs sink more study, the positive-sequence dynamic model is developed. Some
VARs when they generate more real power, the generated wind of the details include the following.
power is rapidly fluctuating with uncontrollable wind speed r Boundary equivalent source is modeled as ideal voltage
and large surge current during frequent startups of wind tur- sources with series equivalent impedances.
bines. Thus, when WF1 is located at the weakest part of the r Transmission lines are represented by their equivalent
loop system, these characteristics of WF1 not only increases the model.
transmission and distribution losses, reduces the system voltage r Transformer is implemented using the PSCAD classical
stability margin, and limits power generation, but also causes transformer modeling approach and including the leakage
severe voltage fluctuations and irritates the customers in the sys- inductance and resistive loss.
tem, particularly in the weak 69-kV loop, where a significant r Loads are considered as constant power. Only one load
portion of the loads are induction motors, which is sensitive to profile is considered. Data for the monitored loads are ob-
voltage fluctuations. tained from the SCADA, and for the nonmonitored loads,
To reduce the voltage fluctuations and improve power factor, they are assumed to be 30% of their supply transformer
small size MSCs (hundreds kilovar) are installed at each individ- rating.
ual SCIG terminal and large size MSCs (12 Mvar) are installed
at bus 6, the 35-kV secondary side of the WF1 main transformer
B. WF Model
T3. Moreover, to provide voltage support, all the main trans-
formers T1T4 and many customer transformers have several Since the focus in this paper is on the system impact study
taps, and two additional MSCs (2.75 Mvar each) are installed at of electrical power flow and voltage, the implemented model of
bus 8. However, because of slow response time, these devices the WFs does not include mechanic dynamics and the detailed
do not satisfactorily address the dynamic issues of WF1, and electrical model of induction machine [6], [12], and it is an ideal
even exacerbate them. voltage source with equivalent series and shunt impedance. For
Fig. 2 shows the selected power injection and voltage profile such a WF model, the following assumptions have to be made.
data at WF1, monitored during a typical three-day operation. r All wind turbines are identical.
The sampling rate of the data is 5 min. In Fig. 2(a), this profile r Wind speed is uniform, so that all wind turbines share the
covers a WF1s whole operating process, from idle (no wind same power generation.
generation) to full-rated power output of 50 MW and back to r Each turbine runs at the same operating modes at all times,
idle. As Fig. 2(b) indicates, the power factor of WF1 is usually and the voltages, current, and power factor of each turbine
very high, about 0.99 lagging, which is fulfilled by controlling are the same.
the MSCs at individual SCIGs and bus 6, as long as the gen- r The series equivalent impedances of underground cables
erated wind power is larger than about 1 MW. The figure also that connect the SCIGs to the common bus 6 are negligible.
shows that, when the system is idle, WF1 produces 12 Mvar r All transformers connecting individual SCIGs are
(capacitive) because of the shunt capacitance of the underground identical.
228 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 23, NO. 1, MARCH 2008

Fig. 1. One-line diagram of the studied system.

Fig. 3. Comparison of simulation results and field data at an operating point.

C. Model Validation
First, a specific operating point in 6-h period is selected.
By tuning the boundary sources, WFs and the nonmonitored
loads, this operating point is simulated on PSCAD/EMTDC.
Fig. 2. Field SCADA data of WF typical operation. The results, given in Fig. 3, match the field data quite well.
Therefore, the 12-bus system model with WFs at the specific
With these assumptions, both WF1 and WF2 are modeled as a operating point is validated.
quasi-dynamic model so that all the real power, reactive power, To simulate the operation of the system during 6-h period, the
and voltage of WFs are dynamically controlled to recur the model is closed-loop controlled by proportionalintegral (PI)
system operation from the field SCADA data for an operating controllers in order to match with the monitored data. Therefore,
point for steady-state study and a continuous period for dynamic a whole continuous period operation of the studied system can
study, where the real power of WF is controlled by the source be fully recurred in the off-line PSCAD simulation.
phase angle, the reactive power of WF is controlled by a shunt The time-domain simulation results for this 6-h period are
cap bank at 35 kV bus of WFs, and the bus voltage of WF is given in Fig. 4 together with the actual data, where the units of
controlled by the source voltage. real power, reactive power, and voltage are, respectively, MW,
From the three-day data in Fig. 2, a 6-h period data of the Mvar, and p.u., which is the same for the units in the later system
WF1 typical low power generation, which represents smaller simulation results. In general, compared to the field data, the
amount of turbine online and the weakest grid connection of simulated real power, reactive power, and voltage follow almost
WF1, is selected for study. This case corresponds to operation the same fluctuation trend and magnitude, and also have good
of eight turbines out of total 83 turbines in WF1. To account for match in terms of the steady-state values. Therefore, the system
the VAR contribution of the underground cables, a 2.06-Mvar models in a continuous operation period are validated and can be
shunt capacitor is added at the 34-kV interface bus 6. used for dynamic STATCOM impact study in the next section.
HAN et al.: STATCOM IMPACT STUDY ON THE INTEGRATION OF A LARGE WIND FARM 229

Fig. 5. Proposed STATCOM and its controller. (a) Generalized CMC-based


Y-connected STATCOM schematic. (b) Internal control strategy of CMC-based
STATCOM.

Moreover, some insights can also be pointed out from Fig. 4


as follows.
r The mismatch at the beginning of each waveform is be-
cause of the simulation initialization transient, which is the
same for the later time domain simulation results and will
not be mentioned again.
r For the real power in Fig. 4(a) and (c), there is some slightly
increasing mismatch between the simulation results and
field data, which is because this period is close to midnight
and the actual loads gradually decrease, while the simulated
loads are all modeled as fixed loads.
r For the voltages in Fig. 4(b) and (c), there is a small steady-
state offset between the simulation results and field data,
though the simulation results follow almost the same fluc-
tuation trend and magnitude while compared to the data.
This could be because the TC settings of some transformers
are unknown and not included into the model.
r In Fig. 4(d), because of the T3s reactance, there is a con-
stant offset between reactive power at 35-kV bus 5 and
69-kV bus 6, and a slightly higher voltage profile at bus 5
than bus 6.

D. STATCOM Model and Control


Fig. 4. Comparison of simulation results and data for a 6-h operation. (a) Bus The proposed STATCOM uses a CMC-based topology, as
2 voltage and power flow from bus 2 to 3. (b) Bus 3 voltage and power flow
from WF2. (c) Bus 4 voltage and power flow from bus 4 to 5. (d) Bus 5 and 6 shown in Fig. 5(a). For this study, a harmonics-free dynamic
voltage and WF1 power output at bus 5 and 6. model of the CMC-based STATCOM with its internal control,
230 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 23, NO. 1, MARCH 2008

Fig. 6. Simulation results of the CMC-based STATCOM model.

as shown in Fig. 5(b), is implemented on PSCAD/EMTDC [9],


[11], [13].
The simulated results, as shown in Fig. 6, illustrate how the
Fig. 7. Steady-state simulation results. (a) PV curve. (b) VQ curve.
STATCOM shown in Fig. 5(a) responds to step change com-
mands for increasing and decreasing its reactive power output,
where the units of dc voltage, reactive current, ac voltage, ac voltage-fluctuation issue rather than to regulate the steady-state
output current, and reactive power output are kV, kA, p.u., p.u., voltage profile.
and Mvar, respectively. As the figure illustrates, the reactive Actually, from technology point of view, the most effective
current step change response has a bandwidth as fast as a quar- location to install STATCOM to suppress the voltage fluctuation
ter cycle, and 10 Mvar is generated by the STATCOM, and related to WF1 is just directly at the WF1s point of common
the average dc capacitor voltage of about 1.5 kV is dynami- point (PCC), which is at 69-kV bus 5. In Fig. 7(b), VQ curve
cally controlled and does not change due to the VAR command obtained by injecting VAR at bus 5, evaluates the size of STAT-
change. Therefore, the STATCOM model is validated. COM. This curve indicates that there is no voltage stability
problem at the operating point again, but the sensitivity of the
bus voltage to VAR injection is quite high; 10-Mvar injec-
IV. SIMULATION AND ANALYSIS
tions can cause about 5% voltage change at the bus. From
With the validated system model at the specific operating the year-round data, the most severe voltage fluctuation, which
point, the PV and VQ curve [14][16] of WF1 at bus 5 is ob- happens rarely, is about 5%, and most voltage fluctuation is
tained through the steady-state simulations, as shown in Fig. 7. less than 1.5%. STATCOM voltage control capability should
First, the PV curve at bus 5, where WF1 is connected to cover not only typical 1.5% cases, but also the most severe
the system, is obtained by regulating the WF1 source angle 5% case. Therefore, a 10-MVA STATCOM is a reasonable
to increase the real-power injection at this bus while keeping size to suppress voltage fluctuations at bus 5 covering the most
the rest of the system constant. Fig. 7(a) shows the PV curve severe 5% case, and a STATCOM with the size of 5 MVA is
obtained with the nose point of the PV curve located around enough to suppress voltage fluctuation for typical 1.5% cases.
(32 MW, 0.88 p.u.). It means that, provided that the WF1 injects Although bus 5 seems an effective location for STATCOM,
unity power-factor power at the operating conditions simulated, if STATCOM can be installed inside the substation at bus 6, as
there is about 30 MW real power injection margin at this bus for shown in Fig. 1, from the practical cost-effectiveness point of
voltage stability, which is already far beyond the total rating of view, the additional space for STATCOM need not be planned
eight online turbines, 4.8 MW, at the specific operating point. and the civil works can be significantly reduced so that the
Moreover, MSCs at WF1 work as power-factor compensator cost can be significantly lowered. To compare the STATCOM
and can further improve the PV curve and extend the WF1 voltage control capability at different locations, the simulation
power-injection margin from voltage stability point of view [7]. results with STATCOM, respectively, installed at bus 5 and bus
Therefore, the voltage stability is not a serious issue for the 6 are shown in Fig. 8, where the solid line is with STATCOM
studied loop system, and STATCOM, utilizing its fast response at 69-kV bus 5, and the dotted line is with STATCOM at 35-kV
for a cost-effective application, can focus on solving the dynamic bus 6. As seen from the waveforms, whatever be the capacitive
HAN et al.: STATCOM IMPACT STUDY ON THE INTEGRATION OF A LARGE WIND FARM 231

Fig. 8. STATCOM voltage control capability versus location. (a) Capacitive


VAR versus bus 5 voltage. (b) Inductive VAR versus bus 5 voltage.

Fig. 9. STATCOM external controller for voltage fluctuation suppresion.

VAR to improve voltage or inductive VAR to depress voltage,


STATCOM at 35-kV bus 6 has almost the same voltage con-
trol capability as STATCOM at 69-kV bus 5, and the voltage
difference between the two locations increases with increas-
ing |Q |. This voltage difference is just 0.005 p.u., even at Fig. 10. Comparison of voltage fluctuations with or without STATCOM.
(a) Bus 2 voltage. (b) Bus 3 voltage. (c) Bus 4 voltage. (d) Bus 5 and 6 voltage.
maximum/minimum STATCOM output 10 Mvar. Therefore, (e) Bus 8 voltage. (f) Bus 11 voltage.
a 10-MVA STATCOM installed at 35-kV bus 6 is still able to
suppress voltage fluctuations at bus 5 covering most severe 5%
case, and a STATCOM with the size of 5 MVA is still enough to An additional benefit of this external scheme is, with well-
suppress voltage fluctuation for typical 1.5% case. Therefore, designed fast voltage bandwidth utilizing the fast switching ca-
considering cost-effectiveness, bus 6 can also be the choice for pability of ETO switches and the synthesization characteristics
STATCOM location. of CMC topology, even the relatively faster voltage fluctuations
Another simulation has been performed to make a preliminary and flicker [13], [17], [18], due to the switchings of MSCs, blade
assessment of the impact of the STATCOM on the system. This passing tower [5], SCIG startup and so on, could be suppressed
simulation involved dynamic operation of the STATCOM at bus automatically together with the short-term (seconds to minutes)
6 during the 6-h monitoring period. The proposed STATCOM voltage fluctuations.
external control for voltage fluctuation suppression is shown Fig. 10 gives the simulation results using STATCOM with its
in Fig. 9. The dc value of bus rms voltage is substracted from control strategy for voltage fluctuation suppression, where the
measured rms voltage, equivalent to feed through a washout solid line is without STATCOM and the dotted line is with STAT-
filter, so that only the voltage fluctuation part is used as the in- COM. The STATCOM is located at 35-kV bus 6. As clearly seen
put to voltage loop controller. Therefore, STATCOM can adap- from Fig. 10(a) and (b), bus 2 and 3 is almost unchanged even
tively deal with voltage fluctuation, independent from system with STATCOM, which is obvious because they are closely
steady-state voltage regulation by operations of MSCs and TCs. connected to a very strong bus 1 with the low impedance of T1
232 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 23, NO. 1, MARCH 2008

and the short 115 kV-transmission line. In the Fig. 10(d), bus REFERENCES
5 voltage fluctuation is almost fully solved, so is bus 6. The
[1] Wind Power Today and Tomorrow: An Overview of the Wind and Hy-
reason why voltage fluctuations at bus 6 are a slightly larger dropower Technologies Program, (2004), U.S. DOE and NREL [Online].
than bus 5 in the case with STATCOM is that the STATCOM Available: http://www.nrel.gov/wind/
control reference is not bus 6 voltage but bus 5 voltage, though [2] T. Ackermann, Wind Power in Power Systems. New York: Wiley, 2005.
[3] J. W. Smith and D. L. Brooks, Voltage impacts of distributed wind gener-
STATCOM is installed not on bus 5 but on bus 5. As shown in ation on rural distribution feeders, in Proc. IEEE PES Transmiss. Distrib.
the Fig. 10(c), (e), and (f), the voltage fluctuation at other 69-kV Conf. Exhib., Oct. 28Nov. 2, 2001, vol. 1, pp. 492497.
[4] A. Kehrli and M. Ross, Understanding grid integration issues at wind
buses are all suppressed considerably as well, and the extents of farms and solutions using voltage source converter FACTS technology,
suppression are dependent on how these buses are close to bus in Proc. IEEE PES Gen. Meeting, Jul. 1317, 2003, vol. 3, pp. 18221827.
5, as the suppression is more at the close bus 4 and 8, and less at [5] Z. Saad-Saoud, M. L. Lisboa, J. B. Ekanayake, N. Jenkins, and G. Strbac,
Application of STATCOMs to wind farms, Inst. Elect. Eng. Proc. Gener.
the far bus 11. Therefore, these dynamic simulation results ver- Transmiss. Distrib., vol. 145, no. 5, pp. 511516, Sep. 1998.
ify the previous analysis and assessment based on steady-state [6] F. Zhou, G. Joos, and C. Abbey, Voltage stability in weak connection
PV and VQ curves, and the effectiveness of STATCOM and its wind farms, in Proc. IEEE PES Gen. Meeting, Jun. 1216, 2005, vol. 2,
pp. 14831488.
control strategy for voltage fluctuation suppression. [7] L. T. Ha and T. K. Saha, Investigation of power loss and voltage stability
In addition, since the STATCOM suppresses the voltage fluc- limits for large wind farm connections to a subtransmission network, in
tuation, it is apparent that, compared to the case without STAT- Proc. IEEE PES Gen. Meeting, Jun. 610, 2004, vol. 2, pp. 22512256.
[8] N. G. Hingorani and L. Gyugyi, Understanding FACTS: Concepts and
COM, the switching times of MSCs and TCs of both main trans- Technology of Flexible AC Transmission Systems. Piscataway, NJ: IEEE
formers and load transformers to address the voltage fluctuation Press, 2000.
issue in the system shall be significantly reduced. Therefore, [9] C. Han, Z. Yang, B. Chen, W. Song, A. Q. Huang, A. Edris, M. Ingram, and
S. Atcitty, System integration and demonstration of a 4.5 MVA STAT-
the maintenance and replacement cost of MSC, TC, and wind COM based on emitter turn-off (ETO) thyristor and cascade multilevel
turbines can be lowered, and the power quality issues related to converter, in Proc. IEEE IECON, Nov. 610, 2005, pp. 13291334.
the switching of MSCs and TCs can also be lessened. [10] B. Chen, A. Q. Huang, S. Atcitty, A. A. Edris, and M. Ingram, Emitter
turn-off (ETO) thyristor: An emerging, lower cost power semiconduc-
tor switch with improved performance for converter-based transmission
controllers, in Proc. IEEE IECON, Nov. 610, 2005, pp. 662667.
V. CONCLUSION [11] S. Sirisukprasert, A. Q. Huang, and J. S. Lai, Modeling, analysis and con-
This paper describes the methodology to conduct an impact trol of cascaded-multilevel converter-based STATCOM, in Proc. IEEE
PES Gen. Meeting, Jul. 1317, 2003, vol. 4, pp. 25612568.
study of a STATCOM on the integration of a large WF into a [12] E. Muljadi, Y. Wan, C. P. Butterfield, and B. Parsons. (2002). A study
weak loop power system. The specific issues and solutions of of a wind farm power system. Preprints, p. 14. NICH Report No.
the studied WF system are illustrated. For the system study, the CP-500-30814. [Online]. Available: http://www.nrel.gov/docs/fy02osti/
30814.pdf
models for the system, WF and STATCOM are developed, and [13] C. Han, Z. Yang, A. Q. Huang, and M. Ingram, Modelling and control of
the system model has also been validated with field data. a cascade-multilevel converter-Based STATCOM for electric arc furnace
From obtained PV and VQ curves from the simulation, the flicker mitigation, in Proc. IEEE IECON, Nov. 610, 2005, pp. 883888.
[14] C. W. Taylor, Power System Voltage Stability. New York: McGraw-Hill,
size and location of STATCOM and the system stability are 1994.
assessed. It indicates that while low-cost MSCs and TCs boost [15] P. Kundur, Power Stability and Control. New York: McGraw-Hill,
the steady-state voltage locally but are ineffective to suppress ch. 14, 1994.
[16] T. V. Cutsem and C. Vournas, Voltage Stability of Electric Power Systems.
the voltage fluctuations (seconds to minutes) due to their nature Norwell, MA: Kluwer, 1998.
of slow dynamic response, a 10-Mvar STATCOM, which is a [17] A. Larsson, Flicker emission of wind turbines during continuous oper-
small percentage of WF rating, can not only effectively suppress ation, IEEE Trans. Energy Convers., vol. 17, no. 1, pp. 114118, Mar.
2002.
the voltage fluctuations of the WF and the whole 69-kV loop [18] A. Larsson, Flicker emission of wind turbines caused by switching oper-
system, but also inherently reduce the operation times of MSCs ations, IEEE Trans. Energy Convers., vol. 17, no. 1, pp. 119123, Mar.
and TCs in the system so that the maintenance and replacement 2002.
cost of MSCs, TCs, and wind turbines can be reduced, and
the power quality issues related to the switching of MSCs and
TCs can also be lessened. The results also show the location of Chong Han (M07) received the B.S.E.E. (Hons.)
STATCOM selected at 35-kV bus 5 can be a good tradeoff from degree from Huazhong University of Science and
cost-effectiveness point of view. Technology (HUST), Wuhan, China, and the M.S.
degree from Virginia Polytechnic Institute and State
For this specific application of suppressing the voltage fluctu- University, Blacksburg, VA. He is currently work-
ations, the dynamic simulation results for a continuous operation ing toward the Ph.D. degree at North Carolina State
period also verify the effectiveness of the proposed STATCOM University (NCSU), Raleigh, NC, all in electrical
engineering.
and its control strategy, which can adaptively deal with voltage From 1999 to 2001, he was with the National
fluctuation, independent from system steady-state voltage reg- Transient Network Analyzer (TNA) Laboratory and
ulation by operations of MSCs and TCs, and even mitigate the Superconductivity Power R&D Center, HUST, where
his research focused on FACTS controller, energy storage system, and power
faster voltage fluctuations and flicker emission, possibly from system automation. From 2001 to 2004, he was a Research Assistant at the Cen-
WFs with well-designed fast control bandwidth. Therefore, it is ter for Power Electronics Systems (CPES), Virginia Tech. From 2004 to 2006,
concluded that the installation of a 10-Mvar STATCOM system he was with the Semiconductor Power Electronics Center (SPEC), NCSU. Cur-
rently, he is with ABB Inc., Raleigh, NC, as a Grid System Consultant. His
is effective for integrating the specific WF into the weak loop current research interests include control of power electronics and power sys-
power system. tem, real-time simulator, energy storage system, and renewable energy.
HAN et al.: STATCOM IMPACT STUDY ON THE INTEGRATION OF A LARGE WIND FARM 233

Alex Q. Huang (S91M94SM96F05) was born Wayne Litzenberger (M73SM00) received the
in Zunyi, Guizhou, China. He received the B.Sc. de- B.S.E.E. and M.S.E.E. degrees from the University
gree from Zhejiang University, Hangzhou, China, in of Washington, Seattle, in 1963 and 1969, respec-
1983 and the M.Sc. degree from the Chengdu Insti- tively.
tute of Radio Engineering, Sichuan, China, in 1986, He was briefly with the Boeing Company in Seat-
in electrical engineering, and the Ph.D. degree from tle. Since 1989, he has been with Bonneville Power
Cambridge University, Cambridge, U.K., in 1992. Administration (BPA), Portland, OR and Vancouver,
Since 1983, he has been involved in the devel- WA, where most of his assignments were related to
opment of modern power semiconductor devices and HVDC and FACTS projects.
power integrated circuits. He fabricated the first IGBT Mr. Litzenberger has been active in the Power En-
power device in China in 1985. He is the inventor and gineering Society, holding a number of offices in the
key developer of the emitter turn-off thyristor technology. From 1992 to 1994, T&D and Substations Committees. He was the U.S. Representative to Cigre
he was a Research Fellow at Magdalene College, Cambridge. From 1994 to Study Committee B4 from 2002 to 2004.
2004, he was a Professor at the Bradley Department of Electrical and Computer
Engineering, Virginia Polytechnic Institute and State University, Blacksburg,
VR. Since 2004, he has been the Alcoa Professor of Electrical Engineering at
North Carolina State University, Raleigh. His current research interests include
utility power electronics, power management microsystems, and power semi-
conductor devices. He is the author or coauthor of more than 100 published
Loren Anderson received the B.S. degree from Oregon State University,
papers in international conferences and journals, and also a holder of 14 U.S.
Corvallis, in 1980.
patents.
Currently, he is the Principal HVDC and FACTS Engineer at the Bonneville
Dr. Huang is the recipient of the NSF CAREER Award and the prestigious Power Administration (BPA), Vancouver, WA. He has vast experience working
R&D 100 Award.
on HVDC systems. His research interests include HVDC control design, equip-
ment maintenance, and failure analysis.

Mesut E. Baran (S87M88) received the Ph.D. de-


gree from the University of California, Berkeley, in
1988.
He is currently an Associate Professor with North
Carolina State University, Raleigh. His research in-
Anders L. Johnson (M02) received the B.S.E.E.
terests include distribution and transmission system and M.S.E.E. degrees from the University of Wash-
analysis and control.
ington, Seattle, in 2002 and 2003, respectively. He
was also a Grainger Graduate Fellow.
Since 2002, he has been an Electrical Engineer at
the Bonneville Power Administration, Portland, OR.
His research interests include electromagnetic tran-
sients simulation, protective relaying, high-voltage
equipment, and power electronics applications to the
Subhashish Bhattacharya (M85) received the B.E. transmission grid.
(Hons.), M.E., and Ph.D. degrees in electrical en-
gineering from the University of Roorkee (IIT-
Roorkee), India, in 1986, Indian Institute of Science
(IISc), Bangalore, India, in 1988, and the University
of Wisconsin, Madison, in 2003, respectively.
From 1994 to 1996, he was with York International
Corporation for commercialization of his active fil- Abdel-Aty (Aty) Edris (SM88) was born in Cairo,
ter Ph.D. research work for air-conditioner chiller Egypt. He received the B.S. (Hons.) degree from
application. From 1996 to 1998, he was a Consul- Cairo University, Cairo, Egypt, the M.S. degree from
tant to Soft Switching Technologies (SST), where he Ain-Shams University, Cairo, and the Ph.D. degree
worked on active filters and resonant link converters. From 1998 to 2005, he from Chalmers University of Technology, Goteborg,
was in the FACTS and Power Quality Division of Siemens Power Transmission Sweden.
and Distribution. Since August 2005, he has been an Assistant Professor in the He was with the ABB Company in Sweden and
Department of Electrical and Computer Engineering at North Carolina State USA for 12 years, where he was involved in the de-
University, Raleigh, where he is also a Faculty Member of the Semiconductor velopment and application of reactive power com-
Power Electronics Center (SPEC). His research interests include FACTS, util- pensators and high-voltage dc transmission systems.
ity applications of power electronics such as custom power and power quality Since 1992, he has been with Electric Power Research
issues, active filters, high-power converters, and converter control techniques. Institute (EPRI), Palo Alto, CA, as a Manager of Flexible ac Transmission Sys-
Dr. Bhattacharya has been involved in several FACTS projects, including the tem (FACTS) technology, where he is currently the Technology Manager of
New York Power Authority (NYPA) 200 MVA Convertible Static Compensator EPRI Power Delivery and Markets.
(CSC), the KEPCO-Korea 40 MVA UPFC, and the American Electric Power Dr. Edris is a member of several IEEE and CIGRE Working Groups and the
(AEP) 150 MVA STATCOM projects. recipient of the 2006 IEEE FACTS Award.

Das könnte Ihnen auch gefallen