Sie sind auf Seite 1von 13

ELECTRO THERMAL TESTING OF HIGH VOLTAGE HIGH FREQUENCY

ESP POWER AR70/1000

Slobodan N. Vukosavi*, eljko V. Despotovi**, Nikola Popov*, Nikola Lepojevi*

School of Electrical Engineering, University of Belgrade*, boban@etf.rs

Institute Mihajlo Pupin, University of Belgrade**, zeljko.despotovic@pupin.rs

Abstract: The modern power supplies of electrostatic precipitators (ESP) are based on high voltage
high frequency (HVHF) power converters. Developed HVFF ESP power, under commercial name
AR70 / 1000, is based on a distributed multi-resonant topology. This power it had to be subjected to
a series of pure electrical tests (short circuit test, open circuit test, full load test), but also of thermal
characterization and electro thermal testing, before delivery and exploitation in real conditions on
the thermal power plant blocks. This paper describes a methodology of electrical thermal testing of
the proposed ESP power, as well as experimental results obtained during tests and thermal heating
in laboratory conditions at nominal output voltage 70kVdc and the nominal output power of 70kW.
The performed experimental results and procedure showed acceptable values and limitations, which
was carried out the verification a given ESP power prior to delivery and installation of the ESP
units on the real conditions on thermal power plants blocks.

Key words: Power converters, ESP power, thermal characterization, thermal load, ESP testing

1. INTRODUCTION

The conventional 50 Hz SCR design had been predominant solution for controlling the particulate
emission from large electrostatic precipitators (ESPs). Although capable to reach removal
efficiencies up to 99, 8%, this design suffers a number of drawbacks, leading to poor energy
efficiency, very large size of electrode plates, and it cannot compete with the high frequency power
source.
High voltage high frequency (HVHF) ESPs power supply and corresponding control require
a lower size and weight of electrodes, offers significant energy savings, prevents back corona,
brings up a very fast reaction to flashover, results in a much higher power factor, and has a
transformer/rectifier set several times smaller and lighter compared to conventional 50Hz design
[1-8].
In many papers is presented a new HVHF distributed multi resonant topology (DMRT) for
ESPs power [9-12]. DMRT in the secondary circuit enables reducing of commutation losses and
the insulation stress, hence suppressing the catalytic effects of the electric field high speed changes
and preventing chemical reactions leading to accelerated dielectric aging [12-13]. DMRT power
converter enables ZCS commutation of IGBT power switches, significantly lowering the overall
converter losses [14-15]. The basic electrical scheme of HVHF power with incorporated of DMT is
shown in Fig.1. The functional blocks are arranged in accordance to disposition on the realized ESP
power, named under commercial trade mark AR70/1000, i.e. output DC voltage 70kV and output
DC of 1000mA. This ESP power was developed on the School of Electrical Engineering, University
of Belgrade (DDC Laboratory). Basic functionality and features of this ESP power are given in the
internet address http://www.esp.etf.rs/.
Fig.1. Basic electrical scheme HVHF distributed multi resonant topology AR70/1000 for ESP power

Since the focus of this paper thermal characterization of power AR70 / 1000, emphasis will be
given to the basic thermal units or subsystems, which are clearly shown in Fig.1. There are three
main thermal parts of ESP power AR 70/1000: cubicle of HF IGBT power converter, oil tank with
corresponding equipment and HV insulator in which is connect ESP load.
The main heat sources in a HF cubicle are: input three phase diode rectifier (with or without
three phase input reactor), capacitor in dc link circuit, IGBT H-bridge and bus bar system (U,V, +AT
and -AT). Much stronger heat sources located within the oil tank: dc reactor Ldc , ac reactor Lac in
primary circuit of HVHF transformer, HVHF transformer and HV rectifier (the chains of high-
voltage diode and associated RC voltage spike suppressors). These last two components largely
determine the thermal behaviour of ESP power AR 70/1000.
Thermal characterization and testing of AR70/1000 were performed in laboratory conditions as
on the part of many other tests (short-circuit, no-load, full load and overload). These tests should be
carried prior to final delivery and installation of HVHF units in real operating conditions of the ESP
installation on thermal power plants.

2. ELECTRO-THERMAL INSTALLATION FOR TESTING ESP POWER AR70/1000

In order to perform a correct thermal characterization and thermal power AR70-1000 tests it was
necessary to provide a high-voltage RC load (parallel connection of resistor R and capacitor C),
nominal voltage of 70kV, nominal current of 1000mA and accordingly nominal output power of
70kW. Like this established load approximately correspond to the real ESP load according Oglesby
as stated in [16]. Since this load is one of the key parts of electro-thermal installations that will be
described in detail.
The basic block diagram of the HV load, which actually emulates real ESP (emission and
collecting electrodes system) and the way of its connection with power AR70/1000, are shown in
Fig.2. The basic elements of this load are: oil tank with accessories, HV resistors, cooling system,
HV insulator and extern HV capacitor. In the oil tank are three high-voltage resistor 23k / 23kW
(connected in series) i.e. R L = 68k/70kW, one shunt resistor Rsh = 220 on which is measured
voltage drop i.e. load current and corresponding measuring equipment. In fact, is constantly a
measure and displays oil temperature in the tank through the thermal probe with indicator
(measuring range 0-100C), but it is in the tank installed thermo-switch that has a no-voltage contact
which gives the signal that the oil temperature reached above a maximum threshold of 70C. When
the oil temperature in tank exceeds this threshold, unconditionally during testing, come to turn-off of
power AR70/1000.
Fig.2. Block scheme test installation and RC load of ESP power AR70/1000; disposition of AR70/1000 is
given in two projections (top and side views)

The case of the oil tank has dimensions 600x600x1200mm, with a separately earthing
connection. On it, at the one lateral side are performed two holes for the inlet and outlet of the
circulating oil, while at the opposite side is carried out the one hatch in which is mounted HV
silicon insulator.
The inlet an outlet of oil tank had two manual valves with associated taps. The oil circulation
is provided by pump, whose motor is electrical supplying from the frequency converter (inverter).
This converter is powered from single-phase voltage 230V, 50Hz, and at its outputs gives the three-
phase voltage variable frequency. With this converter is adjusted the flow of circulating oil, which
provides cooling of resistive part of load. In heat exchanger oil-water is provided reliably
dissipate heat from load.
HV insulator is reliably mounted on the oil tank, very well done sealing and at its end was
attached to high voltage capacitor C L = 25nF/100kV. The parallel connection of resistor R L and
capacitor C L , approximately correspond to the real ESP load.
The measurement of the high voltage at the RC load is achieved from high voltage resistors
R1 and R2 (in series connection) and the micro-ammeter. Besides this, it provided an additional
measurement of high-voltage by electrostatic voltmeter (ESV) with bright spot at the linear division
scale 0-100% (i.e. 0-100kV). In this way, it is possible to remotely and visually monitoring the
value of high voltage at the RC load.
HV output of AR70/1000 is connected to insulator of load through HV cable 200kV/2.5mm.
It is important to note that it is extremely reliably derived connections all of earthing (PE
connections: the oil tank, HV capacitor, power AR70/1000 and high voltage measuring equipment).
As an additional measure of protection against direct touch with HV installation was provided
Faraday cage made of metal mesh grid, which was also grounded in more places and connected to
other terminals for earthing.
Fig.3 shows the detailed installation which was carried out by electro thermal testing of ESP
power AR70/1000. Fig.3 (a) shows the single-pole electric scheme of test installation and
topologies of key functional blocks of HF power converter (named DS200) and HV output parts
(HVHF transformer, HV rectifier, HV insulator,etc.) . Figure 3 (b) shows the three-dimensional
appearance of ESP power AR70/1000 with disposition of all the key components that largely affect
of the thermal characterization. The positions of the components 1-6 in the electrical scheme
correspond to the positions at the three-dimensional view of ESP power AR70/1000.

Fig.3. Electrical installation of ESP power AR70/1000; (a) Single pole electrical scheme of test installation,
(b) three-dimensional view of AR70/1000 power with the positions of associated equipments
In anticipated tests established three groups of electrical measurements: at the input terminal
of AR70/1000 (connection to power supply network), electrical measurement within HF cabinet
(cubicle) and measurements on HV side.
On the input terminal is provided three-phases measurements of input current I and voltage
U , also measurement of active and reactive power P and Q , respectively, as well as power factor
.
Inside of the HF cabinet are realized measurement of instantaneous values of current I dc and
voltage U dc in the DC link circuit of DS2000 converter, respectively, and is actual values of current
I ac and voltage U ac at the output terminals DS 2000 converter i.e. IGBT H-bridge (primary winding
of HVHF transformer). The third group of electrical measurement is performed on HV side. Thereby
were measured output high voltage (output voltage of HV rectifier) U DC and output current I DC of
AR70/1000 unit.
Based on the above-mentioned measured values of current and voltage are obtained power, and
based on them are obtained the values of dissipation losses in certain parts of interest (as shown in
Fig.4): dissipation losses at the input of three-phase rectifier P 1 , dissipation in DC link circuit
(capacitor Cdc and inductance Ldc ) P 2 , dissipation losses in IGBT H-bridge P 3 and finally
dissipation losses on the HVHF transformer and HV rectifier, a total of P 4 .

Fig.4. Distribution of power losses in ESP power AR70/1000

Each of these losses on their way affects on the thermal characterization and rising
temperatures in certain parts of the ESP power AR70/1000. The largest impact they have
losses P 4 , considering that their largest amount, however, should not ignore the impact of losses in
the dc inductance, or the impact of losses in the IGBT H-bridge, the fact that his heat sinks with its
back side mounted in oil tank (in which HVHF is located), such as showing in Figs.1,3.
Thermal characterization was achieved for the various operating modes of ESP power
AR70/100. Change the operating modes of AR70/1000 power are achieved through the two
reference values: switching frequency f [kHz] of IGBT H-bridge converter (in ZCS resonant mode)
and the pulse width of their output voltage i.e. duty-cycle [%] . In references [x-y] is explained in
detail how the two reference values affect on the operating modes of DMRT integrated in assembly
of IGBT H-bridge, HVHF transformer and HV rectifier.

3. THERMAL CHARACTERIZATION OF ESP POWER AR70/1000


In this section will be presented positions (i.e. measuring point) at which they are placed
temperature sensors in certain areas of interest within the ESP power AR70/1000. Fig.5 presents the
disposition of equipment within the considered power AR70/1000 as well as the exact arrangement
of measurement points
The temperature measurements were carried out in 14 measurement points (T1-T14) at the
transformer oil tank and within cubicle of HF power. Also certain group of measurements is made
on the HF device DS2000 and at the HVHF transformer. Measurements at all points are achieved
Pt1000 sensors (except for measurement points T3-T8 and T9, T10) and suitable measuring
transmitters. The obtained measuring signals are introduced in the simple data acquisition system
and after that was performed computer processing of the results.
Detailed specifications of all measurement points, according to the dispatch planning drawing
in Fig.5, is given in Table I. This table shows the three groups of temperature measurements that
fully correspond to the thermal characterization:

(i)-measuring points in HVHF transformer oil tank


(ii)-measuring points at HVHF transformer (windings, magnetic circuit and oil temperature)
(iii)-measuring points in HF converter DS2000 (H-bridge, input 3ph- rectifier, DSP
controller)

Fig.5. Disposition of measuring points of characteristic temperatures in ESP power AR70/1000, (a) view on
the right lateral side, (b) view on the top side, (c) view on the front side

Based on this above setting measurement points was carried out a series of experiments and
thermal tests , after which the unit AR70/1000 was ready for delivery to ESP station on thermal
power plant.
(i) MEASURNIG POINT IN OIL TANK (ii) TEMPERATURE IN HVHF
(T1.T14) TRANSFORMER ( end measured values)
T1 Heat sink DS2000 Cu1 Primary side winding (Cu1)
T2 Oil temperature in tank Cu2 Secondary side winding (Cu2)
T3-T8 Heat sink ribs (lateral side Fe Magnetic circuit (ferrite-Fe)
0%-20%-40%-60%-80%-100%)
T9 Air temperature (fans of DS2000) transf.oil Temperature of transformer oil
T10 Top side of oil tank (iii) MEASURED TEMPERATURE IN DS2000
(end measured values)
T11 Indoor of cubicle-position 1 12 V-bus bar (AT+) *see Fig.1
T12 Indoor of cubicle-position 2 45 Block capacitor in DS2000, 0.47uF/850V,
MKP-CS13 ( <70C)
T13 Temperature of electrolytic capacitors 78 Hexagonal pad bollard , U bus bar
in DC link circuit (AT+)
T14 Ambient temperature 10-11 Temperature of electrolytic capacitor
in DC link circuit
Table I- Characteristic measuring points in the thermal characterization of ESP power AR70/1000

4. EXPERIMENTAL RESULTS
This section presents the experimental results obtained in the framework of the thermal
characterization of ESP power AR70/1000. A series of thermal tests is achieved a view to finding
the most acceptable solutions of the cooling system of proposed ESP power at different operating
regimes (at different operating frequency and output power). The aim of the tests was to achieve
maximum output power of 70kW (70kV/1A), and in order not to overheat the power unit
AR70/1000.

Fig.6. Test No1: Thermal characterization of ESP power AR70/1000 at switching frequency f=6.9 kHz, and
output power 61.35kW; power losses P 4 =4kW
Fig.6 shows the experimental results for Test No1. In this case, is adjusted operating
frequency resonant inverter (IGBT H-bridge in ZCS regime) at 6.9 kHz. Output current AR70 it
amounted 207V / 220 = 0.94A, the output voltage of 65kV or output power of 61.35kW. Power
losses (in most are localized in oil tank of AR70) in these conditions amounted to 4kW. The
temperature in the oil tank of load it amounted in a steady state 48 C, variable frequency drive of
circulating pump was set to 30Hz, and the flow of circulation oil in tank of load was about 2.1 l/s.
The ambient temperature (average daily) was about 12.5C (min 10C, max 15C). Time duration
of test is amounted about 13h.
Under these conditions, the highest increase in temperature had measuring points T1, T2, T8
and T13. In these most critical points T1 (i.e. heat sink of DS2000) and T13 (electrolytic capacitor
in DC link circuit) temperatures are amounted about 69C and 71C, or temperature increases of
54C and 56C, respectively. The other temperature increases are not critical.

Fig.7. Test No2: Thermal characterization of ESP power AR70/1000 at switching frequency f=6.4kHz, and
output power 57.25kW; power losses P 4 =3kW

Reducing the operating frequency at 6.4kHz and output power at 57.25kW (and thus power
loss at 3kW) there was a reduction in the temperature increase (<50C) of the above mentioned
temperatures (T1- heat sink of DS2000 and T13-electrolytic capacitor in DC link circuit) as shown
in the diagrams of Test No2, in Fig.7. However, the output power is significantly reduced, which
was not the final and desired goal.
In Test No. 3, our goal was to raise the operating frequency to 7.4 kHz and output power to
67.5kW (69kV/0.98A), in the other almost the same conditions that applied to a Test No1 and Test
No2. In this case, there are a certain difficulties and problems. After six hours of operation, there
was a overheating of the DC electrolyte and the excessive temperature rise in the heat-sink of
DS2000, as shown in Fig.8. The result is a AR70/1000 power failure since there has been a
response to the thermal protection device DS2000 ("FAULT 128 -HEAT SINK"). After an hour of
pause, the unit AR70/1000 is turned on again, and after operation for about two hours there was a
power failure again. Temperature of the DC electrolytes and heat-sink of DS2000 have reached
critical temperature thresholds of 75C and 80C, respectively. This test showed that under these
conditions the ESP power cannot give the full value of the output power, i.e.70kW.
Fig.8. Test No3: Thermal characterization of ESP power AR70/1000 at switching frequency f=7.4 kHz, and
output power 67.45kW; power losses P 4 =3.65kW

Fig.9. Test No4: Thermal characterization of ESP power AR70/1000 at switching frequency f=7.4 kHz, and
output power 65.6kW; power losses P 4 =3.67kW
In Fig.9 shows the temperature responses obtained in the Test No4, for the case when the
ambient temperature was below 5C, compared to the previous Test No3. This resulted in a slightly
lower temperature increase (T1- heat sink of DS2000 and T13-electrolytic capacitor in DC link
circuit) than in the previous case, as can be seen in Fig.9.
But regardless of these results, it is generally a problem of critical temperature rise had solved
the forced cooling AR70/1000 unit. The following tests just give the results that they have achieved
a positive effect.

Fig.10. Test No5: Thermal characterization of ESP power AR70/1000 at switching frequency f=7.4 kHz, and
output power 68.08kW; power losses P 4 =3.8kW, air flow speed (side fans) 2.1 m/s

Fig.11. Test No6: Thermal characterization of ESP power AR70/1000 at switching frequency f=7.4 kHz, and
output power 68.18kW; power losses P 4 =4.5kW, air flow speed (side fans) 3.5 m/s
The following are presented the results of three tests in which was examines the influence of
forced cooling. Forced cooling was provided by fans, which have been set to all the three ribbed
side of transformer oil tank, as shown in Figs 5 (a) and 5(c). On each of the ribbed sides of
transformer oil tank, from the bottom side is set of five fans with the ability to adjust their speed (by
voltage adjusting) or airflow velocity. Thermal characterization of this case was carried out for
three air velocity 2m/s, 3.5m/s and 5.2m/s at approximately the same other conditions: output power
about 68kW, operating frequency of HF resonant IGBT converter of 7.4kHz and time duration of
test about 10h. At these tests average value of the ambient temperature was about 15C.

Fig.12. Test No7: Thermal characterization of ESP power AR70/1000 at switching frequency f=7.4 kHz, and
output power 68.10kW; power losses P 4 =4.5kW, air flow speed (side fans) 5.2 m/s
On Fig.10 shows that air velocity from 2.1m/ s significant affect on reducing the oil
temperature-T2 in transformer tank. In the case of natural cooling (tests No1-4) the temperature in
the steady state it amounted 60-65C. After the application of forced cooling (airflow velocity
2.1m/s), this value of temperature was decrease of about 10C, and it was about 52C. Similar also
applies to the temperature rise.
On Fig.11 shows that air velocity from 3.5m /s additionally reduces the temperature of the oil
in the transformer tank, for T=8C, or on the value about 44C. The best effect is achieved at the
airflow velocity of 5.2m / s (Fig.12), in which case the oil temperature is reduced to the value less
than 40C.
Forced cooling has shown positive effects on the decrease of the heat sink temperature T2 of
converter DS2000, who with his ribbed side immersed in transformer oil tank. This value was
reduced from 70C (the case with natural cooling) to an acceptable the value of 55C (test No7 -
Fig.12).
A more modest effect of forced cooling was applied on decrease the temperature of the
electrolytes in DC link circuit, or on the temperature T13. In the case of forced cooling with a
velocity from 2.1m/s temperature T13 was still above the threshold value from 70 C (Fig.10). At
velocity from 3.5m/s the temperature was also above the threshold of 70C (Fig.11). At the flow
velocity from 5.2m/s, this temperature was reduced at the value of about 69C. For this reason, it is
performed additionally forced cooling of HVHF cubicle of AR70/1000 power, with fan, which is
placed on the lower right side of the cubicle, as shown in Figs.3 and 5 (in/out air flow). Applying
this cooling system the temperature of DC electrolytes was significantly reduced (on values
approximately 40-50C).
5. CONCLUSIONS
The paper describes electro thermal installation that was used for testing and thermal
characterization of ESP power AR70 / 1000 (nominal output voltage of 70kV and output current of
1000mA). In addition to the many standard electrical tests was performed detailed thermal testing
of this power. These tests have been mandatory before delivery and after that, installing these
devices on ESP station, on thermal power plants. Thermal tests showed some disadvantages of the
natural cooling initially anticipated. This primarily related to the components within the HF
resonant converters DS2000 (DC electrolytes and IGBT modules mounted on its own heat-sink).
Also, the temperature of the oil in the transformer tank is in these conditions, was at the upper limit.
Applying forced cooling of the transformer oil tank and cubicle of HF resonant IGBT converter, are
solved all these problems and achieved the acceptable values increase in temperature in relation to
ambient temperature under all operating regimes and in steady state. After this ESP power
AR70/1000, were ready for final delivery. The results of testing and thermal characterization of
ESP power AR70/1000 are presented by numerous experimental tests that are shown in this paper.

ACKNOWLEDGEMENT
The proposed multiresonant topology represents the basis of power supply AR70/1000 developed in
the framework of scientific cooperation between the School of Electrical Engineering, the University
of Belgrade and Mihailo Pupin Institute, University of Belgrade. This investigation has been carried
out with the financial support of the Serbian Ministry of Science- Project No: TR33022-Integrated
system for flue gas cleansing and development of technologies for zero pollution power plants

REFERENCES
[1] K. Parker, Electrical operation of electrostatic precipitators, The Institution of Electrical
Engineers, London, 2003.
[2] Norbert Grass, Werner Hartmann, Michael Klckner, Application Of Different Types Of High-
Voltage Supplies On Industrial Electrostatic Precipitators, IEEE Trans. on Industry
Applications, vol. 40, no. 6, pp. 1513-1520, Nov/Dec 2004.
[3] P. Ranstad, C. Mauritzson, M. Kirsten, and R. Ridgeway, On experiences of the application of
high-frequency power converters for ESP energization, International Conference on
Electrostatic Precipitation ICESP 2004.
[4] J. Liu, Sheng, J. Shi, Z. Zhang, X. He, LCC Resonant Converter Operating under Discontinuous
Resonant Current Mode in High Voltage, High Power and High Frequency Applications, in
Applied Power Electronics Conference APEC2009, pp. 1482-1486.
[5] R. L. Streigerwald, A Comparison of Half-Bridge Resonant Converter Topologies, in IEEE
Trans. on Power Electronics, vol 3, no. 2, April 1988, pp. 174-182
[6] .Despotovi, S.Vukosavi, D.Arnautovi, I. Stevanovi Visokofrekventno napajanje i njegov
uticaj na kvalitet rada ESI, ELEKTROPRIVREDA,Vol.4, pp.132-143, Dec. 2008 (in serbian).
[7] H.Huang, Designing an LLC Resonant Half-Bridge Power Converter,
http://focus.ti.com/asia/download/Topic_3_Huang_28pages.pdf
[8] John C. Fothergill, Philip W. Devine, and Paul W. Lefley, A Novel Prototype Design for a
Transformer for High Voltage, High Frequency, High Power Use, in IEEE Trans. on Power
Delivery, vol. 16, no. 1.
[9] Zeljko V.Despotovic, Slobodan N.Vukosavic, Mladen Terzic (2013).Contemporary Approach
to Power of Electrostatic Precipitators, 260-265. In PROCEEDINGS of the XII International
Conference INFOTEH 2013, Jahorina .
http://www.infoteh.rs.ba/rad/2013/ENS-4/ENS-4-1.pdf
[10] S.N.Vukosavic, Z. V.Despotovic, Nikola Popov et al. (2013), Multi Resonant Topology of ESP
Power: Simulations and Experimental Results, PROCEDINGS of 17th INTERNATIONAL
SYMPOSIUM on POWER ELECTRONICS - Ee 2013.
[11] S.N.Vukosavic, Z. V.Despotovic, N.Popov (2012) , THE MULTI RESONANT POWER
CONVERTER TOPOLOGY FOR SUPPLYING ELECTROSTATIC PRECIPITATORS ON
THERMAL POWER PLANTS, In PROCEEDINGS of the IV International Conference Power
Plants 2012.
http://e2012.drustvo-termicara.com/resources/files/papers/5574a7.pdf
[12] Slobodan N.Vukosavic, Nikola Popov, Zeljko V.Despotovic (2010), Power Electronics
Solution to Dust Emissions from Thermal Power Plants, 231-252. In Serbian Journal of
Electrical Engineering 7 (2).
http://www.doiserbia.nb.rs/img/doi/1451-4869/2010/1451-48691002231V.pdf
[13] H.A.Pohl, Dielectrophoresis. Cambridge: Cambridge University Press, 1978.
[14] E.H. Kim, B.H. Kwon: Zero-voltage and Zero-current Switching Full-bridge Converter with
Secondary Resonance, IEEE Transaction on Industrial Electronics, Vol. 57, No. 3, Mar.
2010, pp. 1017 1025.
[15] J.A.M. Ramos, A.M. Pernia, J. Diaz, F. Nuno, J.A. Martinez: Power Supply for High
Voltage Application, IEEE Transaction on Power Electronics, Vol. 23, No. 4, July. 2008, pp.
1608 1619.
[16] S. Oglesby, G. Nichols, Electrostatic precipitation, Dekker, New York, 1978

Das könnte Ihnen auch gefallen