Winters Summers
Air Temp 15 C 45
Density of dry air 1.221 kg/cu.m 1.106
Mass flow of dry air 3.55E-02 kg/s 2.97E-02
Winters Summers
Low High Low
Humidity Humidity Humidity
Temperature 15 15 C 45
Absoulte Partial Pressure at Suction 101.325 101.325 Kpa 101.325
Relative Humidity 15 50 % 60
Vapor Pressure at Suction 1.6977 1.6977 Kpa 9.5606
Humid Air Volume 1.749343 5.808662 Low Flow Case 1.705602
m3/min
m3/min
5.76
Summers 0.029
High
Humidity
45 C
101.325 kpa
85 %
9.5606 Kpa
1.749343 Highest Flow to be handled
m3/min
Max
0.65
101.33
4.54 KW
1.83 KW
6.38 KW
7.50 KW 289.25
0.080347
0.09648
Step 1 Flow Calculation
Winters Summers
Air Temp 15 C 45
Density of dry air 1.221 kg/cu.m 1.106
Mass flow of dry air 2.28E+00 kg/s 2.28E+00
Winters Summers
Low High Low
Humidity Humidity Humidity
Temperature 15 15 C 45
Absoulte Partial Pressure at Suction 101.325 101.325 Kpa 101.325
Relative Humidity 15 50 % 60
Vapor Pressure at Suction 1.6977 1.6977 Kpa 9.5606
Humid Air Volume 112.2121 112.8757 Low Flow Case 130.9839
m3/min
m3/min
Summers
High
Humidity
45 C
101.325 kpa
85 %
9.5606 Kpa
134.3431 Highest Flow to be handled
m3/min
Max
0.65
68.6
236.306 KW
8.899998 KW
245.206 KW
Step 1 Flow Calculation
Winters Summers
Air Temp 15 C 45
Density of dry air 1.221 kg/cu.m 1.106
Mass flow of dry air 1.53E+00 kg/s 1.53E+00
Winters Summers
Low High Low
Humidity Humidity Humidity
Temperature 15 15 C 45
Absoulte Partial Pressure at Suction 101.325 101.325 Kpa 101.325
Relative Humidity 15 50 % 60
Vapor Pressure at Suction 1.6977 1.6977 Kpa 9.5606
Humid Air Volume 75.26423 75.70933 Low Flow Case 87.85503
m3/min
m3/min
4504.8
Summers
High
Humidity
45 C
101.325 kpa
85 %
9.5606 Kpa
90.10814 Highest Flow to be handled
m3/min
Max
0.65
68.6
158.4979 KW
7.58594 KW
166.0839 KW
Shaft Power Shaft Power
(Min) (Min)
KW KW
Case-I (6720 m3/hr & 101.325 Kpa)
Case-II (6720 m3/hr & 68.6 Kpa)
Case-III (4500 m3/hr & 68.6 Kpa)