chiller controller for water
refrigerators and heat pumps

GENERAL DESCRIPTION GENERAL OPERATION


WHAT IT IS
CH-DIN is an electronic device designed Machine states
CH-DIN is an electronic device to control water refrigerators and heat Four different machine states are provided:
designed to control water pumps (air-air, air-water and water-water). ON, OFF, STAND-BY and VIRTUAL OFF.
refrigerators and heat pumps (air- Its main feature is the capability to perform In the ON state (machine on) both the front
air, air-water and water-water). all functions that are usually assigned to key and the remote input (parameter 90 =
Its main feature is the capability to external devices, thus eliminating addition- 2 and remote ON-OFF input closed) can
perform all functions that are al electrical connections to anything other be used to start the instrument.
usually assigned to external than the controlled devices. The OFF state (machine off) is achieved
devices, thus eliminating additional It controls the temperature of the cooling through the front key only; the Line Led is
electrical connections to anything and heating water, the defrost cycles, the on if the instrument is powered.
other than the controlled devices activation of the anti frost resistors for the The STAND-BY state is accessed by
water circuit, the compressor activation pressing the Mode front key (only when
timing and performs the continuous pro- parameter 68 = 2). In this case all the ma-
HOW IT IS MADE portional regulation of the condensing chine outputs are disabled save those
fans. controlling the anti frost resistors; the dis-
Main outputs: 4 relay outputs The CH-DIN functions can also be ex- play of all alarms but the anti frost and the
4(2)A AC 250V for compressor, anti- panded through other elements of the CH- flow switch are active.
frost resistors, water pump and DIN Microtech system: the control mod- The machine can be set to VIRTUAL OFF
inversion valve circuit 1 ules for a second compressor (C2-DIN, by the remote input only (parameter 90 = 2
Condenser fan output: 1 voltage C2-DIN/P and C2-DIN/12/ID220), the re- and remote ON-OFF input open). In this
digital output to drive the special mote keyboards (TS-DIN/S, TS-W and TS- state the compressor, fan and pump out-
fan modules W/OP), the fan control modules (CF-05, puts are disabled and the E00 error mes-
Alarm output: 1 output on static CF-15, CF-22 and CF-REL) and the inter- sage is displayed.
relay (SSR) 1248 Vac, maximum face modules to install a remote keyboard Selecting the type of regulation
consumption 200 mA (CS-DIN/TTL-CL), the connection to a lo- The regulation type can be selected
CH-DIN analogue inputs: 3 PTC cal PC (CS-DIN/232-TTL) and to a remote through the Mode front key or through
probes for input water control, PC (CS-DIN/232-485 and CS-DIN/485- the remote ON-OFF input in the terminal
output water in circuit 1 and TTL). block.
condensation circuit 1 (CH-DIN) CH-DIN is supplied in the 70x85 mm for- In the first case parameter 68 allows to de-
CH-DIN/P analogue inputs: 2 PTC mat (4 modules) for Din rail (Omega 3) or fine the type of regulation performed by the
probes for input water control and wall mount. machine at startup; the operation mode for
output water control circuit 1 and A range of numeric parameters allows in- the key can be selected through parame-
one 420 mA / 030 bar for strument configuration according to the ter 67.
pressure probes (condensation application. In case the ON-OFF remote input is set as
control circuit 1) active for the selection of the regulation
PTC probe display range: type (parameter 90 = 1, parameter 67 = 0
-50,099,9 C and parameter 68 = 2) the Mode front
Digital inputs: 6 ON/OFF inputs
for flow switch, circuit 1 fan thermal
system per, remote ONOFF,
maximum pressure switch circuit 1,
minimum pressure switch circuit 1
and compressr thermal magnetic
circuit 1
Power supply : 12 Vac 3VA

PLUS PRODUCT

The functions can also be


expanded through other elements
of the CH-DIN Microtech system:
the control modules for a second
compressor, the remote keyboards,
the fan control modules, and the
interface modules to install a
remote keyboard, the connection to
a local PC and to a remote PC.
key is ignored. pressor machine. The setpoint of the sec- circuit 1 condensation probe if the circuit 2
Displaying the state of the machine ond compressor (parameter 48) is not de- probe was declared as not present; in
resources fined as absolute value but as distance case both probes are present the one
The states key allows to access the dis- from the first compressors setpoint (the in- reading the lowest value shall be consid-
play phase for the state of resources. tervention differential is the one set for the ered.
By pressing the key the Indexes display first compressor in case of heating regu- Defrost is permitted only when the ma-
shows the codes related to resources (the lation - parameter 5). chine is in heating mode and its control is
Up and Down keys can be used to nav- Parameter 55 defines the sign of the enabled (parameter 84).
igate through the codes), while the compressor differential, i.e. the number of Defrost input
Values display shows the codes related active compressors when setpoint is To enable defrost the external exchanger
to the state of resources. reached (see parameter 55). probe (circuit 1 or circuit 2 condensation
For the meaning of codes related to re- Controlling compressors probe) shall have detected a temperature
sources and their states refer to table The thermal regulator controls power deliv- (pr pressure) lower than the defrost start
Codes for states and resources. ered by the compressor (or compressors, temperature (parameter 20) for a time
Operation time for the compressor in case the C2-DIN module is used) to ob- longer than the defrost calling time (para-
and the water pump tain the temperature value set by the User meter 22).
The instrument automatically stores the through parameters 02 ( cooling regula- Count starts only when the compressor in
hours the compressor (or the compres- tion ) and 03 ( heating regulation). the related circuit is working.
sors, in case module C2-DIN is being dri- Compressors are inserted according to If the probe in the external exchanger de-
ven) and the pump worked. the following concepts: tects a temperature (or a pressure) higher
When entering the resource status display a) the compressor with the lowest opera- than the defrost start temperature time
mode the display shows the values stored tion time is enabled; count is suspended, not zeroed.
(they shall be multiplied by 100 in case the b) in case of equal number of hours the The time count is zeroed after a defrost cy-
Hoursx100 led is turned on). compressor with the lowest safety time cle, when the operation mode is changed
During value display it is possible to reset shall be selected (parameters 49 and 50); at a new restart.
the values by simultaneously pressing keys c) in case of equal times priority is granted IMPORTANT
Up and Down. to compressor 1 (the one controlled by If defrost was enabled (parameter 84) the
Start and stop CH-DIN). defrost call time (parameter 22) shall not be
The instrument is turned on and off by Compressors are turned off according to set to 0.
pressing the On/Off key. the following logic: Control during defrost
In case no alarm conditions are present at a) the compressor with the most operating During defrost the inversion valve switches
startup, the display shows the value of the hours is disabled; to cooling mode.
PTC probe referring to water in circuit input b) in case of equal times priority is granted Fans are disabled and are restarted at the
1 (or of the condensation PTC probe for to compressor 1 (the one controlled by maximum speed when the temperature (or
circuit 1 in case of water-water machine CH-DIN). pressure) exceeds the quantity at fan start
and winter operation - parameter 1 = 5); The start and stop of compressor are de- in defrost (parameter 25).
in case the probe was declared as not termined by some time rules: In case of double compressor machines
present three dashes (- - -) will be dis- a) a time interval (set by parameter 49) shall with separate defrosts, when a compres-
played. elapse between the stop and the start of sor circuit enters defrost the thermoregula-
When the instrument is turned off the man- the same compressor; tor automatically balances it by activating
ual alarms will be reset. b) a time interval (set by parameter 50) the free compressor. If defrost is required
In case of power failure the instrument shall elapse between two subsequent also for the second compressor circuit, it
stores the type of regulation in progress starts of the same compressor; can take place after a delay from the end
and recovers it when power supply is re- c) a time interval (set by parameter 53) shall of the first defrost (set by parameter 24 -
stored. All timings in progress at power fail- elapse between the start of the first com- defrost interval between circuits).
ure are zeroed, including defrost which is pressor and the start of the second; In case of simultaneous defrost double
not restarted. d) a time interval (set by parameter 54) compressor machines both circuits enter
shall elapse between the stop of the first defrost simultaneously.
TEMPERATURE REGULATION compressor and the stop of the second; Anti frost resistors (see parameter 86) can
Setting the setpoint e) the activation of compressors is subject be enabled during defrost.
We shall analyse two cases related to set- to a delay from the water pump start which Exiting defrost
point setting: single compressor (CH-DIN can be selected through parameter 40; Defrost is exited when the end defrost
without C2-DIN) and double compressor f) when the machine is started the magne- temperature (or pressure) is reached (para-
(CH-DIN with C2-DIN) machine. to-thermal compressor alarm is delayed for meter 21). Once the defrost time-out is ex-
In case of single compressor machine the the time set through parameter 46. pired (parameter 23) the defrost end is
regulation setpoint is set through parame- forced even if the end defrost value has not
ters 02 (cooling) and 03 (heating) while CONTROLLING DEFROST been reached.
the intervention differential can be set General information Defrost can be interrupted if an alarm con-
through parameters 04 (cooling) and 05 CH-DIN can control single or double (using dition which is not compatible with its
(heating). C2-DIN) compressor machines. prosecution occurs.
Please note that the differential is meant In the former case the reference input is Defrost end always involves the stop of re-
over the setpoint: e.g. in case of heat- the condensation probe for circuit 1 con- lated compressors and therefore a delay in
ing regulation the off point is setpoint plus nected to CH-DIN. their activation (delay OFF-ON: parameter
half the value of the differential, while the In the latter case the reference input de- 49).
intervention point is setpoint less the value pends on the settings of parameter 66
of the differential. (separate-simultaneous defrosts). When WATER PUMP REGULATION
In case of double compressor machines defrosts are separate the reference for cir- Setpoint setting
the regulation setpoint for the first com- cuit 2 is the circuit 2 condensation probe The activation logic for the water pump
pressor and the related intervention connected to C2-DIN. In case of simulta- can be set through parameter 39; it can be
differential shall be set as for a single com- neous defrosts the reference input is the declared as absent or its continual opera-

CH-DIN(/P) 3/98 ing 2


tion can be selected or, more, a call activa- parameter 14 shall be lower than para- whenever fans are required to be con-
tion can be chosen (pump working when meter 6 and 6 shall be lower than 7; trolled by the sole input declared as pre-
compressor is ON, pump stopped when parameter 15 shall be greater than para- sent or by the more influent of the two (the
compressor is OFF). meter 8 and 8 shall be greater than9. one reading the higher value in case of
In any case, parameter 40 allows the defi- On-Off regulation cooling regulation, the one reading the
nition of a delay, in seconds, between the On-Off regulation involves operation of lower value in case of heating regulation).
pump start and the following compressor fans at the maximum speed or their stop. Fan synchrony
start so as to allow the water circuit to The temperature value related to stop is Parameter 89 determines whether fan ac-
reach its steady condition. Only in case of set through parameters 06 (cooling regu- tivation (in case of double compressor ma-
call activation will parameter 41 allow to lation) and 08 (heating regulation). The chines) shall be independent or synchro-
set a delay, in seconds, between the com- one related to start is set through parame- nised.
pressor stop and the pump stop so that ters 07 (cooling regulation) and 09 (heat- If an exchanger and an analogue input is
the machine is protected against physical ing regulation). related to each fan select option indepen-
stress due to sudden water shortage. This type of regulation requires to set para- dent fans.
meters 16, 17 and 38 (fan start at the max- Synchronised fans shall be selected
ANTI FROST RESISTORS imum speed, cut-off by-pass and phase whenever fans are required to be con-
REGULATION displacement times) to 0. The minimum trolled by the sole input declared as pre-
Anti frost resistors are enabled when the and maximum speed (parameters 12 and sent or by the more influent of the two (the
anti frost resistor setpoint is reached (para- 13) shall be set to 0 and 100 respectively. one reading the higher value in case of
meter 32) by one of the output water tem- By declaring regulation probes as not pre- cooling regulation, the one reading the
perature probes (circuits 1 and 2) or by the sent (parameters 76 and 77) a call opera- lower value in case of heating regulation).
circuit 2 condensation probe (only when tion for fans can be enabled: they shall Fan output linearization
parameter 86 = 2). start only when the compressor is enabled. Fan output linearization is available only in
The intervention differential for resistors IMPORTANT case proportional regulation (parameters
can be set through parameter 33. In case of On-Off regulation the following 10 and 11) is selected and fans operate in-
This regulation is enabled in ON, STAND- rules for parameters setting shall be re- dependently (parameter 89). It allows to
BY and virtual OFF states (see parameter spected: drive fans at the best even with displace-
90); it is not enabled in OFF state from key- parameter 14 shall be lower than para- ments between voltage and current that
board. meter 6; occur when a non purely ohmic load is
parameter 15 shall be greater than para- connected.
FAN REGULATION meter 8. To perform such linearization proceed as
General information Pickup at startup follows:
CH-DIN is provided with an output port to In case of proportional regulation the fans set temperature (or pressure) values cor-
control fans in circuit 1; fans in circuit 2 can start at the maximum speed can be se- responding to the minimum and maximum
be controlled through module C2-DIN, dri- lected (parameter 16); the pickup length speeds for fans (e.g. parameter 6 = 10 C
ven by CH-DIN. can be set through parameter 18. and parameter 7 = 20 C);
Two regulation types are provided (can be Please note that when the compressor is set the minimum and maximum speeds
set through parameters 10 and 11): phase started for the first time fans start at the for fans (e.g.: parameter 12 = 0 %, para-
cut proportional and On-Off. maximum speed meter 13 = 100 %);
Fans are controlled through special control Cut-off function set the cutoff temperature outside the
modules directly connected to CH-DIN In case of proportional regulation a tem- regulation band (e.g.: parameter 14 =
and C2-DIN: CF-05, CF-15 and CF-22 are perature (or pressure) can be selected so 5 C);
designed to drive single phase motors with that when it is reached fans are disabled to set parameter 38 (fan displacement) to 0;
maximum powers of 500, 1500 and 2200 prevent unnecessary thermal exchanges. start the machine in cooling mode (the
W respectively; CF-REL is designed to At machine start the cut-off function is sus- same operation can be performed when
control On-Off single phase motors. pended for a time set by parameter 17. the machine is in heating mode by set-
In case of double compressor machines The intervention differential of the cut-off ting the related parameters) and select the
the two outputs shall be configured for the function is one tenth of the modulation central band temperature for the regulation
same type of regulation. band, i.e. the difference between the mini- (in this case: 15 C);
Proportional regulation mum and the maximum speed. measure the voltage in parallel to the
This type of regulation provides fan speed Dependent or independent activation load and set this voltage to half the line
modulation between a minimum and a Parameter 19 determines whether fan ac- voltage modifying parameter 38 (fan dis-
maximum value that can be set as a per- tivation shall be dependent or independent placement).
centage of the maximum supply voltage from the compressor state. Now the fan displacement is set and other
through parameters 12 and 13. In case of dependent activation fans are parameters can be modified according to
The temperature value related to the mini- enabled, according to the regulation requirements.
mum speed can be set through parame- probes, only when the compressor is IMPORTANT
ters 06 (cooling regulation) and 08 (heat- working. In case of a mains frequency of 60 Hz ab-
ing regulation). The temperature related to If independent mode is selected, fan acti- normal situations might occur in fan con-
the maximum speed shall be set through vation shall be independent from the com- trol. Such situations can usually be solved
parameters 07 (cooling regulation) and pressor state. by setting a minimum speed (parameter
09 (heating regulation). Fan synchrony 12) below 10% and a maximum speed
The speed of fans is directly proportional to Parameter 89 determines whether fan ac- (parameter 13) below 90%.
the temperature in case of cooling regu- tivation (in case of double compressor ma- However in case of 60 Hz mains, it is ad-
lation, inversely proportional in case of chines) shall be independent or synchro- visable to check correct fan operation as
heating regulation. nised. different adjustments according to the type
IMPORTANT If an exchanger and an analogue input is of motor used might be necessary.
In case of proportional regulation the fol- related to each fan select option indepen- Fan voltage limitation
lowing rules on parameter settings shall be dent fans. If the maximum fan speed shall be limited
respected: Synchronised fans shall be selected due to the line voltage exceeding the max-

3 CH-DIN(/P) 3/98 ing


imum allowed operate on parameter 13 to CODES FOR STATES AND RESOURCES
set a maximum driving voltage equal to the
Resource code Resource State code Meaning
voltage for fans (e.g. on a 230 Vac network
set parameter 13 = 96 to use fans original- 01 compressor 1 01 summer operation
ly designed for a 220 Vac supply). 02 winter operation
03 operating on defrost
COMMANDS ON FRONT PANEL
Value Display 04 timing in progress
It is the 3 digit plus - sign display located 06 not active
on the left of the front panel. It shows the 02 hours compressor 1 valore operating hours (since last reset)
values of parameters and resource condi-
03 fans circuit 1 01 operating
tions, the error codes and the temperature
measured by the water probe temperature 02 off for defrost in progress
in circuit 1 input and condensation (con- 04 timing in progress
densation only when parameter 01 = 5 and
06 not active
heating regulation selected).
Index Display 04 defrost circuit 1 --- not enabled (parameter 84)
It is the 2 digit display located on the right 01 in progress
of the front panel. It shows the numeric 02 security count compressor 1
code (parameter or state) to which the val-
ue shown by the Value display refers. 03 defrost time count
Hoursx100 led 04 delay in defrost in progress
This Led is located on the top left of the 06 not active
Value display. When on it indicates the
05 fans output circuit 1 number from 0 to 100%
value of hours of operation for compres-
sors displayed by Value display shall be 21 compressor 2 --- not present
multiplied by 100. 01 summer operation
Heating Led 02 winter operation
When on indicates the instrument is oper-
ating in heating mode. 03 operating on defrost
Cooling Led 04 timing in progress
When on indicates the instrument is oper- 06 not active
ating in cooling mode.
22 hours compressor 2 --- not present
Menu led
When on indicates the Menu key has operating hours (since last reset)
been pressed and parameters program- 23 fans circuit 2 --- not present
ming mode has been entered. 01 operating
Comp Led
When on indicates the compressor in cir- 02 off for defrost in progress
cuit 1 is active; when blinking indicates 04 timing in progress
temporization in progress. 06 not active
Status Led
24 defrost circuit 2 --- not enabled (parameter 84)
When on indicates the Status key has
been pressed and resource state display 01 in progress
mode has been entered. 02 security count compressor 2
Alarm Led
03 defrost time count
When on indicates alarm condition in
progress. 04 delay in defrost in progress
Line Led 06 not active
When on indicates the instrument is pow- 25 fans output circuit 1 --- not present
ered.
valore power supplied (value from 0 to 100%)
Up and Down keys
Keys used to increase values shown by 40 temperature probe --- not present
displays Index and Value. When valore value in tenth of degree
pressed simultaneously they reset the op-
On closed input
eration hours for compressors and pump
(only when displayed). Off open input
Mode Key ERR error in probe
Allows to select the regulation type for the 41 On-Off remote input --- not present
instrument (see parameters 67 and 68).
On closed input
Menu key
Allows to enter parameters programming Off open input
mode and exit it 42 output water temperature --- not present
Set key
probe in circuit 1 valore value in tenth of degree
In parameters programming mode it allows
to select either Index or Value display On closed input
mode. Off open input
Status key ERR error in probe
Allows to display the state of the machine
resources. In parameters programming

CH-DIN(/P) 3/98 ing 4


CODES FOR STATES AND RESOURCES ters available in CH-DIN (including para-
meters accessible via PC only); please re-
Resource code Resource State code Meaning
fer to the parameters table for their rela-
43 output water temperature --- not present tionship with the correspondent access
probe in circuit 2 value value in tenth of degree level.
01 machine configuration
On closed input
Allows the selection of the machine type to
Off open input be controlled.
ERR error in probe The correct setting of this parameter, while
44 condensation input --- not present influencing keyboard and resource man-
agement, does not exclude a proper set-
circuit 1 valore value in tenths of degree
ting for all other machine regulation para-
ERR error in probe meters.
45 condensation input --- not present 00 = air-water chiller;
01 = water-water chiller;
circuit 2 valore value in tenths of degree
02 = air-water heat pump without defrost;
ERR error in probe 03 = air-water heat pump with defrost;
46 water pump --- not present 04 = water-water heat pump with gas in-
01 working
version;
05 = water-water heat pump with external
06 not active manual inversion;
47 water pump hours --- not present 06 = air-air pump with or without inversion.
hours of operation (since last reset) 02 cooling regulation setpoint
It is the temperature above which com-
48 anti frost resistors --- not present
pressors are enabled in case of summer
01 active operation
06 not active 03 heating regulation setpoint
49 resource code not used --- state code not used
It is the temperature below which com-
pressors are enabled in case of winter
operation.
mode brings the parameters of the second selected one ( Value display active); when 04 cooling regulation differential
display level to the first display level. both displays blink the parameter is out of It allows to select the intervention differen-
On/Off key range and cannot be stored. tial (over the setpoint) in case of summer
Allows to turn the instrument ON and OFF; To exit parameters programming mode operation (see Temperature regulation
the key is enabled also in case the remote press key Menu; in case of changes in section).
selection of ON and VIRTUAL OFF states parameters values the power supply shall 05 heating regulation differential
are enabled (parameter 90 = 2). be disconnected to store the set values Allows to select the intervention differential
properly. (over the setpoint) for winter operation
PARAMETERS PROGRAMMING Accessing second level parameters (see Temperature regulation section).
For ease of use and safety reasons three Second level parameters can be accessed 06 temperature (or pressure) for mini-
different parameters access levels (dis- by accessing first level parameters and mum speed in cooling regulation
play/change) are provided. then entering the correct password into Allows to select the temperature (or pres-
The first access level, the easiest, is suit- parameter 92. sure) below which fans operate at the min-
able for parameters that shall be frequent- Once the password has been entered, imum speed.
ly displayed/changed. press the Set key until the Index display 07 temperature (or pressure) for max-
The second level involves a password; it is starts blinking; now also second level pa- imum speed in cooling regulation
therefore suitable for parameters that shall rameters are accessible and can be modi- Allows to select the temperature (or pres-
not be modified without the Servicing sup- fied. When the Led in the lower part of the sure) above which fans operate at the
port. left digit in the Index display is on it con- maximum speed.
The third level involves the use of a firms the currently displayed parameter be- 08 temperature (or pressure) for mini-
Personal computer connected to the in- longs to the first level menu. mum speed in heating regulation
strument through special interface mod- A second level parameter can be brought temperature
ules; this level is usually reserved to the to first level; once the parameter to be Allows to select the temperature (or pres-
manufacturers and allows to access all pa- modified has been selected press the sure) above which fans operate at the min-
rameters and set the access level for each Status until the Led in the lower part of imum speed.
one of them. the left digit in the Index display is turned 09 temperature (or pressure) for max-
Accessing first level parameters on. The opposite operation (from the first imum speed in heating regulation
First level parameters can be accessed by to the second level) can only be achieved temperature
pressing the Menu key: the Index dis- via PC programming. Allows to select the temperature (or pres-
play shows the label of the first parameter In second level parameter programming sure) below which fans operate at the
(01), the Value display shows the relat- also third level parameters can be dis- maximum speed
ed value. played but they cannot be modified. 10 fan output type circuit 1
The Set key can be used to skip from Accessing third level parameters Allows to select the output regulation type
one display to the other, i.e. from the se- Third level parameters can only be ac- for circuit 1 fan control.
lection of the parameters to be dis- cessed through an IBM compatible PC 0 = proportional output 0220 Vac (fan
played/modified to its actual change; the once the special Microtech software has modules CF-05/15/22 only);
currently selected display blinks. been installed. 1 = ON/OFF output (fan module CF-REL
The Up and Down keys can be used to only);
browse parameters ( Index display ac- PARAMETERS DESCRIPTION 2 = disabled output.
tive) or change the value of the currently Hereunder is a description for all parame- 11 fan output type circuit 2 (C2-DIN

5 CH-DIN(/P) 3/98 ing


Allows to select the output regulation type It is the temperature (or pressure) above It allows to set a delay in flow switch alarm
for circuit 2 fan control. (set to 2 in case of which the start function for fans at maxi- deactivation, in order to avoid transients
single compressor machine). mum speed during defrost is enabled due to non constant flow.
0 = proportional output 0220 Vac (fan 26 anti frost alarm setpoint 44 restore mode for compressor ther-
modules CF-05/15/22 only); It is the temperature below which the anti mal magnetic alarm
1 = ON/OFF output(fan module CF-REL frost alarm is enabled. 0 = automatic restore;
only); 27 anti frost alarm differential 1 = manual restore (instrument start/stop
2 = disabled output. Allows to select the intervention differential through the on/off-reset key).
12 minimum fan speed for the anti frost alarm. 45 restore mode for fan thermal
Allows to select the supply voltage for fans 28 anti frost alarm restore mode alarm
corresponding to their minimum speed. 0 = automatic restore; 0 = automatic restore;
Expressed in percentage, from 0 to 100%, 1 = manual restore (instrument on/off 1 = manual restore (instrument start/stop
of the maximum allowed speed. through the on/off-reset key). through the on/off-reset key).
13 fan maximum speed 29 anti frost alarm configuration by- 46 by-pass time for the compressor
Allows to select the supply voltage for fans pass thermal magnetic alarm
corresponding to their maximum speed. Allows to set the activation mode for the Allows to set a delay in the activation of the
Expressed in percentage, from 0 to 100%, anti frost alarm by-pass. compressor thermal magnetic alarm at
of the maximum allowed speed. 0 = not active; machine startup. In tens of seconds.
14 cooling regulation cut-off set- 1 = active in case of heating regulation; 47 measurement unit
point 2 = active in case of cooling regulation; Allows to select the measurement unit for
Temperature (or pressure) below which 3 = always active temperature display. Please note that the
fans are disabled to prevent unnecessary 30 not used instrument does not automatically re-cal-
heat exchanges. 31 by-pass time for anti frost alarm culate the values of previously set parame-
15 heating regulation cut-off set- Allows to set a delay in the anti frost alarm ters.
point activation at machine start. In seconds. 0 = Celsius grades;
Temperature (or pressure) above which 32 anti frost resistors setpoint 1 = Fahrenheit grades.
fans are disabled to prevent unnecessary It is the temperature below which anti frost 48 intervention temperature differen-
heat exchanges. resistors are enabled. tial for the second compressor
16 fans start at maximum speed 33 anti frost resistors differential Allows to define the temperature differen-
Allows to select fans startup at the maxi- Allows to select the intervention differential tial between the activation of the first and
mum speed. for the anti frost resistors the second compressor. In case of single
0 = restart without pickup; 3437 not used compressor machine it shall be set to 0
1 = restart with pickup. 38 fans displacement (see section Temperature regulation).
17 cut-off by-pass time Allows to set a delay through which the dif- 49 OFF-ON delay
Allows to select a delay in the activation of ferent electrical features of the fan motors Minimum stop time for a compressor after
the cut-off function activation at fans start- are compensated. Operates on both the it is turned off. In tens of seconds.
up. In seconds. fan outputs. 50 ON-ON delay
18 fan pickup time 39 water pump activation logic Minimum time between two subsequent
Allows to select the length of the fan start Allows to set the activation logic for the starts of the same compressor. In tens of
pickup. In seconds. water pump. seconds.
19 fan start logic 0 = pump not present; 51 minimum pressure alarm by-pass
Allows to select the logic for fan start. 1 = continual operation (pump always op- time (winter operation)
0 = dependent activation (fans enabled ac- erating); It allows to set a delay in the activation of
cording to the regulation probes only for 2 = call activation (water pump working the minimum pressure alarm at compres-
compressor ON, fans always disabled for when compressor ON, water pump idle sor start (heating regulation only).
compressor OFF); when compressor OFF). Expressed in seconds.
1 = independent activation (according to 40 delay in the activation of pump- 52 minimum pressure alarm by-pass
regulation probes only). compressor time (summer operation)
20 temperature (or pressure) for de- Allows to set a delay between the pump It allows to set a delay in the activation of
frost start and the compressor starts to allow the wa- the minimum pressure alarm at compres-
la temperature (or pressure) below which ter circuit to reach steady condition. In sor start or when entering defrost (cool-
the defrost cycle is started. seconds ing regulation only). Expressed in sec-
21 temperature (or pressure) for de- 41 delay in compressor-pump dis- onds.
frost end abling 53 time interval between the inter-
It is the temperature (or pressure) above Allows to set a delay between the stop of ventions of the first and the second
which defrost ends. the compressor and the pump so as to compressor
22 defrost call time preserve the machine from physical stress Allows to define the time interval between
It is the permanence time of the conden- due to the sudden shortage of water (only the activation of the first and the second
sation probe below the temperature (or when parameter 39 = 2). In seconds. compressor. In case of single compressor
pressure) for defrost start to start the de- 42 flow switch alarm by-pass time machine it shall be set to 0. Expressed in
frost cycle. In minutes. from pump activation seconds.
23 defrost time-out Allows to set a delay in the activation of the 54 time interval between the stops of
It is the maximum time for defrost. In min- flow switch alarm which starts from the ac- the first and the second compressor
utes. tivation of the water pump, in addition to Allows to define the time interval between
24 defrost interval between circuits the one starting from input opening (see the stop of the first and the second com-
Allows to set the interval between the de- parameter 70); this allows the water circuit pressor. In case of single compressor ma-
frost end for a circuit and the defrost start to reach a constant flow condition. chine it shall be set to 0. Expressed in sec-
for the other. In minutes. Expressed in seconds. onds.
25 temperature (or pressure) for fan 43 by-pass time for flow switch alarm 55 compressors active when setpoint
start in defrost restore is reached

CH-DIN(/P) 3/98 ing 6


Allows to set the number of active com- stand-by state (only for parameter 68 = C2-DIN/P).
pressors when the regulation setpoint is 2); 78, 79, 80 probe calibration referred
reached. In case of single compressor ma- 1 = toggle function (heating, cooling to parameters 72, 73, 74 respectively
chine it shall be set to 0 (see Temperature and stand-by state regulations selection). These parameters allow to compensate
regulation section). 68 configuration at machine startup the error that might occur between the real
0 = single compressor machine; Allows to define the state of machine at temperature and the value read by the
1 = only one compressor active (the value startup. probes. The correction is performed by in-
for parameter 48 is considered as negative 0 = cooling regulation; putting a value equal to the error detected,
referred to the setpoint in case of winter 1 = heating regulations; but with opposite sign.
operation and positive in case of summer 2 = stand-by state. 81 not used
operation); 69 not used 82, 83 probe calibration referred to
2 = two active compressors (the value for 70 flow switch alarm by-pass time parameters 76 and 77 respectively
parameter 48 is considered as positive re- when the related input is opened. These parameters allow to compensate
ferred to the setpoint in case of winter It allows to set a delay in the activation of the error that might occur between the real
operation and negative in case of sum- the flow switch alarm from the opening of temperature and the value read by the
mer operation). the related input. Value expressed in sec- probes. The correction is performed by in-
56 compressor presence circuit 1 onds. putting a value equal to the error detected,
Allows to set the presence of the com- Please note that the activation of this alarm but with opposite sign.
pressor in the first circuit. is also subject to a by-pass time from the 84 defrost enable
0 = compressor absent; activation of the water pump (see parame- Allows to enable or disable the start of de-
1 = compressor present. ter 42). frost cycles.
57 compressor presence circuit 2 71 not used (set to 0) 0 = defrost disabled;
Allows to set the presence of the com- 72 input water PTC probe input con- 1 = defrost enabled.
pressor in the second circuit. figuration 85 presence of anti frost resistors
0 = compressor absent; Allows to configure the input of the input Allows to set the presence of anti frost re-
1 = compressor present. water PTC probe. sistors.
58 cooling regulation setpoint mini- 0 = probe absent; 0 = resistors absent;
mum limit 1 = digital input (for the control of motor 1 = resistors present.
Allows to set the minimum limit for setpoint condensing machines only); 86 configuration for anti frost resis-
in summer operation 2 = analogue input (PTC probe). tors controller circuits 1 (CH-DIN) and
59 cooling regulation setpoint max- 73 output water PTC probe input 2 (C2-DIN)
imum limit configuration circuit 1 Allows to define the activation mode for the
Allows to set the maximum limit for set- Allows to configure the input of the output anti frost resistors.
point in summer operation. water PTC probe in circuit 1. 0 = thermally controlled operation with reg-
60 heating regulation setpoint mini- 0 = probe absent; ulation on the output probe circ. 1 and on
mum limit 1 = digital input (for the control of motor the output water probe 2 of C2-DIN;
Allows to set the minimum limit for setpoint condensing machines only); 1 = thermally controlled operation with reg-
in winter operation. 2 = analogue input (PTC probe). ulation on the output water probe circ. 1
61 heating regulation setpoint max- 74 output water PTC probe input and on the output water probe 2 of C2-
imum limit configuration circuit 2 (C2-DIN) DIN - always On during defrost;
Allows to set the maximum limit for set- Allows to configure the input of the output 2 = thermally controlled operation (even
point in winter operation. water PTC probe in the circuit 2 on mod- during defrost) with regulation on the out-
62 minimum limit for anti frost alarm ule C2-DIN. In case of single compressor put probe circ. 1 and on the output water
Allows to set the minimum limit for the anti machine it shall be set to 0. and condensation probes of circuit 2 (C2-
frost alarm. 0 = probe absent; DIN; usually in case of water-water ma-
63 maximum limit for anti frost alarm 1 = digital input (for the control of motor chines with gas inversion).
Allows to set the maximum limit for the anti condensing machines only); 87 maximum pressure alarm restore
frost alarm. 2 = analogue input (PTC probe; not selec- mode
64 inversion valve presence table in case module C2-DIN/12/ID220 is 0 = automatic restore;
Allows to set the presence of the inversion used). 1 = manual restore (instrument stop/restart
valve. 75 not used (set to 0) through the on/off-reset key).
0 = valve absent; 76 input configuration for condensa- 88 minimum pressure alarm restore
1 = valve present. tion probe circuit 1 mode
65 inversion valve configuration Allows to configure the condensation 0 = automatic restore;
Allows to define whether the valve is active probe input circuit 1. 1 = manual restore (instrument stop/restart
in case of winter or summer operation. 0 = probe absent; through the on/off-reset key).
0 = relay ON for cooling regulation;. 1 = digital input (not selectable); 89 fan synchronism
1 = relay ON for heating regulation. 2 = analogue input (PTC probe in the CH- Allows to define whether the fan activation
66 separate-simultaneous defrosts DIN or input 420 mA / 030 bar in the (in case of double compressor machines)
Allows to define whether the defrosts in the CH-DIN/P). shall be independent or synchronised (set
two circuits shall be simultaneous or sepa- 77 input configuration for condensa- to 0 in case of single compressor ma-
rated by a time interval (which can be set tion probe circuit 2 chines).
through parameter 24). In case of single Allows to configure the condensation 0 = independent fans; an exchanger and
compressor machine it shall be set to 0. probe input circuit 2 on the C2-DIN mod- an analogue input is related to each fan in
0 = separate defrosts; ule. In case of single compressor machine the machine..
1 = simultaneous defrosts. it shall be set to 0. 1 = synchronised fans; the fans are con-
67 mode key configuration 0 = probe absent; trolled by the only input declared as pre-
Allows to define the operation mode for the 1 = digital input (not selectable); sent or by the more influent between the
mode front key. 2 = analogue input (PTC probe in the C2- two (the one reading the highest value in
0 = cooling regulation selected and DIN or input 420 mA / 030 bar in the case of cooling regulation, the one read-

7 CH-DIN(/P) 3/98 ing


DEFAULT VALUES AND PARAMETERS ACCESSIBILITY FOR STANDARD MODELS
Parameter Description Range Default Unit Accessibility
01 machine configuration 05 3 number PC
02 cooling regulation setpoint p. 58p. 59 20 C/10 1st level
03 heating regulation setpoint p. 60p. 61 400 C/10 2nd level
04 cooling regulation differential 0126 10 C/10 1st level
05 heating regulation differential 0126 20 C/10 2nd level
06 cooling minimum speed temp. (press) 0126 (030) 30 C (bar) 2nd level
07 cooling maximum speed temp. (press) 0126 (030) 40 C (bar) 2nd level
08 heating minimum speed temp. (press) 0126 (030) 10 C (bar) 2nd level
09 heating maximum speed temp. (press) 0126 (030) 7 C (bar) 2nd level
10 circuit 1 fan output type 02 0 number PC
11 circuit 2 fan output type (C2-DIN) 02 2 number PC
12 minimum fan speed 0100 45 max % 2nd level
13 maximum fan speed 0100 100 max % 2nd level
14 cooling regulation cut-off setpoint 0126 (030) 25 C (bar) 2nd level
15 heating regulation cut-off setpoint 0126 (030) 13 C (bar) 2nd level
16 fan start at maximum speed 0/1 1 flag 2nd level
17 cut-off by-pass time 0126 10 seconds 2nd level
18 fans pickup time 0126 3 seconds PC
19 fans activation logic 0/1 0 flag PC
20 defrost start temperature (pressure) -280500 (0300) -50 C/10 (bar/10) 2nd level
21 defrost end temperature (pressure) -280500 (0300) 295 C/10 (bar/10) 2nd level
22 defrost call time 0126 20 minutes 2nd level
23 defrost time-out 0126 8 minutes 2nd level
24 defrost interval between circuits 0126 0 minutes PC
25 fans start temp. (press.) in defrost 0126 (030) 29 C (bar) 2nd level
26 anti frost alarm setpoint p. 62p. 63 20 C/10 1st level
27 anti frost alarm differential 0126 20 C/10 2nd level
28 anti frost alarm restore mode 0/1 0 flag 2nd level
29 anti frost alarm by-pass configuration 0..3 0 number PC
30 not used PC
31 anti frost alarm by-pass time 0255 240 seconds 2nd level
32 anti frost resistors setpoint -280500 20 C/10 2nd level
33 anti frost resistors differential 0126 10 C/10 2nd level
3437 not used PC
38 fans phase displacement 0126 8 number 2nd level
39 water pump activation logic 02 1 number PC
40 pump-compressor activation delay 0126 0 seconds PC
41 pump-compressor de-activation delay 0126 5 seconds 2nd level
42 flow switch by-pass time at pump start 0126 0 seconds PC
43 flow switch alarm restore by-pass time 0126 0 seconds PC
44 compressor thermal magnetic alarm restore mode 0/1 0 flag 2nd level
45 fan thermal alarm restore mode 0/1 0 flag 2nd level
46 compressor thermal magnetic alarm by-pass time 0126 10 seconds x 10 PC
47 measurement unit 0/1 0 flag 2nd level
48 second compressor intervention differential 0126 0 C/10 PC
49 OFF-ON delay 0126 0 seconds x 10 PC
50 ON-ON delay 0126 0 seconds x 10 2nd level
51 minimum press. Alarm by-pass time (heating) 0255 0 seconds 2nd level
52 minimum press. Alarm by-pass time (cooling) 0255 0 seconds 2nd level
53 first and second compressor intervention interval 0126 0 seconds PC
54 first and second compressor shutdown interval 0126 0 seconds PC
55 active compressors when setpoint is reached 02 0 number PC

CH-DIN(/P) 3/98 ing 8


DEFAULT VALUES AND PARAMETERS ACCESSIBILITY FOR STANDARD MODELS
Parameter Description Range Default Unit Accessibility
56 circuit 1 compressor presence 02 1 number PC
57 circuit 2 compressor presence 02 0 number PC
58 setpoint minimum limit cooling regulation -20p. 2 -5 C 2nd level
59 setpoint maximum limit cooling regulation p. 260 20 C 2nd level
60 setpoint minimum limit heating regulation -10p. 3 25 C 2nd level
61 setpoint maximum limit heating regulation p. 360 45 C 2nd level
62 setpoint minimum limit for anti frost alarm -28p. 26 -10 C 2nd level
63 setpoint maximum limit for anti frost alarm p. 2660 10 C 2nd level
64 inversion valve presence 0/1 1 flag PC
65 inversion valve configuration 0/1 0 flag PC
66 separate-simultaneous defrosts 0/1 1 flag PC
67 mode key configuration 0/1 1 flag PC
68 machine start configuration 02 2 number 2nd level
69 not used PC
70 flow switch alarm by-pass time since input opening 0126 1 seconds PC
71 not used leave at 0 PC
72 PTC probe input configuration for input water 02 2 number PC
73 PTC probe input configuration for output water circ. 1 02 2 number PC
74 PTC probe input configuration for output water circ. 2 02 0 number PC
75 not used leave at 0 PC
76 condensation probe input configuration circuit 1 02 2 number PC
77 condensation probe input configuration circuit 2 02 0 number PC
7879 probes calibration as for parameters 72 and 73 -100100 0 C/10 2nd level
80 probe calibration as for parameter 74 -100100 0 C/10 PC
81 not used PC
82 probe calibration as for parameter 76 -100100 0 C/10 (bar/10) 2nd level
83 probe calibration as for parameter 77 -100100 0 C/10 (bar/10) PC
84 defrost enable 0/1 1 flag PC
85 anti frost resistors presence 0/1 0 flag PC
86 conf. for circuits 1 and 2 anti frost resistors regulator 02 1 number PC
87 restore mode maximum pressure alarm 0/1 0 flag 2nd level
88 restore mode minimum pressure alarm 0/1 0 flag 2nd level
89 fans synchrony 02 0 number PC
90 remote ON-OFF input 02 2 number 2nd level
91 not used PC
92 password 0..126 0 number 1st level
93 not used always visible

ing the lowest value in case of heating 93 not used 2.5 mm2 wires for the connection to fans
regulation). Access to this parameters cannot be mod- modules, a screw terminal block for 1
90 ON-OFF remote input ified. mm2 wires for alarm output and digital in-
Allows to configure the operation mode for puts for flow switch, fan thermal control
the remote ON-OFF input. INSTALLATION circuit 1 and ONOFF (remote), and Faston
0 = input not used; CH-DIN is designed for wall (extractable 6.3 mm terminal block for other connec-
1 = heating (when close) and cooling brackets) or Din rail (Omega 3) mount. tions.
(when open, for parameters 68 = 2 and 67 The operating temperature range for cor- Check the supply voltage complies with
= 0 only) regulations selection; rect operation is between -5 and 60 C; do what required by the instrument. If the CH-
2 = remote selection for ON (when close) - not install the instrument in moist and/or DIN module is used in a three phase sys-
virtual OFF (when open; outputs for com- dirty places. tem the phase powering the instrument
pressor, fans and pump are disabled as shall be different from the one supplying
well as the displaying of error message ELECTRICAL WIRING loads.
E00) states. CH-DIN is provided with a telephone con- In case the fan module is used the phase
91 not used nector for the connection to the TS-DIN/S powering it shall be the same as the one
92 password keyboard or to interface modules, a comb powering the CH-DIN module.
Allows to input the access password for connector for the connection to the C2- The three PTC probes (two in CH-DIN/P)
second level parameters (its value is 47). DIN module, a screw terminal block for do not require polarised insertion and can

9 CH-DIN(/P) 3/98 ing


be lengthened using a standard bipolar ca- fans in circuit 1 (fans remain active in case the fans and the fans in circuit 1 (in circuit
ble. CE regulations states that low voltage synchronised activation is selected 2 too in case fan synchronised activation is
signals (probe cables, digital inputs and through parameter 89), turns the Alarm selected through parameter 89), turns the
connections to expansion modules) shall led on and enables output SSR 1248 Alarm led on and enables output SSR
be kept far from power cables (compres- Vac. 1248 Vac. Relay outputs are not dis-
sor control cables, resistors, etc.). Restore mode can be selected through abled in case of cooling regulation and
The probes should be fixed so that the ca- parameter 88. when the water-water pump is configured
ble exits downward to prevent liquid E03 compressor alarm circuit 1 with external manual inversion (parameter
spilling into the metallic bulb containing the Code E03 appears when the digital input 1 = 5).
sensor. for the compressor thermal magnetic sys- Check connections before replacing the
The compressor relay output is free from tem in circuit 1 is opened. probe.
voltage and can drive a direct load up to 1 This alarm disables the compressor in cir- E21 maximum pressure alarm circuit
Hp at 220 Vac (please note the common cuit 1, turns the Alarm led on and en- 2 (C2-DIN)
terminal of relays - terminal 22 - can bear a ables output SSR 1248 Vac. Code E21 appears when opening the dig-
maximum load of 4.5A). For heavier loads Restore mode can be selected through ital input for the maximum pressure switch
use a suitable contactor. parameter 44. in circuit 2 provided by module C2-DIN.
At startup the alarm is subject to a delay This alarm disables the compressor in cir-
ERROR SIGNALS whose length can be selected through pa- cuit 1, turns the Alarm led on and en-
The presence of an error condition is indi- rameter 46. In case of activation request ables output SSR 1248 Vac.
cated by the related Led and the display of for the compressor during such delay the Restore mode can be selected through
the relevant code on the Value display. compressor does not start if the alarm is parameter 87.
In case of error signal a partial or total present and the related led blinks. E22 minimum pressure alarm circuit
block of users takes place together with E04 fan alarm circuit 1 2 (C2-DIN)
the activation of special output SSR Code E04 appears when the digital input Code E22 appears when opening the dig-
1248 Vac. for the fan thermal magnetic system in cir- ital input for the minimum pressure switch
In case of automatic restore alarm the re- cuit 1 is opened. in circuit 2 provided by module C2-DIN.
moval of the event causing the alarm de- This alarm disables the compressor and This alarm disables the compressor and
termines immediate restart of normal oper- the fans in circuit 1 (in circuit 2 too in case the fans in circuit 2 (fans remain active in
ation of the instrument and the connected fan synchronised activation is selected case synchronised activation is selected
machine. In case of manual restore alarm through parameter 89), turns the Alarm through parameter 89), turns the Alarm
the alarm condition and the block of users led on and enables output SSR 1248 led on and enables output SSR 1248
remain after the cause of the alarm has Vac. Vac.
been removed; normal operation can be Restore mode can be selected through Restore mode can be selected through
restored only by turning the instrument off parameter 45. parameter 88.
and then on using the On/Off front key. E05 anti frost alarm circuit 1 E23 compressor alarm circuit 2
For some alarms (anti-frost, thermal-mag- Code E05 appears when the anti frost Code E23 appears when opening the dig-
netic compressor, minimum and maximum alarm setpoint (parameter 26) is reached in ital input for the compressor thermal mag-
pressures) it is possible to select the re- the output water temperature probe in cir- netic system in circuit 2 provided by mod-
store mode through parameters; for others cuit 1. ule C2-DIN.
(anti-frost, thermal magnetic compressor This alarm disables the compressor and This alarm disables the compressor in cir-
and minimum pressure) it is possible to set the fans, turns the Alarm led on and en- cuit 2, turns the Comp. al led (in the C2-
a by-pass time at startup. ables output SSR 1248 Vac. DIN module) on and enables output SSR
E00 virtual OFF alarm selection The intervention differential can be set 1248 Vac.
Code E00 appears in case the virtual OFF through parameter 27. Restore mode can Restore mode can be selected through
state is selected, i.e. when the remote ON- be selected through parameter 28. parameter 44.
OFF input is opened with parameter 90 = E06 output water temperature PTC At startup the alarm is subject to a delay
2. probe alarm in circuit 1 whose length can be selected through pa-
This alarm disables compressor, fan and Code E06 appears in case of shorted, dis- rameter 46. In case of activation request
pump alarms. The pump goes off after the connected or interrupted probe. for the compressor during such delay the
parameter 41 delay. The same message appears in case of compressor does not start if the alarm is
NOTE under range, i.e. in case the lower display present and the related led blinks.
When error code E00 is displayed the limit is exceeded or in case of over range, E24 fan alarm circuit 2
Alarm led is not turned on and the SSR i.e. in case the upper display limit is ex- Code E24 appears when opening the dig-
1248 Vac output is not enabled ceeded. ital input for the fan thermal magnetic sys-
E01 maximum pressure alarm cir- This alarm disables the compressor and tem in circuit 2 provided by module C2-
cuit 1 the fans and the fans in circuit 1, turns the DIN.
Code E01 appears when the digital input Alarm led on and enables output SSR This alarm disables the compressor and
for the maximum pressure switch in circuit 1248 Vac. the fans in circuit 2 (in circuit 1 too in case
1 is opened. Check connections before replacing the fan synchronised activation is selected
This alarm disables the compressor in cir- probe. through parameter 89), turns the Fan Al.
cuit 1, lights the Alarm led and enables E07 PTC condensation probe in cir- led (in module C2-DIN) on and enables
the special SSR 1248 Vac output. cuit 1 output SSR 1248 Vac.
Restore mode can be selected through Code E07 appears in case of shorted, dis- Restore mode can be selected through
parameter 87. connected or interrupted probe. parameter 45.
E02 minimum pressure alarm in cir- The same message appears in case of E25 anti-frost alarm circuit 2 (output
cuit 1 under range, i.e. in case the lower display water temperature probe)
Code E02 appears when the digital input limit is exceeded or in case of over range, Code E25 appears when the anti frost
for the minimum pressure switch in circuit i.e. in case the upper display limit is ex- alarm setpoint (parameter 26) is reached in
1 is opened. ceeded. the output water temperature probe in cir-
This alarm disables the compressor and This alarm disables the compressor and cuit 2.

CH-DIN(/P) 3/98 ing 10


CONNECTIONS

magneto-thermal switch

circuit 1 condenser input


circuit 1 outgoing water

magneto-thermal switch

circuit 1 outgoing water


circuit 1 high pressure
circuit 1 low pressure

circuit 1 high pressure


circuit 1 compressor

circuit 1 low pressure

420 mA / 030 bar


circuit 1 compressor
circuit 1 condenser

ingoing water

ingoing water
PTC probe

PTC probe

PTC probe

PTC probe

PTC probe
switch

switch

switch

switch
12 Vdc output

420 mA input
12 11 10 9 8 7 6 5 4 3 2 1 12 11 10 9 8 7 6 5 4 3 2 1
to the circuit 1 fans control module to the circuit 1 fans control module
C2-DIN mod.

CH-DIN

C2-DIN mod.
CH-DIN/P
to

to
SSR TTL ser. line
alarm TTL ser. line
to TS-DIN/S
alarm output keyboard SSR output
to TS-DIN/S
keyboard
or to interf.
or to interf.
modules
modules

25 24 23 22 21 20 19 18 17 16 15 14 13 25 24 23 22 21 20 19 18 17 16 15 14 13

circuit 1 anti- circuit 1 anti-


remote ON-OFF
circ. 1 fans th. switch
1248 Vac

flow switch

reversing freeze

circ. 1 fans th. switch


1248 Vac

remote ON-OFF

flow switch
reversing freeze
valve heater valve heater

circ. 1 water circ. 1 water


comp. pump comp. pump

POWER POWER
POWER POWER
SUPPLY SUPPLY
SUPPLY SUPPLY

This alarm disables the compressor and through parameter 89), turns the Alarm have been working for a time selectable
the fans, turns the Alarm led on and en- led on and enables output SSR 1248 through parameter 42.
ables output SSR 1248 Vac. Vac. This alarm disables the compressors and
The intervention differential can be set Check connections before replacing the the fans and turns the Alarm led on.
through parameter 27. Restore mode can probe. Restore is automatic.
be selected through parameter 28. E28 parameter 75 alarm Alarm stop is subject to a delay whose
E26 output water temperature PTC Code E28 appears in case of wrong set- length can be set through parameter 43.
probe alarm in circuit 2 (C2-DIN) ting for parameter 75 (its value shall be set E42 hardware failure alarm
Code E26 appears in case of shorted, dis- to 0). Code E42 appears in case of wrong con-
connected or interrupted probe. E40 input water temperature PTC nection between CH-DIN and C2-DIN.
The same message appears in case of probe alarm Check the connections between the mod-
under range, i.e. in case the lower display Code E40 appears in case of shorted, dis- ules and in case the error persists call the
limit is exceeded or in case of over range, connected or interrupted probe. Service Centre.
i.e. in case the upper display limit is ex- The same message appears in case of E43 anti frost alarm circuit 2 (con-
ceeded. under range, i.e. in case the lower display densation probe)
This alarm disables the compressor and limit is exceeded or in case of over range, Code E43 appears when the anti frost
the fans in circuit 2, turns the Alarm led i.e. in case the upper display limit is ex- alarm setpoint (parameter 26) is reached in
on and enables output SSR 1248 Vac. ceeded. the condensation probe in circuit 2 (only
Check connections before replacing the This alarm disables the compressors and for water-water heat pump with gas inver-
probe. the fans, turns the Alarm led on and en- sion - parameter 1 = 4).
E27 PTC condensation probe in cir- ables output SSR 1248 Vac. Relay out- This alarm disables the compressors and
cuit 2 (C2-DIN) or output water circuit puts are not disabled in case of heating the fans, turns the Alarm led on and en-
2 (C2-DIN) regulation and when the water-water ables output SSR 1248 Vac.
Code E27 appears in case of shorted, dis- pump is configured with external manual The intervention differential can be set
connected or interrupted probe. inversion (parameter 1 = 5). through parameter 27. Restore mode can
The same message appears in case of Check connections before replacing the be selected through parameter 28.
under range, i.e. in case the lower display probe.
limit is exceeded or in case of over range, E41 flow switch alarm TECHNICAL DATA
i.e. in case the upper display limit is ex- Code E41 appears in case the flow switch Housing: plastic 4 Din modules
ceeded. alarm is activated. This is subject to two 70x85 mm.
This alarm disables the compressor and conditions: the flow switch input shall have Depth: 61 mm.
the fans in circuit 2 (in circuit 1 too in case been opened for a time selectable through Mount: on Din rail (Omega 3) or wall.
fan synchronised activation is selected parameter 70 and the water pump shall Protection grade: IP54 front.

11 CH-DIN(/P) 3/98 ing


Serial connections: a telephone connec-
tor for the connection to the TS-DIN/S key-
board or to the interface modules and a
comb connector for the connection to the
C2-DIN module,
Connections: a screw terminal block for
2.5 mm2 wires (connection to fan mod-
ules), a screw terminal block for 1 mm2
wires (alarm output connection and digital
inputs for flow switch, fan thermal control
in circuit 1 and remote ON-OFF), Faston
terminal block 6.3 mm for other connec-
tions.
Display: on 10 mm high digits
Parameters storage: on non volatile
memory (EEPROM).
Operating temperature: -560 C.
Storage temperature: -3075 C.
Main outputs: 4 relay outputs 4(2)A AC
250V for compressor, anti-frost resistors,
water pump and inversion valve circuit 1;
terminal 22 can bear a load up to 4,5A.
Condenser fan output: 1 voltage digital
output to drive the special fan modules.
Alarm output: 1 output on static relay
(SSR) 1248 Vac, maximum consumption
200 mA.
CH-DIN analogue inputs: 3 PTC probes
for input water control, output water in cir-
cuit 1 and condensation circuit 1 (CH-DIN).
CH-DIN/P analogue inputs: 2 PTC probes
for input water control and output water
control circuit 1 and one 420 mA /
030 bar for pressure probes (condensa-
tion control circuit 1).
PTC probe display range:
50,099,9 C.
Digital inputs: 6 ON/OFF inputs for flow
switch, circuit 1 fan thermal system per, re-
mote ONOFF, maximum pressure switch
circuit 1, minimum pressure switch circuit
1 and compressr thermal magnetic
circuit 1.
Resolution: 0.1 C.
Accuracy:
0,5 % end of scale within reading range
from -1580 C.
1 % end of scale within reading range
from 5015 C and from 8099,9 C.
Power supply: 12 Vac 3VA.

Microtech s.r.l.
via dellIndustria
Zona Industriale
32010 Pieve dAlpago (BL)
Italy

Telephone +39 (0)437 986444


Facsimile +39 (0)437 989146,