SNA 4043 K SNA 4044 K

SNA 4063 K SNA 4064 K


Basic unit for emergency stop and guard door applications
Basic unit as per EN 62061 and EN ISO 13849-1
For safety category 4 and stop category 0
Single or twin channel control
With or without cross short detection
Reset, manually monitored SNA 406xK or automatic SNA 404xK
4 release current circuits SNA 40x4K or 3 release current circuit, 1 signal generator current circuit SNA 40x3K

Equipment versions
SNA 40xxK with screw terminals, fixed
SNA 40xxK-A with screw terminals, plug-in
SNA 40xxK-C with spring force terminals, plug-in

Circuit diagram Inteded use


SNA4043K, SNA4063K
The SNA 40xxK is a safety switch unit. It must only be used as part of the
protection devices on machines for the purpose of personal, material and
machine protection.
It may only be used by competent persons and only on the machine where it
has been fitted and commissioned by a competent person in accordance with
the operating instructions. In the event of any other use and in the event of
modifications to the unit - even in the framework of fitting and installation -
any claim under warranty against Schleicher Electronic GmbH & Co. KG
becomes invalid.
The user must carry out a risk assessment in accordance with
DIN EN ISO 12100.
On this basis you must carry out validation of the entire installation/
SNA4044K, SNA4064K machine in accordance with the applicable standards
The quoted performance level (PL) is only reached if an average num-
ber of switching cycles per year is not exceeded, depending on the
loading of the unit (EN ISO 13849-1 Table C.1) and the specific appli-
cation (EN ISO 13849-1, C.2.4 and Table K.1). Using an assumed B10d
value for maximum load 400,000 we get, for example, a maximum cy-

new release: 24 June 2014 / previour release: 02 December 2013 / datasheet SNA 40xx K / subject to change without further notice
cle number of 400,000 / (0.1 x 30) = 133,333 switching cycles/year.

Function

The inputs to the safety relay are prepared for connecting the safety sen-
sors listed in the section "Areas of application for the unit". Two separate
LED display Significance input circuits control the internal relays. The release current circuits are
SUPPLY (green) Supply voltage is present designed as safe outputs. Setting up an emergency stop device according
to stop category 0 is possible (EN 62061). The unit corresponds to catego-
K1 (green) Current circuit K1 switched ry 4 for safety-relevant parts of control systems (EN ISO 13849-1).
K2 (green) Current circuit K2 switched Functional description: Opening the input circuits causes the release
current circuits to open immediately and the signal generator current
Terminal allocation circuit to close, if available.
Allocation Description SNA 406xK, manual monitored reset: Closing the input circuits does not
cause the current circuits to close immediately as this only happens when
A1 Supply voltage UB+ the reset button is pressed. The reset is performed with a rising edge.
A2 Supply voltage GND SNA 404xK, automatic reset: Closing the input circuits causes
the current circuits to close immediately if the feedback circuit is closed.
S11 +22 V DC (control voltage) This function must be implemented using a corresponding switching circuit.
0 V DC (control voltage) Cross short detection: If the input circuits are switched across two channels,
S21
a cross short is detected if they are switched with a different polarity.
S12 + input circuit 1 (K1) Contactor monitoring: The contactor monitoring monitors the switched
gates controlled by the release current circuits (e.g. motor contactors). The
S52 + input circuit 2 (K2)
release current circuits close via the wiring on the signaling contacts of the
S22 input circuit 2 (K2) switched gates connected in series to the feedback input, but only when
all the switched gates are open. This monitoring only becomes active in
S34 Manually monitored or automatic reset
reset.
13 14 Release current circuit 1
23 24 Release current circuit 2
33 34 Release current circuit 3
43 44 Release current circuit 4, SNA 40x4K
41 42 Signal generator current circuit, SNA 40x3K

Page 4
Functional diagrams
SNA 406xK, manual monitored reset

A1 / A2 , LED SUPPLY
S12, LED K1
S52/S22, LED K2
S34
13/14, 23/24, 33/34 (SNA 4063), 43/44 (SNA 4064)
41/42 (SNA 4063)

tA2 = response time


tB = delay time
tM = minimum switch-on time
tR = fallback time
tW = time required to be ready for operation again
SNA 404xK, automatic reset
A1 / A2 , LED SUPPLY
S12, LED K1
S52/S22, LED K2
S34
13/14, 23/24, 33/34 (SNA 4043), 43/44 (SNA 4044)
41/42 (SNA 4043)

tA2 = response time


tR = fallback time
tW = time required to be ready for operation again

Input switching Function test


Single channel operation Function test with manual reset
The safety sensor is connected between S11 and S12. Connect a wire If the safety sensor is not actuated (e.g. emergency stop not pushed)
bridge between S12S52 and S21S22. Connect a wire bridge be- and if the supply voltage is present, the unit is ready (LED SUPPLY
tween S11S52. lights up). After pressing the reset button, close the release current
Twin channel operation with cross short detection circuits (LED K1 and LED K2 light up). Actuating the sensor causes the
The two isolated switching elements on the safety sensor must be release current circuits to open (LED K1 and LED K2 switch off imme-
connected between S12S52 or S21 S22. Connect a wire bridge diately).
Function test with automatic reset

new release: 24 June 2014 / previour release: 02 December 2013 / datasheet SNA 40xx K / subject to change without further notice
between S11S52. If there is a short circuit in the lines leading to the
emergency stop button, the voltage applied to S11 and S21 is shorted If the safety sensor is not actuated (e.g. emergency stop not pushed)
(cross short detection). Relays K1 and K2 switch back to standby and if the supply voltage is present, the release current circuits close
position, the release current circuits open and the electronic fuse (LED SUPPLY, LED K1 and LED K2 light up). Actuating the sensor causes
triggers. the release current circuits to open (LED K1 and LED K2 switch off im-
mediately).
Regular testing of the protection equipment by competent per-
Derating sons
Max. total current I of all current circuits depending on the ambient Test the installation in accordance with the applicable national
temperature regulations at the intervals quoted therein. This is to show any
changes to the machine or manipulation of the protection equip-
ment since initial commissioning.
Each safety application must be tested at the time intervals that
you have stipulated. The effectiveness of the protection equipment
must be checked by competent and appointed persons.
If changes have been made to the machine or the protection
equipment or if the safety relay has been replaced or repaired, you
should test the installation again.

Areas of application for the unit


The safety relay SNA 40xxK can be used
in accordance with EN 62061 to SILCL3
in accordance with EN ISO 13849-1 to PL e and Category 4
The actual performance level achieved and the safety category as per EN
ISO 13 849-1 depends on external switching, execution of the wiring,
selection of command generator and its setup on the machine.
DC devices The relevant actuators on the machine or plant can be safely deac-
AC devices tivated via the touch-sensitive switching outputs on the safety relay.
Note: Diagram applies to max. operating voltage UO. The safety relay was designed exclusively for use in conjunction with
Observe the max. steady current per current isolated safety sensors such as: emergency stop buttons
path In! The diagram does not apply to UL/CSA (EN ISO 13 850): single channel, twin channel, safety locking devices
applications! Observe Isum ! (EN 1088): single channel, twin channel

Page 5
Technical data SNA 40xxK
Supply circuit, (A1,A2) Minimum Typical Maximum
Input voltage, AC/DC 20.4 V 24 V 26.4 V
Ripple Upp 2.4 Vpp
Rated power at UN 1.6 W / 2.9 VA
Peak current IPeak 1.5 A
Operating voltage UO AC 42 - 48 V AC 35.7 V AC 52.8 V
Rated power 2.3 W / 2.6 VA
Operating voltage UB AC 115 - 120 V AC 97.8 V AC 126.5 V
Rated power 2.2 W / 2.5 VA
Operating voltage UB AC 230 V AC 195.5 V AC 253 V
Rated power 2.1 W / 2.4 VA
Device fuse T 0.5 A
Nominal AC frequency 50 Hz 60 Hz
Control voltage (S11, S21)
Control voltage 22 V DC 40 V DC
Short circuit behavior Short circuit proof without fail
Input circuits S12, S52/S22, S34
Input voltage, UI 19.2 V 26.4 V
Input current S12/S52 25 mA 100 mA
Fallback time, tF 10 ms
Interruption time of Ue (test pulses) 1 ms
Duration of interruption time 25 ms
Reavailability time (tR) 750 ms
Availability time (S34), tA 350 ms
Response time of reset button (S34), (tR1) 150 ms 350 ms
Response time of reset button (S34), (tA2) 50 ms 100 ms
Minimum actuation time (S34), (tM) 100 ms
Output circuit relay contacts (NO contacts, 13/14, 23/24, 33/34 <SNA 40x3K>, 43/44 <SNA 40x4K>)
Release current circuits (NO contacts) 3,4 positively guided
Signal generator current circuit (NC contact, not secure, SNA 40x3K) 1, positively guided
Steady current per current circuit In 8A
Steady current per current circuit In for UL/CSA application 6A
Total current Itot See diagram 1
Total current Itot for UL/CSA applications 12 A
Switching voltage Un 300 V
Switching load 2000 VA
Use category as per DIN EN 60947-5-1 AC-15 Ue 230 V AC, Ie 5 A / DC-13 Ue 24 V DC, Ie 5 A

new release: 24 June 2014 / previour release: 02 December 2013 / datasheet SNA 40xx K / subject to change without further notice
Limited short circuit current 450 A
Contact fusing, gG max. 8 A
Mechanical service life (cycles) 107 switching cycles
Operating data
Contact protection (EN 60664-1) as per DIN EN 60664-1
Rated surge voltage 4 kV
Over-voltage category II
Contamination level 3 external, 2 internal
Rated voltage 300 V AC
Test voltage Ueff 50 Hz 2 kV
Protection rating housing/terminals as per DIN EN 60529 IP 40 / IP 20
Ambient/storage temperature -25 C to +55 C / -25 C to +75 C
Terminal and connection data Screw terminals Spring-loaded terminals
Single core or fine wire 1 x 0.2 - 2.5 mm / 2 x 0.2 - 0.75 mm 2 x 0.2 - 1.5 mm
Stripped length max. 8 mm
Fine wire with core ferule as per DIN 46228 1 x 0.25 - 2.5 mm / 2 x 0.25 - 0.5 mm 2 x 0.25 - 1.5 mm
Permitted tightening torque Max. 0.6 Nm
Weight of DC devices / AC devices 0.21 / 0.25 kg
General system data
Safety integration level SIL3 (IEC 61508), SILCL3 (EN 62061)
Category Category 4 (EN ISO 13849)
Performance Level PL e (EN ISO 13849)
B10d value (relay)
AC-15, 230 V, I = 5 A 300 103 switching cycles
DC-13, 24 V, I = 2 A 2 x 108 switching cycles
I=2A 7 x 108 switching cycles
PFHd (average probability of a hazardous failure per hour) 1) 3 x 108
TM (service life) 20 years (EN ISO 13849)
Stop category 0 (EN 62061)

Page 6
Overview of devices / Part numbers
Type Rated voltage Terminals Part no.
SNA 4043K AC 115-120V 50-60HZ screw terminals, fixed R1.188.1709.0
AC 230V 50-60HZ R1.188.1719.0
AC 42-48V 50-60HZ R1.188.1699.0
AC/DC 24V 50-60HZ R1.188.1689.0
SNA 4043K-A AC 115-120V 50-60HZ screw terminals, pluggable R1.188.1839.0
AC 230V 50-60HZ R1.188.1849.0
AC 42-48V 50-60HZ R1.188.1829.0
AC/DC 24V 50-60HZ R1.188.1819.0
SNA 4043K-C AC/DC 24V 50-60HZ spring terminals, pluggable R1.188.1949.0
SNA 4044K AC 115-120V 50-60HZ screw terminals, fixed R1.188.1759.0
AC 230V 50-60HZ R1.188.1769.0
AC 42-48V 50-60HZ R1.188.1749.0
AC/DC 24V 50-60HZ R1.188.1739.0
SNA 4044K-A AC 115-120V 50-60HZ screw terminals, pluggable R1.188.1889.0
AC 230V 50-60HZ R1.188.1899.0
AC 42-48V 50-60HZ R1.188.1879.0
AC/DC 24V 50-60HZ R1.188.1869.0
SNA 4044K-C AC/DC 24V 50-60HZ spring terminals, pluggable R1.188.1969.0
SNA 4063K AC 115-120V 50-60HZ screw terminals, fixed R1.188.1429.0
AC 230V 50-60HZ R1.188.1439.0
AC 42-48V 50-60HZ R1.188.1729.0
AC/DC 24V 50-60HZ R1.188.1629.0
SNA 4063K-A AC 115-120V 50-60HZ screw terminals, pluggable R1.188.1459.0
AC 230V 50-60HZ R1.188.1469.0
AC 42-48V 50-60HZ R1.188.1859.0
AC/DC 24V 50-60HZ R1.188.1449.0
SNA 4063K-C AC/DC 24V 50-60HZ spring terminals, pluggable R1.188.1959.0
SNA 4064K AC 115-120V 50-60HZ screw terminals, fixed R1.188.1799.0
AC 230V 50-60HZ R1.188.1809.0
AC 42-48V 50-60HZ R1.188.1789.0
AC/DC 24V 50-60HZ R1.188.1779.0
SNA 4064K-A AC 115-120V 50-60HZ screw terminals, pluggable R1.188.1929.0
AC 230V 50-60HZ R1.188.1939.0
AC 42-48V 50-60HZ R1.188.1919.0
AC/DC 24V 50-60HZ R1.188.1909.0
SNA 4064K-C AC/DC 24V 50-60HZ spring terminals, pluggable R1.188.1979.0

new release: 24 June 2014 / previour release: 02 December 2013 / datasheet SNA 40xx K / subject to change without further notice
Dimension diagram
SNA 40xxK SNA 40xxK -A

SNA 40xxK -C

Page 7
Application example (SNA 4044K) Application example (SNA 4063K)
Twin channel EMERGENCY STOP application (cross short detec- Twin channel emergency stop application (cross short
tion) with automatic reset detection) with manual reset and reset button monitor-
The twin channel emergency stop switching is equipped with an ing.
automatic reset. Terminals S12 and S34 must be connected to enable The application example is with reset button monitoring. The device
the automatic reset. The automatic reset is activated if the emergen- is released when the reset button is pressed (terminals S11/S34 rising
cy stop button is not pressed. If the emergency stop button is edge).
pressed, the device switches back to standby and the release current The twin channel emergency stop switching is also deactivated if one
circuits 13/14, 23/24, 33/34, 43/44 open immediately. If the emer- of the two contacts on the emergency stop button does not open. If
a fault occurs (e.g. the emergency stop contact on S22 does not
gency stop button is unlocked again, the SNA 4044K is activated by
open), the safety circuit is activated by the second (redundant) con-
the automatic reset. External contactors are activated via two of the
tact S12. Release current circuits 13/14, 23/24, 33/34 open immedi-
release current circuits on the SNA 4044K. The function of the exter- ately. During periodical self tests, the reset button is used to detect a
nal contactors is monitored by the relevant NC contact. The NC contact between lines and prevents the release current circuits from
contacts must be connected in series in the feedback circuit S12/S34. interconnecting.
Note: An unmonitored manual reset with reset button can be con-
nected in the feedback circuit.

new release: 24 June 2014 / previour release: 02 December 2013 / datasheet SNA 40xx K / subject to change without further notice