Security Access Control System - ACR 23

Security Access Control System (Model ACR21)

> Trouble Shootings


> Reset Procedure
> Firmware Up Gradation Procedure
> Factory Settings (Version 2.1) Dtd.12.06.2015

**Important Points**
Controller Firmware:
The firmware was developed in 2 Stages
Stages.
* Initially, the firmware Version 5.0 was having limited features. The Protocols and other settings were
assumed at early stage to start the work. It needs to upgrade the same with latest Version before
Actual Use.

*A New Version of Firmware 7.7.6 were Developed Later as per actual requirement.
Before commissioning, the Controller Should be Upgraded with Firmware Ver. 7.7.6. Although the same can
be done even after commissioning through SNOC (at RJIL NHQ), but right now it is mandatory to get it done
@ field only.

In field, some of the sites are Upgraded with Latest Firmware Vesion and Some are Still to be up graded.

**Commissioning and Integration with SNOC (at RJIL NHQ)**


**During Commissioning and firmware up gradation to 7.7.6, A Specific IP Address is to be assigned to
controller and further to be integrated with SNOC.

**All Access Cards are supposed to be assigned through SNOC Only.

**Main Purpose of this Document**


** In order to avoid any mistake during Firmware Up gradation and IP Configuration
* This is important to be noted that in any of condition, if the Controller get Configured with Non Confirmed
IP Address, will result in -Controller Stop responding. Neither it will respond to Local Computer nor to
SNOC. In such Condition the Controller need to reset to its factory Settings with help of a Electronic
Hardware +Software Tool. So' Even during any experiment - the controller Last Updated IP Must be
known .

* In case of Controller having Firmware Version - 7.7.6 , makes the resetting very easy by simple
procedure of less than one Minute. So Better to Upgrade the Firmware Firstly in order to save time in case
of Lost IP Addresses. (Procedure Given)

LMD Hitech India Private Limited


Page: 1 of 7 Plot No: 620, Sector8, IMT Manesar, Gurgaon (Haryana) 122050
Security Access Control System - ACR 23

TroubleshootingPointsCheckList&Procedure(V.1.2)

1 ControllerdoesnotrespondswithSNOC
Pleasecheckthesepointsfortroubleshooting Effect,ifnotConfirmed MethodofCorrection

1.1 PowerCableConnectedatrightSource12VoltDC Thecontrollerwillgetburnincaseitget AskwithRJILTechniciantocorrectthesupply.


(OtherAvailableSourcesaremorethan12V) connectedevenforsmalltime.
1.2 ControllerPowerisonand12V.:Thisshouldbechecked AskwithRJILTechniciantocorrectthesupply.
IfLessLockcannotbeoperated.
atcontrollersidebyMultimeter.Itshouldbeinbetween
IfhighThecontrollerwillgetburn.
9~16Volt.
1.3 EthernetCableisOKornot.CanbeCheckedbyelights ChangeorReplacetheFaultyConnectorsof
Willnotrespond
blinkingonbothsideatRJ45Port. EitherEnd.
1.4 IPAddressCrossChecking: WithresettingtoolProcedure#5or
EvenCiscorouterIPmaygetchangedLater(Gateway) WillNotRespondwithSNOC Procedure#7,ifalreadyupgradedtoFW
V7.7.6
1.5 ControllerIPMisconfiguredorforget Withresettingtool
WithresettingtoolProcedure#5or
Procedure#5or
CannotbeintegratedtoSNOC Procedure#7,ifalreadyupgradedtoFW
V7.7.6
1.6 ControllerPingslocally&NotwithSNOC GetthesameConfiguredwithCiscoTeam.
NotreachabletoSNOC
TalkCisco/RJILTechnician.
1.7 FirmwareVersionupdatedwith7.7.6orNot EXITbuttonwillworkbutnoResponse UpgradethefirmwareusingRadiantUtility
withSNOC asperProcedure#6
1.8 EthernetCableisProperlyConnectedwithRJ45Port. ConnecttheSameproperly.Changethe UnplugandPlugagainuntilthePortlight
ConnectorifNeeded. Blinks.
Note:OnceControllerisUpgradedtofirmwareversion7.7.6,theControllerCanberesetwithouttoolwithhelpofExitButton.TheMethodisgivenin
Enclosed Sheet IP Addresses will be set with help of Wipro Simulator only
EnclosedSheet.IPAddresseswillbesetwithhelpofWiproSimulatoronly.

2 AccessCardNotWorking:
Pleasecheckthesepointsfortroubleshooting Effect,ifnotConfirmed MethodofCorrection

2.1 CheckthereaderDataCable PlugthesameProperlyCableRouting UnplugandPlugitagainProperly


mustnotbeloose.
2.2 ReaderCableisinsertedinCorrectportornot.ThisCheck Readerwillgetburn. Oncereader
isonlyincase8pinReader.Thereadersideishaving8 burnt,no
8PIN ReaderandController
Pinswhereasthecontrollersideishaving4+4pins. CONNECTOR (
Connection(For8 Pin Repairing
4pinsaredatapinsand4arepower&beep.Itshouldbe ispossible.
pluggedasperpicture. Replacement
ofReader
Black Cable/Sleeve Grey Cable/Sleeve
inRightPort isonly
inleftPort
Solution.
READER
Note:Thereare2Type ofReaders
AvailableinField.8Pinand7Pin.
8PinReaderneedthisPrecaution,
whereas7pinalreadyfullproofed.

2.3 Checkforbeepwhileshowingthecard.ItShouldBe Lockwillnotgetopened. ReassignthecardwithhelpofSNOC.


SingleBeepSound. Readermayalsogivedoublebeepsound.

Note:ManytimesthereadergivesdoublebeepsoundevenafterassignfromSNOC.ConfirmthefacilitycodewithSNOC.

3 MechanicalODCLocknotWorking
Pleasecheckthesepointsfortroubleshooting Effect,ifnotConfirmed MethodofCorrection
ChecktheActuatorAlignment.Itshouldbeparalleltothe TheactuatorCanbeunscrewedandrefit
3.1
31 LockwillnotbeopenedElectronically
Lock will not be opened Electronically
Rod. again.Dontovertightthescrews.
CableConnection(LockSide):LockShouldbeproperly
3.2 ItwillnotoperatebySNOC PlugthesameFully.
pluggedwithHarness
+ PowerInRed/Black
PowerInRed/Black
CableConnection(ControllerSide):theHarnessMustbe
ProperlyConnectedwithController.TheREDandBlack +/ LockPowerRed
3.3 Doorwillopenonceonly Controller +/
LockPowerBlack
WireshouldbePluggedinPoweroutSocketwhereas +/
TriggerWhite/Blue/Gray
other2wiresshouldbeintriggerpoint. +/ TriggerWhite/Blue/Gray

ChecktheSupplyofController.Itshouldbeonand
pp y
34
3.4 Door will not give any response
Doorwillnotgiveanyresponse Correct the Power supply if Less than 9 Volt
CorrectthePowersupply,ifLessthan9Volt.
minimum9VoltDC
Note:ThekeycanonlyberotatedafterPressingittowardsDoor.NeverRotatewithoutPressing.

LMD Hitech India Private Limited


Page:2of7 PlotNo:620,Sector8,IMTManesar,Gurgaon(Haryana)122050
Security Access Control System - ACR 23

4 ProceduretoCommissionthecontrollerhavingFirmwareVersion7.7.6
4.1 Power off the Controller and Connect RFID Reader.
Press the Exit Switch and keep the switch in PRESSED state and Power it ON by using 12Volt DC supply for next 10 sec or a next BEEP sound
4.2
(Process Given in Procedure #7)
By Above process the Controller will come at its Default IP/Factory Setting, as given below-

Static IP - 10 . 0 . 1 . 2
4.3
Subnet mask - 255 . 255 . 255 . 0
Gateway - 10 . 0 . 1 . 1

Connect Controller and Laptop with help of Cat-6 Cable and Open Network and sharing center. Change IP address of your Computer as Below.

Static IP - 10 . 0 . 1 . 1
4.4 Subnet mask - 255 . 255 . 255 . 0
Gateway - 10 . 0 . 1 . 1
D N S - 10 . 0 . 1 . 1

4.5 Open
p the Internet Explorer
p and enter 10.0.1.2 in Address Bar.
4.6 Take a screen Shot for Ref of Mac ID and Firmware Version (7.7.6) , If Required
4.7 Copy MAC Address
Go to the Wipro Simulator and enter the parameters as Below.
Controller Password - 12345678
Controller 1: IP address - 10.0.1.2
MAC address - Paste Here
4.8 for example- a3:bb:c7:de:77:ff
if MAC Address is a3bbc7de77ff

Press "Configure" Button


4.9
and then press OK (comes later)

On top, go on "Controller Configuration" tab and


Select Controller by using given navigation
arrow / Pallet / Down Arrow
4.10

Click on "Select option" and


choose "UPDATE TARGET COMMUNICATION"

4.11 Enter the IP, Subnet mask, Gateway and DNS


of RIL site in given fields and
press "SUBMIT BUTTON"

LMD Hitech India Private Limited


Page:3of7 PlotNo:620,Sector8,IMTManesar,Gurgaon(Haryana)122050
Security Access Control System - ACR 23
4.12 Now Close the WIPRO SIMULATOR and change the IP address of your Computer Example given below

Example IP Address : Example Computer IP Address:


Target IP - 10 .194.129.116 Static IP - 10 .194 .129.113
Target Subnet - 255.255.255.240 Subnet mask - 255.255.255. 240
Gateway - 10 .194 .129.113 Gateway - 10 .194 .129.113
D N S - 10 .194 .129.113 D N S - 10 .194 .129.113

4.13
4. 3 Open
p Internet Explorer
p and enter Access Controller IP ( Example
p )

Open the Radiante Tester10.2 and choose WIPRO tab


4.14 then enter the "lock box IP , LAPTOP IP" and "MAC Address".
and press the "START BUTTON"

4.15 Press "Beep Test" , "Door Operate 1" and then "UPDATE SERVER Ips" button

4.16 Now Controller is ready to SNOC Integration

5 ProceduretouseRadianteResetterTooltoResetthecontroller
(ResetCumFirmwareUpgradationtoFWVersion7.7.6)

5.1
Unplug/Disconnect Cat-6 Cable from Computer and Controller - Both.
No other Device should be Connected with Computer. (Not Even Programming Tool) x ----------------------- x
5.2 Run the "STM32 St-link utility" on your Computer


5.3 Connect the Cables : 1st Card Reader with Controller, 2nd USB cable between
ST Programming tool and Computer, 3rd Programming tool to Controller and Power12VDC
then Power on by 12 Volt. Computer
4
(Please Dont Change the Sequence of Connecting ) 2
3
Sequence given in Diagram

Reader
5.4 In Target Menu, select "Option Bytes" Controller

ResettingTool

Change the levels to level 0 and OFF


5.5
as shown in image

Ensure all three checkboxes are Unmarked/ Unchecked


5.6
Click on "Unselect all"
Press "Apply"

LMD Hitech India Private Limited


Page:4of7 PlotNo:620,Sector8,IMTManesar,Gurgaon(Haryana)122050
Security Access Control System - ACR 23

In "Target" Menu, go to "Program & Verify"


5.7 Browse and Choose the "chip_Erase_V1.0.hex" file
and "Press Start"

Wait for until a "Beep" Sound comes from Computer

5.8 again In "Target Menu", go to "Program & Verify"


Browse and This time Choose
"Ethernet_IAP_v2_4_1.hex"

5.9 Press "Start" and wait till process get complete.

Go to "Option Bytes" and change


5.10 its levels to "Level 1" form "Level 0" and
"Level 3" from Level "OFF"

Ensure all three Checkboxes are unmarked/ unchecked


5.11
Click on unselect all
Press apply

5.12 Unplug all Cables and Restart the Controller by Disconnecting power wait for 5 Seconds and Reconnect the Power.
5.13 Change adaptor Setting of your Computer. Change IP, Gateway, Subnet Mask and DNS as given below

IP address - 64 . 235 . 234 . 30


Subnet mask - 255 . 255 . 255 . 0
Gateway - 64 . 235 . 234 . 30
DNS - 64 . 235 . 234 . 30

NOW Connect Cat-6 cable between Computer p and Controller. Open


p Internet Explorer
p and Enter "IP- 64.235.234.31" in address bar as Our
5 14
5.14
Controller is having Default IP 64.235.234.31 this time

5.15 Login to page by Entering the USER ID as < user > and PASSWORD as < Acs_13 >

Click on Browse and select the .bin file "Access_Control_System_V7_7_6"


5.16 (Although we could select "Access_Control_System_v5_0" here but by using "Access_Control_System_V7_7_6" the controller will directly
come to FM Version 7.7.6 and up gradation Step Version 5.0 to 7.7.6 would not be required)

5.17 Press Upload Button and Reset MCU


5 18 Enter the Access Control IP in Internet Explorer Address Bar again,
5.18 again You can Confirm the Firmware version 77.6.6
6 6 and MONITORING

5.19 Now controller is completely ready to communicate with "Wipro Simulator"

LMD Hitech India Private Limited


Page:5of7 PlotNo:620,Sector8,IMTManesar,Gurgaon(Haryana)122050
Security Access Control System - ACR 23

6 FirmwareUpgradation
(Fromanyversionto7.7.6byRadianteUtility)
PleaseNote:ThisProcessisforthoseSAS/ControllerofwhichtheIPAddressisalreadyhadbeenchangedasperRJILbut
havingLowerVersionofFirmware.InCase,iftheIPaddressislost,itisrecommendedtoResetthecontrollerbyResettool.In
suchcasesProcedure#5applicable.
6.1 Power up (12 Volt DC) the Controller through Connector-Top one(As shown in Figure) . Connect the Power
12V. DC
co t o e to laptop
controller aptop by us g Cat
using 6 cab
Cat-6 e. Thee bblinking
cable. g oof LED on
o RJJ 455 Jack
Jac wwill
ensure the perfect connection.
Change adaptor Setting of your Computer. Change IP, Gateway, Subnet Mask and DNS as given below:

Example IP Address (Already Changed in Controller Example Computer IP Address:


during 1st Commissioning)

Existing IP (Controller)- 10 .194.129.116 Static IP - 10 .194 .129.113


6.2 Existing Subnet - 255.255.255.240 Subnet mask - 255.255.255. 240
Existing Gateway - 10 .194
194 .129.113
129 113 Gateway
Gateway - 10
10 .194
194 .129.113
129 113
D N S - 10 .194 .129.113
Note:
** If, IP and Gateway, DNS of controller are not known or does not match with previously used when configured it, in such condition it will not
connect to the utility so be sure about the IP used in the controller before. Reset by tool is the only way to bring the same on Factory Setting.

** Many times Cisco Router Address found Changed by some technical reasons. one need to be sure while SNOC integration.
Now open the Radiante Tester and change the value of "Lock Box IP" Pressthe"Start" button ,commandokmessagewillappearafter
and Laptop IP according to the Static IP and Gateway respectively thatcheckBeepTestandDoorOperate1 notrequired
of the site and press the respective given buttons and confirm it

Start
LockBoxIP Button

6.3 Start

& LaptopIP
6.4

6.5 Click on "Factory Set(4)" button in bottom of window.


POP Message will Appear to Confirm
6.6 Wait
W i for
f 15 seconds
d andd then
h Close
Cl Radiante
R di tester.
6.7 Go in "Task Manager" on your system and "END" the process "Dual Server" (***Very important***)

6.8 Unplug the Rj45 cable from laptop and Plug it again after 5 Secs.
6.9 Go to Explorer and Write Controller IP in Address Bar. > Login Page will appear. <
6.10 Login to page by Entering the USER ID as < user > and PASSWORD as < Acs_13 >
6.11 Click on Browse and select the .bin file "Access_Control_System_V7_7_6"
6.12 Press "Upload Button" and Reset MCU
6.13 Enter the Access control IP in IE again You can see the Firmware version 7.7.6 is there
6.14 Copy the Mac Address from web page and Open the Radiante tester and go to "Wipro Tab"
6.15 Paste the Mac Address in the given field and change the value of Lock Box IP and Laptop IP
according to the Static IP and Gateway resp. of the site and press the respective given buttons and
confirm it.

6.16 Press the "Start Button" and it will show connected instead of Status Now and check Beep Test and
Door Operate 1 again .

6.17 Press the button "Update


Update Server IP
IP's"
s Please confirms ok/yes and there will be a message that Server
IP updated Successfully
6.18 Close the Radiante Tester and your Controller is ready to communicate with SNOC Server.

LMD Hitech India Private Limited


Page:6of7 PlotNo:620,Sector8,IMTManesar,Gurgaon(Haryana)122050
Security Access Control System - ACR 23

ResetaControllertoFactorySettingbyPressingExitButton
7
(AvailableonlyifControllerisalreadyupgradedtoFirmwareVer.7.7.6)
Once any controller is upgraded with Firmware version 7.7.6 , it can be Reset "n" number of times just with help of Exit Button.

1 2
Unplug ThePowerSocket
&ConnectReaderwithController

Reader
Reader

PressExitButton
3 Keep the Button Pressed and Plug the Power Socket
KeeptheButtonPressedandPlugthePowerSocket 4 Keepthe ButtonPressedformorethan
10SecondsoraBeepSoundComes.
whereasthepowermustbeon.

5
Releasethepowerbuttonafter10Seconds. IMPORTANT!!

***
AssignnewIPAddress.Don't UnplugorSwitchthePoweruntill
you Assign new IP address to controller by"WiproSimulator
youAssignnewIPaddresstocontrollerby "Wipro Simulator
Utility".

*** Now
NowourControllerisonFactorySettingandHavingIPaddressasbelow:
our Controller is on Factory Setting and Having IP address as below:
Static IP - 10 . 0 . 1 . 2
Subnet mask - 255 . 255 . 255 . 0
Gateway - 10 . 0 . 1 . 1

8 OtherPointstobeNotedWhileUpgradation/CommissioningProcess
A Utility may not connect with controller or any process can also be hindered because of following reasons.
TheremustnotbeanyotherconnectionsrunningintheLaptop(Example:Wireless,WLANorVirtualLANs).onlyWiredLANshouldbeEnabled
onwhichtheboardisconnecteddirectly.
hi h th b d i t d di tl
AntiVirussoftwareattimesblockstheports.Sotheseshouldbedisabledtemporarilyorport8080shouldbeallowedtopass.
WindowsFirewallmayalsointerfereattimes.Port8080inInboundrulesshouldbeenabledorFirewallshouldbedisabled.

ForanytypeoftroubleshootingQueryPleaseContact: