EAFR-01
EAFR-06 EAFR-08
EAFR-07
DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY
The information, recommendations, descriptions and safety notations in this document are based on Eaton Corporations
(Eaton) experience and judgment and may not cover all contingencies. If further information is required, an Eaton sales
office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in
appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser.
THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES
OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY
EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE
CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES.
In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or other-
wise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or
loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing
power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recom-
mendations and descriptions contained herein. The information contained in this manual is subject to change without notice.
Contents
1. ARC SENSORS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.1 Arc Light Point Sensor Group: EAFR-01-A, EAFR-01-B, and EAFR-01-C. . . . . . . . . . 1
1.2 Arc Light Fiber Optic Loop Sensor (Plastic) EAFR-06. . . . . . . . . . . . . . . . . . . . . . . 2
1.3 Arc Light Fiber Optic Loop Sensor (Glass) EAFR-07. . . . . . . . . . . . . . . . . . . . . . . . 3
1.4 Arc Light Fiber Optic Loop Sensor (High Temperature) EAFR-08 . . . . . . . . . . . . . . 3
1.5 Sensor Type Dependencies. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2. SENSOR CONNECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.1 Arc Light Point Sensor EAFR-01 Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
3. ORDERING CODES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Figure 3. EAFR-01 Point Sensor Mounted Outside The cable to be used for wiring to the sensor should be
Compartment. a shielded, twisted pair cable. Table 1 lists several cables
that can be used. Equivalent cable styles are acceptable
to be used for the dielectric and temperature requirements
of the application. Cable connectors are located beneath
the covers on each end of the EAFR-01 sensors. The cov-
ers can be conveniently detached for fastening the sensor
wires. Reattach the covers after installing the wires. Cable
connectors are located at both ends of the sensor for series
connecting a maximum of three sensors in one line (see
Figure 4).
Figure 4. EAFR-06 Arc Light Fiber Optic Loop Sensor Figure 5. EAFR-07 Arc Light Fiber Optic Loop Sensor
(Plastic). (Glass).
Table 3. Technical Data for the EAFR-06 Arc Light Fiber Light Intensity Threshold 8,000 Lux
Optic Loop Sensor (Plastic). Detection Radius 360 Degrees
Light Intensity Threshold 8,000 Lux Maximum Length 50 m (164 ft)
Detection Radius 360 Degrees Diameter 1.2 mm (0.047 in.)
Maximum Length 40 m (131.23 ft) Bending Radius 1 cm (0.394 in.)
Diameter 1 mm (0.039 in.) Operating Temperature -40 to 85C (-40 to 185F)
Bending Radius 5 cm (2 in.)
Operating temperature -10 to 85C (14 to 185F)
1.4 Arc Light Fiber Optic Loop Sensor (High
Temperature) EAFR-08
The EAFR-08 is an arc light fiber optic loop sensor used for
1.3 Arc Light Fiber Optic Loop Sensor (Glass) EAFR-07 high temperature applications. It is developed to withstand
The EAFR-07 is an arc light fiber optic loop sensor. The temperatures of up to 125C (257F) and is therefore suit-
EAFR-07 fiber is a robust fiber optic cable providing practi- able for installation in wind turbine windings. The EAFR-08
cally unlimited bending radius. EAFR-07 contains hundreds fiber is a robust fiber optic cable providing practically unlimit-
of glass fiber drains covered by a plastic tube making it ed bending radius. The EAFR-08 contains hundreds of glass
extremely strong. The EAFR-07 sensors can be ordered fiber drains covered by a plastic tube making it extremely
in pre-manufactured lengths of 10, 15, 20, 25, 30, 35, strong. EAFR-08 loop sensors can be ordered in pre-
40, 45, 50 m (32.81, 49.21, 65.62, 82.02, 98.43, 114.83, manufactured lengths of 10, 15, 20, 25, 30, 35, 40, 45, 50
131.23, 147.64, 164.04 ft). The EAFR-07 loop sensor fiber m (32.81, 49.21, 65.62, 82.02, 98.43, 114.83, 131.23, 147.64,
optic cable should be distributed throughout the protected 164.04 ft) The EAFR-08 loop sensor fiber optic cable should
switchgear cells. be distributed throughout the protected switchgear cells.
The EAFR-07 is not recommended to be cut and/or spliced The EAFR-08 is not recommended to be cut and/or spliced
on site. If accidental breakage of the loop sensor occurs, on site. If accidental breakage of the loop sensor occurs,
Eaton recommends replacing the loop sensor. Contact your Eaton recommends replacing the loop sensor. Contact your
nearest Eaton representative for more information. nearest Eaton representative for more information.
The fixed light sensitivity of the EAFR-07 sensor is 8,000 The fixed light sensitivity of the EAFR-08 loop sensor is
Lux. The sensor does not require user settings. The loop 8,000 Lux. The sensor does not require user settings. The
sensors detection radius is 360 degrees (see Figure 5). loop sensors detection radius is 360 degrees (see Figure 6).
Figure 6. EAFR-08 Arc Light Fiber Optic Loop Sensor 2. Sensor Connection
(High Temperature).
Figure 9. Sensor Cable Connected to a Sensor Channel 6. After connecting the sensor to the relay, the ERROR
on the Back of the Relay. LED turns on, and the appropriate sensor channel LED
starts to blink (e.g. S1 LED) (see Figure 12). The LEDs
will blink to indicate that there is a new connection that
has been made and the system auto-configuration set-
ting has not been run (see step 7).
Figure 11. Cable Connected to the Sensor PCB. 8. After completing the system auto-configuration setting,
the ERROR LED should be reset and then close both
end covers of the point sensors (see Figure 14).
Figure 14. End Covers Closed on the Sensor. Figure 16. Arc Light Fiber Sensors Plugged into EAFR
Relay.
10. For arc light fiber sensors, they can be plugged into the
back of an EAFR relay as shown in Figure 16.
3. Ordering Codes
2016 Eaton
All Rights Reserved Eaton is a registered trademark.
Printed in USA
Publication No. MN026008EN / TBG1251 All trademarks are property
February 2016 of their respective owners.