Sie sind auf Seite 1von 5

Harmonic Current Emission of Photovoltaic

Installations under System Conditions

Juergen Schlabbach

University of Applied Sciences, Bielefeld, Germany


Wilhelm-Bertelsmann-Str. 10
D-33609 Bielefeld, Germany
Phone: +49 521 1067213
Email: juergen.schlabbach@fh-bielefeld.de

Index terms – PV-generators, Harmonic currents, generation; the THDI will remain below 10% in case the
ENS-signal, EN 50160, Test conditions loading of the inverter exceeds 18% of the rated power [2],
[3]. Some measurements are significantly lower for low load
Abstract—Harmonic currents of PV-inverters show a conditions, which is the effect of the ENS-signal generated by
significant dependency on the harmonic voltage content of the inverter to detect and to prevent islanding operation [4].
the AC-system voltage. Measurements of harmonic For increasing generating conditions, the ENS-signal is
currents were carried out in LV-systems and under increasing the variety of the THDI only to a comparatively
laboratory test conditions with adjustable harmonic small extend, as can be seen in Fig. 1.
content of the AV-voltage. Two PV-inverters, one with
coupling transformer and one without transformer were International standards [5] and [6] define standard test
tested. The results indicated that the emitted harmonic conditions with respect to the harmonic voltages of the
currents depend strongly on the harmonic voltages voltage source, in order to measure the emitted harmonic
prevailing in the AC-voltage. PV-inverters without currents of any equipment; the standards have to be applied to
transformer show significant lower harmonic currents PV-inverters as well, as special standards are missing up to
than inverters with coupling transformer. The standard now. The defined maximal harmonic voltages, e.g. for the
test conditions as defined in international standards does 5th harmonic equal 0.4%, are comparatively lower than the
not consider real system conditions with respect to the expected values of harmonic voltages of power systems [7].
harmonic voltages in system voltage. The measured
currents as documented in data sheets are therefore
comparatively lower than under the condition of real
system operation.

1. INTRODUCTION
Grid-connected photovoltaic systems (PV-systems) with
DC/AC-converters are subject to harmonic current emission
which depend on the type of technology used, on the control
strategy of the DC/AC-inverter, on the existence of high- or
low-frequency coupling transformer and on the harmonic
voltages prevailing in the AC-power system. A dominant role
on the harmonic current emission is also given by the
performance of the AC/DC-inverter under partial generating
conditions [1].
Fig. 1 indicates the total harmonic current THDI of a PV- Figure 1. THDI of current of a PV-inverter without transformer
(PAC = 5 kW) for different loading conditions
generator (Pn = 5 kW; PWM-frequency 16 kHz; without
transformer) under different generating condition (ratio P/Pn),
measured for the period of one week. The shape of the THDI
is characterised by a comparative high value under low
2. MEASUREMENTS IN POWER SYSTEMS
_________________________________________________
2.1 PV-Inverter under Investigation
978-1-4244-1744-5/08/$25.00 ©2008 IEEE
Measurements of harmonic currents and voltages in a
generating conditions with a sharp decay for increased

Authorized licensed use limited to: AALTO UNIVERSITY. Downloaded on February 23,2010 at 05:05:56 EST from IEEE Xplore. Restrictions apply.
LV-power system have been carried out for periods between 0,5

four days and one week. The power system consists of cables

I in A
0,5 0-5 % Pr
and overhead-lines supplying mainly domestic load, small 0,4
5-10% Pr

industry and some agricultural load. The system is fed from 0,4
10-15 % Pr

the local 20-kV-system (S”k = 46 MVA at 20 kV; 630-kVA-


15-20 % Pn

0,3 20-40 % Pr

transformer; uk = 6 %). Different types of PV-generators with 0,3


40-60 % Pn

rated power of the DC/AC-inverter between 2.1 kW and


60-100 % Pr

0,2 >100 % Pr
5 kW, with and without transformer, are installed in the 0,2
system.
0,1

As example the measurement results of a 5-kW-inverter 0,1

without transformer (nominal AC-power: 4.6 kW; maximal 0,0

DC-power: 5.3 kW; MPP-tracking-range: 125 to 750 V; PV- 3 5 7 9 11


Harmonic order
13 15 17 19 21

panel 6 kW) are presented in the context of this chapter,


except were noted. Figure 3. Harmonic currents (95%-probability) of the inverter for
different generating conditions measured during one week

2.2 Harmonic Currents and Generated Power


Fig. 2 indicates the THDI (Total Harmonic Distortion) 12

and the generated power of a 5-kW-inverter measured

Ih /I1 in %
0-5% Pr
10
through one day in summer. During start- and stop-period of 5-10% Pr
10-15% Pr
the generator in the morning and evening hours, characterised 8 15-20% Pr

by low generated power (below ≈ 800 W), the THDI is 20-40% Pr


40-60% Pr
significantly higher than during the rest of the day. 6
60-100% Pr
>100% Pr

50 10000 2

40 9000
0
30 8000
T H D (I) [% ]

3 5 7 9 11 13 15 17 19 21

Harmonic order
20 7000

10 6000
Harmonic order
P [W ]

0 5000

-10 4000 Figure 4. Relative harmonic currents (95%-probability) of the


-20 3000
inverter for different generating conditions measured
-30 2000
during one week
-40 1000 The absolute values of the harmonic currents as per Fig. 3
-50 0 are increasing, whereas the relative harmonic values of the
00:00 02:00 04:00 06:00 08:00 10:00 12:00
Time
14:00 16:00 18:00 20:00 22:00 00:00
harmonic currents as per Fig. 4 are decaying with increasing
generated power. This seems to be a typical behaviour of the
Figure 2. THDI (upper curve) and generated power (lower curve) of PV-inverters, as it was found for all types and rating of the
the PV-inverter (PAC=5kW) investigated inverters.
A statistical assessment of the low order harmonic 2.3 Harmonic Currents and Harmonic Voltages
currents has been carried out with the measured data of one
week. Figures 3 and 4 outline the 95%-probablity-values of Further assessment of the measurement results was
the odd harmonic currents up to the 21st order with different carried out to indicate the relation between harmonic current
loading condition of the inverter. Other harmonic currents emission of the inverter and harmonic voltages, prevailing in
were measured and assessed as well, however are of less the power system. Fig. 5 indicates the results of this
significance as compared with the indicated. Significant assessment obtained for a PV-inverter operated with
differences in the harmonic current emission for different approximately 2.35 kW to 2.45 kW (47% of rated power).
generated power are indicated for the indicated ranges of The straight lines in Fig. 5 indicate the average increase of the
P/Pr below 5%; up to 10%, 15% and 20%; up to 40%, 60% emitted harmonic currents for increasing harmonic voltage.
and 100% and above 100% as indicated. The power range as mentioned was chosen due to the
availability of a sufficient high number of data (n ≥ 50) for
each harmonic order of voltage and current. As can be seen
from Fig. 5 the emitted harmonic currents are increasing with
increasing harmonic voltage for harmonic orders 5 to 11 and
decreasing for the 3rd harmonic.

Authorized licensed use limited to: AALTO UNIVERSITY. Downloaded on February 23,2010 at 05:05:56 EST from IEEE Xplore. Restrictions apply.
3. LABORATORY MEASUREMENT
300 3.1 Test Equipment
Pn = 5kW
250 rd P =2.35kW- 2.45kW In order to separate the different effects from each other,
3
the emitted harmonic currents of the PV-inverter were
Harmonic current in mA

th
7
200 measured under defined conditions in laboratory tests with a
voltage source having adjustable harmonic voltages in a
150 th
5 suitable range that coincide with harmonic voltages in real
power systems. The effect of the prevailing harmonic
100
th
9
voltages in the power system can be eliminated if a pure
50 th
sinusoidal voltage source is used for the measurement.
11
A waveform generator, harmonic voltages to be adjusted
0 individually up to the 40th order, to represent the AC-system
0,0 0,5 1,0 1,5 2,0 2,5 and a DC-voltage constant with maximal output voltage
Harmonic voltage in% 300 V to represent the DC-voltage source were used. The
AC-load was represented by small electrical heating
Figure 5. Emitted harmonic currents of PV-inverter for different appliances having different power between 200 W and 2 kW,
harmonic voltages, generated power: 2.35kW – 2.45kW to be switched on and off according to the required load.
Measurement of harmonic voltages and currents was carried
out in accordance to IEC 61000-4-7 [8].
This dependency of the harmonic currents from the
harmonic voltages in the power system is typical for all types
of inverters without 50-Hz-transformer. Inverters having a 3.2 Voltage Parameter for Testing
transformer on the AC-side show a slightly different
behaviour of the harmonics, as the 3rd harmonic current as all During the tests, the harmonic voltages of the AC-source
other harmonic currents is increasing with increasing have been modified one by one to different values starting
harmonic voltage. As can be seen from Fig. 5, the range of from zero up to some percent of the nominal system voltage.
the harmonic voltages is comparatively small. The maximal percentage value of the individual harmonic
voltages was taken from EN 50160 [7]. This standard
The assessment of the even order harmonics similar to describes, besides other power system disturbance
those of the odd order could not be carried out, as the number parameters, the expectation values of harmonic voltages
of measurements of harmonics was very small and the results which coincide with the compatibility levels as per IEC
did not show any coincidence. 61000-3-2 and IEC 61000-3-12, details are included in Table
Table I shows the gradient “increase of harmonic current II.
related to the increase of harmonic voltage” obtained from The test voltage, e.g. for the 5th harmonic, was adjusted
Fig. 5. between 0% and 6% in steps of 0.6% each, the power of the
inverter was adjusted for all tests to 50% of the rated power
TABLE I. GRADIENT FOR THE INCREASE OF EMITTED HARMONIC
by adjusting the voltage-constant DC-source and the AC-load
CURRENTS RELATED TO PERCENTAGE HARMONIC VOLTAGE (DATA IN accordingly.
MA/% OF VOLTAGE)

Harmonic order Gradient in 3.3 Results of Laboratory Measurement


mA/ % of voltage
3rd -20.2 A set of 15 measured data per harmonic order and
5th 35.0 harmonic voltage step was measured during the tests,
7th 79.3 however the variety between the individual measurements for
9th 62.3 the same harmonic order was negligibly small. Figs. 6 and 7
11th 42.7 indicate the dependency of the individual harmonic currents
from the harmonic voltage in the AC-side. The individual
The result as per Table 1 indicates, that the emitted steps indicate the percentage increase, step 10 is identical to
harmonic currents depend strongly on the harmonic voltages the maximal value of harmonic voltage as per EN 50160.
prevailing in the power system as the harmonic currents are The 3rd harmonic is characterised by a constant decay with
increasing with increasing harmonic voltage. This effect of increasing harmonic voltage with a similar gradient as in the
increasing (decreasing) harmonic current with increasing field test. The odd order harmonics, represented in Fig. 6 up
harmonic voltage can be interpreted either originating from to the 19th order, show a minimum at different voltage steps.
the PV-inverter itself or from the power system. The The minimum, if any, of the even order harmonic currents
individual effects cannot be measured separately in this case. (see Fig. 8) occurs with step 1 of the harmonic voltage except
for the 2nd order harmonic where the minimum of the
harmonic current is reached between step 2 and step 3.

Authorized licensed use limited to: AALTO UNIVERSITY. Downloaded on February 23,2010 at 05:05:56 EST from IEEE Xplore. Restrictions apply.
400,00 4. TEST CONDITIONS AND H ARMONIC ASSESSMENT
3

350,00
5 4.1 Standards for Harmonic Current Emission
7
9
300,00 11 International standards IEC 61000-3-2 and IEC 61000-3-12
13
[5, 6] define voltage test conditions (type test) to carry out
Cu rren t in mA

15
250,00 17
19 measurements of harmonics emitted by power electronics.
200,00 These standards have to be applied to PV-inverters as well, as
far as specific standards for PV-inverters are not available.
150,00
Both standards apply for low-voltage systems, PV-inverters
100,00 with low rating (Ir ≤ 16 A) are allowed to be tested under
more restricted conditions than inverters with higher rated
50,00
power (Ir ≤ 75 A).
.
0,00
Sinus Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 Step 7 Step 8 Step 9 Step 10

Voltage step
4.2 Comparison of Standard Test Conditions and Real
Figure 6. Emitted odd order harmonic currents of a PV-inverter System Conditions
for increasing harmonic voltage during laboratory tests
Table III outlines the maximal values of the harmonic
voltages for standard test conditions and the maximal
expected values in real power systems as per EN 50160 [7].
120,00
The values (columns 2 and 3) indicate that the harmonic
2
4
voltages defined in the standard test conditions as per IEC
100,00
6 610000-3- are lower than the harmonic voltages that might be
8
10 expected in the power system (column 4). The standard test
80,00 12
14
conditions as per IEC 61000-3- do not reflect the harmonic
C u rent in m A

60,00
16
18
conditions that are expected in power systems, the harmonic
20 current will be significantly higher than those measured
40,00
during the type test.

20,00
TABLE III. PERMISSIBLE HARMONIC VOLTAGES (IEC 61000-3-2
AND EN 61000-3-12), EXPECTATION VALUES (EN 50160)
0,00
Sinus Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 Step 7 Step 8 Step 9 Step 10
Harmonic order Voltage in % of nominal voltage
Voltage step
61000-3-2 61000-3-12 EN 50160
3 0.9 1.25 5.0
Figure 7. Emitted even order harmonic currents of an inverter
5 0.4 1.5 6.0
for increasing harmonic voltage during lab-tests
7 0.3 1.25 5.0
9 0.2 0.6 1.5
The harmonic voltages for minimal harmonic current are 11 - 0.7 3.5
13 - 0.6 3.0
indicated by bold figures in Table II. For comparison the
Even (2 - 10) 0.2 0.4 2.0 - 0.5
expectation values as per EN 50160 are also included in the
Other (11 - 39) 0.1 - 3.5 - 1.5
table. The minimal conditions for the even order harmonics Other (12 - 40) - 0.3 -
are given for harmonic voltages: u2 = 0.4%; u4 = 0.1% and for
higher odd harmonics u6 = 0.05%.
Table IV gives the relation between the minimal harmonic
currents for the maximal permissible harmonic test voltage as
TABLE II. MINIMUM OF EMITTED HARMONIC CURRENT ( ODD per IEC 61000-3-12 and the harmonic currents emitted under
ORDER) AS COMPARED WITH THE HARMONIC VOLTAGE DURING maximal expected harmonic voltage conditions as per EN
LABORATORY TEST 50160.
Harmonic Step of uh [%] uh [%]
Order test voltage of test voltage EN 50160
3 > 10 > 5% 6%
5 4 2.4% 6%
7 2-3 1.2 – 1.5% 5%
9 5 0.75% 1.5%
11 1 0.35% 3.5%
13 1 0.3% 3%
15 4–5 0.02 – 0.025% 0.5%
17 1 0.02% 2%
19 - - 1.5%

Authorized licensed use limited to: AALTO UNIVERSITY. Downloaded on February 23,2010 at 05:05:56 EST from IEEE Xplore. Restrictions apply.
TABLE IV. COMPARISON OF HARMONIC CURRENTS EMITTED UNDER [3] Drees, S.; Kohn, A.; Schlabbach, J.; Strathmann, D.; Vogel, E.:
STANDARD TEST CONDITIONS (EN 61000-3-12) AND IN CASE OF Harmonic current emission of PV-installations (German). ew, Bd. 104
MAXIMAL HARMONIC VOLTAGES (EN 50160) (2005), Heft 02, S. 68-71.
[4] E DIN VDE 0126-1-1 (2005-5): Automatic disconnection device
Harmonic Minimal current; Exp. current Relation between a generator and the public LV-grid (German).
order col. 3 to
Test as per Voltages as per Col.2 [5] IEC 61000-3-2 (2005-11): Electromagnetic compatibility (EMC) - Part
3-2: Limits - Limits for harmonic current emissions (equipment input
IEC 61000-3-12 EN 50160 current <= 16 A per phase).
3 74.3mA 74.3mA 0.0
5 65.8mA 193.8mA 2.9 [6] IEC 61000-3-12 (2004-11): Electromagnetic compatibility (EMC) -
Part 3-12: Limits - Limits for harmonic currents produced by equipment
7 30.4mA 285.9mA 9.4 connected to public low-voltage systems with input current >16 A and
9 15.1mA 69.2mA 4.6 <=75 A per phase.
11 29.6mA 349.9mA 11.8
[7] EN 50160 (2006-8): Voltage characteristic of electricity supplied by
13 31.5mA 365.8mA 11.6 public distribution systems (German).
[8] IEC 61000-4-7 (2004-7): Electromagnetic compatibility (EMC) - Part
Table IV indicates that the emitted harmonic current under 4-7: Testing and measurement techniques - General guide on harmonics
and interharmonics measurements and instrumentation, for power
real system conditions can exceed the harmonic currents of supply systems and equipment connected thereto.
the PV-inverter obtained for standard test conditions as per
IEC 61000-3- by far.
Juergen Schlabbach (b. 1952) studied power system engineering at the
Technical University of Darmstadt, Germany, from where he received the
5. CONCLUSION AND OUTLOOK academic degrees as Dipl.-Ing. in 1977 and as Dr.-Ing. in 1982. He worked
till 1992 in an engineering company. He worked in responsible positions for
The comparison of site measurements and laboratory tests planning and design of public and industrial power systems mainly in
with controlled harmonic voltage conditions indicated that the Arabian and Asian countries.
emitted harmonic currents depend strongly on the harmonic Since 1992 he is Professor at the University of Applied Sciences in
Bielefeld, Germany, responsible for electrical energy systems and renewable
voltages in the AC-voltage. Standard test conditions as energy schemes. He is member IEEE, VDE and VDI.
defined in IEC 61000—3-2 and IEC 61000-3-12 do not take Topics of research include measurement and analysis of harmonics and
account of this characteristic of the PV-inverter. The flicker, connection of renewable energy generation to the power system and
harmonic voltages in the test voltage to be allowed for the optimization of medium voltage cable systems. More information can be
obtained from: www://http.fh-bielefeld.de/fb2/labor-ev
standard test procedure do not reflect the expected harmonic
voltages in AC-systems. The emitted harmonic currents
depend furthermore on the generated power of the PV-
inverter, resulting in high values of the harmonics for low
generation conditions and low values for high generation
conditions.
It is strongly recommended to consider a new approach for
testing of harmonic current emission of PV-inverters. The
special characteristic of the PV-inverters as explained in the
paper shall be taken into account. Tests for harmonic current
emission shall be carried out taking account of:
. maximal expected harmonic voltages in power system as
per EN 50160 to determine the worst conditions,
. partial generation conditions of the PV-inverter.
Assessment of the system connection of PV-inverters shall
be based on the distribution function of the expected
harmonic current emission and shall take account of the
typical daily and seasonal generation. The application of
simulation programmes is highly recommended.

References
[1] Chicco, G.; Schlabbach, J.; Spertino, F.: Characterisation of the
harmonic emission of grid-connected PV-systems. Proc. of IEEE-
Conference St. Petersburg PowerTech 2005. St. Petersburg, Russland
(June, 27-30, 2005), paper 66.
[2] Schlabbach, J.: Simulation of harmonic current emission of grid-
connected photovoltaic generators. Proc. of 8th International Conference
on Electrical Power Quality and Utilisation EPQU’05. Cracow, Poland
(Sept. 21-23, 2005), Paper 23, pp 545-552.

Authorized licensed use limited to: AALTO UNIVERSITY. Downloaded on February 23,2010 at 05:05:56 EST from IEEE Xplore. Restrictions apply.

Das könnte Ihnen auch gefallen