The substation transformer is rated 24 MVA, 230 kV delta-13.8 kV wye. Three single-phase Type B
regulators are connected in wye. The equivalent line impedance between the regulators and the load
center node is
Page 1 of 16
= = 120
13800
( )
3
= = 66.3953
120
La corriente secundaria nominal de transformador definir la corriente nominal primaria del CT, y la
secundaria ser la estandarizada de 5 A secundarios
24000000
= = 1004,08
3 13800
= = 1000
= = 5
1000
= = 200
5
b) Determine the R and X settings in Ohms and volts for the compensator circuit.
L= 10,000 ft.
10000
La impedancia de line es: ZL = (0.264 + 0.58 ) = 0.5 + 1.0985
5280
1000
+ = (0.5 + 1.0985 ) = (0.5 + 1.0985 ) = 7.5307 + 16.5448 []
66.3953
7.5307 + 16.5448
+ = = 1.5061 + 3.3090[]
5
c) The substation is serving a balanced three-phase load of 16 MVA, 0.9 lagging power factor
when the output line-to-line voltages of the substation are balanced 13.8 kV and the
regulators are set in the neutral position. Assume the voltage level is set at 121 V and a
bandwidth of 2 V. Determine the final tap position for each regulator (they will be the same).
The regulators have a total of 32 steps (16 raise and 16 lower) with each step changing the
voltage by 5/8%.
669.3916 25.84
= = 3.3470 25.84
200
Page 2 of 16
= (1.5061 + 3.3090)[] (3.0123 + 1.4588) = 9.3640 + 7.7706
= 12.1683 39.68
El voltaje a travs del rel
= = 120 9.3640 + 7.7706 = 110.64 7.7706 []
= 110.91 4.0175
El nivel de voltaje esta ajustado en 121 con un Bandwindth de 2V entonces el regulador se ajustara
en el tap para el voltaje en la carga este entre 120 y 122 V
120 110.91
= = 12,12
0.75
La posicin final del Tap ser la+ 12
El radio de regulacin ser = 1 0.00625 12 = 0.925
d) What would be the regulator tap settings for a load of 24 MVA, 0.9 lagging power factor with
the output voltages of the substation transformer are balanced three-phase 13.8 kV.
1004.1 25.84
= = 5.0205 25.84
200
El nivel de voltaje est ajustado en 121 con un Bandwindth de 2V entonces el regulador se ajustara
en el tap para el voltaje en la carga este entre 120 y 122 V
120 106.592
= = 17.876
0.75
La posicin final del Tap ser la+ 16 mxima posicin
El radio de regulacin ser = 1 0.00625 16 = 0.9
e) What would be the load center voltages for the load of part (d)?
= = 0.9
Page 3 of 16
1
= = 1.1111
= = 8133.10
= = 903.67 25.84
Page 4 of 16
Phase A: 15 kVA, 2400240 V, Z = 1.3 + j1.0%
Phase B: 25 kVA, 2400240 V, Z = 1.1 + j1.1%
Phase C: same as phase A transformer
The transformers are connected to a balanced source of 4.16 kV line to line. The primary currents
entering the transformer are
0.0667 0.0333 0
= [ 0 0.0667 0.0333]
0.0333 0 0.0667
= (3);
= (3);
= [, 0,0; 0, , 0; 0,0, ]
= (1/3) [2,1,0; 0,2,1; 1,0,2];
= [1, 1,0; 0,1, 1; 1,0,1];
= [1,0, 1; 1,1,0; 0, 1,1];
= (1/3) [1, 1,0; 1,2,0; 2, 1,0];
= (^ 1)
= (^ 1)
=
=
=
= (3)
Page 5 of 16
a) Determine the primary line-to-neutral voltages. Select VAB as reference.
4.160
= [4.16 120]
4.16120
1 2 1 0
= [0 2 1]
3
1 0 2
2.0800 1.2009 2.4018 30
= = = [2.0800 1.2009 ] = [2.4018 150]
0.0000 + 2.4018 2.401890
30.6636 34.2892
= () = [69.1716 1.9833 ]
38.8686 + 37.0530
Page 6 of 16
kVA transformador A= 10.923 kVA, 0.9513 lagging power factor
kVA transformador B = 16.456 kVA, 0.8814 lagging power factor
kVA transformador C = 12.718 kVA, 0.6884 lagging power factor
e) Is it possible to determine the load currents in the delta-connected load? If so, do it. If not,
why not?
No es posible calcular las corrientes de carga en el delta puesto que no se ha presentado una
transformacin de corrientes de lnea a corrientes entre fases la carga.
8.12 The three transformers of Problem 8.11 are serving an unbalanced delta-connected load of
Page 7 of 16
The transformers are connected to a balance 4160 line-to-line voltage source. Determine the load
voltages and the primary and secondary line currents for the following transformer connections:
Page 8 of 16
Open wyeopen delta connection, where the transformer connected to phase C has been
removed.
Se emplea el script Problema3OPENGRYV
Page 9 of 16
10.1 For the system described at Page 371 of Kerstings book, and assuming that the regulators are in
the neutral position:
a) Determine the forward and backward sweep matrices for the substation transformer and the
line segment.
Page 10 of 16
Calculo de matrices generalizadas de linea
function [a, b, c, d, A, B] = GeneralizedMatricesL(zabc, yabc, L, NoPh)
a=eye(NoPh)+(1/2)*(zabc*L)*(yabc*L);
b=zabc*L;
c=(yabc*L)+(1/4)*(yabc*L)*(zabc*L)*(yabc*L);
d=eye(NoPh)+(1/2)*(zabc*L)*(yabc*L);
A=a^-1;
B=A*b;
Page 11 of 16
Potencia transformador de la Subestacin
= 5000000
= 69000
= 4160
69000
= 3 ( 4160 ) = 28.7287
4160 2
= = 3.4611
5000000
1.5 + 8
= = 0.0519 + 0.2769
100
0.0519 + 0.2769 0 0
= [ 0 0.0519 + 0.2769 0 ]
0 0 0.0519 + 0.2769
= (1/) [1,0, 1; 1,1,0; 0, 1,1];
= ;
= (/3) [0,2,1; 1,0,2; 2,1,0];
= ;
= (1/) [1, 1,0; 0,1, 1; 1,0,1];
0 0 0
= [0 0 0]
0 0 0
Page 12 of 16
b) Use the modified ladder technique to determine the line-to-ground voltages at node 3. Use a
tolerance of 0.0001 per unit. Give the voltages in actual values in volts and on a 120 V base.
Page 13 of 16
Problem # 5 (20 points)
10.2 For the system described at Page 371 of Kerstings book, three type B step-voltage regulators
are installed in a wye connection at the substation in order to hold the load voltages (node 3) at a
voltage level of 121 V and a bandwidth of 2 V.
11 = 22 = = (0.2296 + 0.4703 )
b) Use a potential transformer ratio of 2400-120 V and a current transformer ratio of 500: 5 A.
Determine the R and X compensator settings calibrated in volts and Ohms. The settings must
be the same for all three regulators.
= 500
= 5
= 2400
= 120
= 2400/120 = 20
500
+ = (0.2296 + 0.4703 ) = (0.2296 + 0.4703 )
20
= 5.7388 + 11.7569 []
5.7388 + 11.7569
+ = = 1.1478 + 2.3514[]
5
Page 14 of 16
c) For the load conditions of Problem 10.1 and with the regulators in the neutral position,
compute the voltages across the voltage relays in the compensator circuits.
345.259 96.3433
= = 3.45 96.3433
100
216.601 151.968
= = 2.16 151.968
100
392.897 35.542
= = 3.92 35.542
100
d) Determine the appropriate tap settings for the three regulators to hold the node 3 voltages at
121 V in a bandwidth of 2 V.
El nivel de voltaje est ajustado en 121 con un Bandwindth de 2V entonces el regulador se ajustara
en el tap para el voltaje en la carga este entre 120 y 122 V
120 108.7906
= = 14.9459 + 15
0.75
120 113.7407
= = 8.3458 + 8
0.75
120 109.5377
= = 13.9497 + 14
0.75
Page 15 of 16
e) With the regulators taps set, compute the actual load voltages on a 120 V base.
1 0.00625 15 0 0 0.9063 0 0
El radio de regulacin ser = [ 0 1 0.00625 8 0 ] = [ 0 0.9500 0 ]
0 0 1 0.00625 14 0 0 0.9125
1 0.00625 15 0 0 1.1034 0 0
= [ 0 1 0.00625 8 0 ] = [ 0 1.0526 0 ]
0 0 1 0.00625 14 0 0 1.0959
Submission
After completing your work, make sure to
1. Submit via email your report (Exam2_LastName_FirstName.docx), and all associated files by Sunday
midnight July 17, 2016. After this time you will have graded zero.
2. Submit a hard copy of your exam on July 22, 2016.