XLPE UNDER GROUND CABLE
AC VOLTAGE WITHSTAND TEST ISSUED DATE
1. TITLE
XLPE UNDER GROUND CABLE AC VOLTAGE WITHSTAND TEST
2. SCOPE
CABLE AC VOLTAGE WITHSTAND TEST
3. OBJECTIVE
This is to assure that the requirements of electrical individual test works are meets the codes
requirements and contract specifications. To make sure, the works are carried out in
acceptable workmanship and follow the requirements in the quality manual.
4. REFERENCE
4.1 Reference Manual
4.2 Applicable Manufacturers Manuals/Standards
4.3 Contract Specifications and Construction Drawing
4.4 Standard for hand-over test of electric equipment installation engineering
( GB Standard 50150-2006 ).
4.5 Withstand voltage tests on XLPE cables can be performed using the AC test
system with variable frequency once laid on-site. The test system operates in
a frequency range from 20 Hz to 300 Hz and complies with the requirements
according to IEC 60840 and IEC 62067.
[Type text]
DOCUMENT
XLPE UNDER GROUND CABLE
AC VOLTAGE WITHSTAND TEST ISSUED DATE
[Type text]
DOCUMENT
XLPE UNDER GROUND CABLE
AC VOLTAGE WITHSTAND TEST ISSUED DATE
Test duration
60 minutes
Time
Capacitor voltage
devider A B C
2x 2,6 nF/160 kV
HV Reactor
3 x 160kV/400kVA
Excitation
Transformer
6/12/18/24 kV / 60 kVA
Input Power
3P/3W , 380 Volt
Variable Frequency
Power Control
Freq kV
Amp
[Type text]
DOCUMENT
XLPE UNDER GROUND CABLE
AC VOLTAGE WITHSTAND TEST ISSUED DATE
8 Test Form.
Test Record
Cable AC Voltage withstand test
Applied Voltage Time Charging current
Phase Remark
( KV ) (minute ) ( Amp )
R 150 60 Passed
S 150 60 Passed
T 150 60 Passed
Remark :
[Type text]
DOCUMENT
XLPE UNDER GROUND CABLE
AC VOLTAGE WITHSTAND TEST ISSUED DATE
Insulation Resistor ( M )
Phase AB PI Remark
R 15 R 60 R 600
Remark :
Signature
Name
Date