FEATURES
Non-Ozone Depleting Fast Acting
Safe for Total Flooding of Occupied Spaces Active Fire Suppression Agent
Clean No Residue to Clean Up UL Component Recognized
Non-Damaging to Hazard Contents FM Approved
EXTINGUISHING AGENT Underwriters Laboratories, Inc. (UL) and Factory Mutual
FM-200 (1,1,1,2,3,3,3-heptafluoropropane) is a com- Research Corporation (FMRC).
pound of carbon, fluorine and hydrogen (CF3CHFCF3). It USE
is colorless, odorless and electrically non-conductive. It FM-200 is used in total flooding fire suppression systems.
suppresses fire by a combination of chemical and physi- It is stored in steel containers, and is super-pressurized
cal mechanisms without affecting the available oxygen. with nitrogen to aid in expelling the agent. The discharge
This allows personnel to see and breathe, permitting time is 10 seconds or less. The maximum fill density of
them to leave the fire area safely. FM-200 has acceptable the agent storage is 70 lb./ft. . 3
tion products which result when the agent is exposed to Critical Density 38.76 lb./ft.3 (621 kg/m3)
fire and other hot surfaces. Exposure to the agent is gen- Critical Pressure 422 PSIA (29.0 bar absolute)
erally of less concern than is exposure to the decomposi- Critical Volume 0.0258 cu.ft./lb. (1.61 L/kg)
tion products. Unnecessary exposure to the agent or the Ozone Depletion Potential 0
decomposition products should be avoided.
TOXICITY Table 2. FM-200 Fire Protection Properties
In tests, the acute toxicity of FM-200 was shown to be
equivalent to that of Halon 1301. FM-200 has been evalu- Cup Burner Concentration (n-Heptane) 6.70% v/v
ated for cardiac sensitization through test protocols Use Concentration for n-Heptane 8.00% v/v
approved by the US EPA. The EPAs SNAP Program Use Concentration for Acetone 8.30% v/v
classifies FM-200 as acceptable for use as a total flood-
Use Concentration for Isopropanol 9.00% v/v
ing agent in occupied spaces. Refer to the SNAP pro-
gram rules for more information. Use Concentration for Toluene 7.00% v/v
This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes Kidde Fire Systems
no responsibility for the products suitability for a particular application. The product must be A UTC Fire & Security Company
properly applied to work correctly. 400 Main Street
If you need more information on this product, or if you have a particular problem or question, Ashland, MA 01721
contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000.
Ph: 508.881.2000
K-90-1900 Rev AB 2007 Kidde-Fenwal Inc. Printed in USA Fax: 508.881.8920
www.kiddefiresystems.com
FM-200 Component Description
Cylinder Valve A UTC Fire & Security Company
FEATURES
For Use with UL Listed, ULC Listed and See Kidde Manual 90-FM200M-021
FM Approved Systems for USCG Approval
BODY
Equivalent Length in Schedule 40 Pipe
SLAVE CYLINDER
ACTUATION PORT
1/8" NPT 1" 16.7' of 1"
A
SAFETY 2" 28.0' of 2"
DISC
PRESSURE 2" 3.5' of 2"
GAGE
B
SAFETY CHAIN ACTUATION PORT
VENT HOLE
CONTROL HEAD MATERIALS
CONNECTION
Valve Body: Brass
DISCHARGE
Piston: Brass
PISTON
OUTLET PORT Finish: Natural
Seat: Rubber
SUPERVISORY
PRESSURE
SAFETY SWITCH
CAP CONNECTION
SEAT
Valve
Part Number A B C D E F
Size
90-140000-000 1" 7.63" 4.83" 5.22" 754-900 PSI 242461 9.9 lb.
This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes Kidde Fire Systems
no responsibility for the products suitability for a particular application. The product must be A UTC Fire & Security Company
properly applied to work correctly. 400 Main Street
If you need more information on this product, or if you have a particular problem or question, Ashland, MA 01721
contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000.
Ph: 508.881.2000
K-90-2080 Rev AB 2007 Kidde-Fenwal Inc. Printed in USA Fax: 508.881.8920
www.kiddefiresystems.com
FM-200 Component Description
A UTC Fire & Security Company
Pressure Operated Control Head
Effective: January 2009
K-90-5010
FEATURES
For Use with UL, ULC and FM Approved Systems See Kidde Manual 90-FM200M-021 for
USCG Approval
P/N: 878737
1.00" HEX
1/8"-27 NPT
PRESSURE INLET
PISTON
2.19"
SWIVEL NUT
SET
OPERATED 1.250-18
UNEF-3B
1.50" HEX
MATERIAL
Body (Retaining Nut and Piston): Brass
This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes Kidde Fire Systems
no responsibility for the products suitability for a particular application. The product must be A UTC Fire & Security Company
properly applied to work correctly. 400 Main Street
If you need more information on this product, or if you have a particular problem or question, Ashland, MA 01721
contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000.
Ph: 508.881.2000
K-90-5010 Rev AC 2009 Kidde-Fenwal Inc. Printed in USA Fax: 508.881.8920
www.kiddefiresystems.com
FM-200 Component Description
Cylinder and Valve Assembly, A UTC Fire & Security Company
200 lb. (90.7 kg) Capacity Effective: April 2007
K-90-2040
FEATURES
For Use with UL Listed, ULC Listed See Kidde Manual 90-FM200M-021
and FM Approved Systems for USCG Approval
ORDERING INFORMATION
90-100200-101 STD
90-100201-101 w/LLI
MATERIALS
Valve Body: Brass
Cylinder: Steel, Painted Red
Notes:
1. The safety cap must be installed on the valve outlet
at all times, except when the cylinders are con-
nected to the system piping, or being filled. The
safety cap must not be removed from its chain.
2. See K-90-2070 for additional information.
This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes Kidde Fire Systems
no responsibility for the products suitability for a particular application. The product must be A UTC Fire & Security Company
properly applied to work correctly. 400 Main Street
If you need more information on this product, or if you have a particular problem or question, Ashland, MA 01721
contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000.
Ph: 508.881.2000
K-90-2040 Rev AB 2007 Kidde-Fenwal Inc. Printed in USA Fax: 508.881.8920
www.kiddefiresystems.com
FM-200 Component Description
Cylinder and Valve Assembly,
350 lb. (158.7 kg) Capacity Effective: August 2012
K-90-2050
FEATURES
For Use with UL Listed, ULC Listed See Kidde Manual 90-FM200M-021
and FM Approved Systems for USCG Approval
ORDERING INFORMATION
VALVE OUTLET
Part Number Description
30
90-100350-001 STD
90-100351-001 w/LLI
PLAN VIEW
MATERIALS
SAFETY CAP CYLINDER VALVE Valve Body: Brass
LIQUID LEVEL
Cylinder: Steel, Painted Red
INDICATOR (LLI)
LIFTING
LUGS
CYLINDER
58.36" 53.14"
CYLINDER
NAMEPLATE
16.00" DIA
Notes:
1. The safety cap must be installed on the valve outlet
at all times, except when the cylinders are con-
nected to the system piping, or being filled. The
safety cap must not be removed from its chain.
2. See K-90-2070 for additional information.
Kidde is a registered trademark of Kidde-Fenwal Inc. All other trademarks are the property of their respective owners.
This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes Kidde Fire Systems
no responsibility for the products suitability for a particular application. The product must be 400 Main Street
properly applied to work correctly. Ashland, MA 01721
If you need more information on this product, or if you have a particular problem or question, Ph: 508.881.2000
contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000.
Fax: 508.881.8920
K-90-2050 Rev AC 2012 Kidde-Fenwal Inc. www.kiddefiresystems.com
FM-200 Component Description
A UTC Fire & Security Company
Pressure Operated Switch
Effective: September 2010
K-90-5180
FEATURES
For Use with UL Listed, ULC Listed and See Kidde Manual 90-FM200M-021 for
FM Approved Systems USCG Approval
P/N: 81-486536-000
STEM SHOWN IN SET POSITION-
PULL UP ON STEM TO MANUALLY
OPERATED OPERATED OPERATE SWITCH
SET SET
0.375"
PRESSURE OPERATED SWITCH
WIRING 3P.D.T. 8 COVER SCREWS
4.00" SCREW TO RESET
PUSH STEM TO SET POSITION
TERMINALS U
15 AMP. 125 V.AC L 10 AMP.250 V.AC
3/4HP250 VAC
PT. NO. 486536
FM
TO RESET
KIDDE-FENWAL, INC.
400 MAIN STREET
ASHLAND, MA 01721
OPERATED
SET
NC NC NC
BOX 3 EACH SIDE
1/2 CONDUIT
SWITCH 3PDT KNOCKOUTS C C C
COVER
NO NO NO
NOTES:
The switch may be mounted in any position; how- Contact Ratings (3 PDT):
ever, the preferred installation is upright, as shown. 15 Amp @125 Vac
Any load connection to the switch must not exceed 10 Amp @ 250 Vac
the switch rating, and shall utilize a suitable protec- 3/4 HP @ 250 Vac
tion device (i.e., circuit breaker, fuse). 1, 2 or 3 Phase
This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes Kidde Fire Systems
no responsibility for the products suitability for a particular application. The product must be A UTC Fire & Security Company
properly applied to work correctly. 400 Main Street
If you need more information on this product, or if you have a particular problem or question, Ashland, MA 01721
contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000.
Ph: 508.881.2000
K-90-5180 Rev AC 2010 Kidde-Fenwal Inc. Printed in USA Fax: 508.881.8920
www.kiddefiresystems.com
FM-200 Component Description
A UTC Fire & Security Company
Electric Control Head
Effective: April 2007
K-90-8010
FEATURES
For Use with UL Listed, ULC Listed and
FM Approved Systems
P/N: 8901XX
This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes Kidde Fire Systems
no responsibility for the products suitability for a particular application. The product must be A UTC Fire & Security Company
properly applied to work correctly. 400 Main Street
If you need more information on this product, or if you have a particular problem or question, Ashland, MA 01721
contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000.
Ph: 508.881.2000
K-90-8010 Rev AB 2007 Kidde-Fenwal Inc. Printed in USA Fax: 508.881.8920
www.kiddefiresystems.com
FM-200 Component Description
Cylinder Mounting Straps
Effective: April 2007
K-90-8130
FEATURES
For Use with UL Listed, ULC Listed and
FM Approved Systems
CYL. O.D. A B C D E F
PART CYL.
NO. SIZE
in. mm in. mm in. mm in. mm in. mm in. mm in. mm
283945 10, 20 7.07 1.80 6.48 165 9.62 244 8.62 219 1.00 25 2.78 71 .437 11.1
283934 40, 70 9.00 229 8.16 207 11.69 297 10.69 272 1.00 25 3.50 89 .437 11.1
292971 200 13.60 345 13.09 332 17.06 433 15.44 392 1.75 44 6.06 154 .625 15.9
pre-3/98
235317 125, 200 12.75 324 12.93 329 16.18 411 14.56 370 1.75 44 5.59 142 .625 15.9
281866 350 16.00 406 15.5 394 19.5 495 17.88 454 1.75 44 6.06 154 .625 15.9
294651 600 22.00 559 21.56 548 25.75 654 24.12 613 1.75 44 10.25 260 .625 15.9
236125 900 24.00 610 23.75 603 27.75 705 26.00 660 1.75 44 12.13 308 .625 15.9
MATERIALS
Steel, Painted Black SAE 1020
This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes Kidde Fire Systems
no responsibility for the products suitability for a particular application. The product must be A UTC Fire & Security Company
properly applied to work correctly. 400 Main Street
If you need more information on this product, or if you have a particular problem or question, Ashland, MA 01721
contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000.
Ph: 508.881.2000
K-90-8130 Rev AB 2007 Kidde-Fenwal Inc. Printed in USA Fax: 508.881.8920
www.kiddefiresystems.com
600 lb. FM-200 Cylinder
P/Ns 90-100600-100 and 90-100601-100
Effective: July 2013
K-90-9043
FEATURES
3-Inch Discharge Valve FM Approved
Optional Liquid Level Indicator UL Listed
Optional Low-Pressure Switch (P/N 06-118263-001) TC Approved
90-100600-100 90-100600-100
Part Number
90-100601-100 90-100601-100
*
For cylinder valves manufactured prior to May 1, 2013 use
supervisory pressure switch P/N: 06-118263-001.
FEATURES
Large Capacity FM-200 Cylinder FM Approved
3-Inch Discharge Valve UL Listed
Optional Liquid Level Indicator TC Approved
Optional Low-Level Switch (P/N 06-118263-001)
DESCRIPTION
Kidde FM-200 900 lb. cylinders store FM-200 super-
QUARTERLY INSPECTION
1. Check the pressure gauges of each agent storage
container. If the pressure gauge indicates a loss in VALVE ORIENTATION
PLAN VIEW
pressure of 10% or more, then it shall be recharged
or replaced. Pressure varies with temperature, and
this must be taken into account when checking the
pressure gauge. In the range of 55F to 85F (13C
70
to 29C) the change is approximately 3 PSI per (1789 mm)
degree F (0.2 bar per degree C).
2. Check all components, including supporting hard- 62
(1566 mm)
ware, and tighten, repair or replace as required.
3. Replace any component if at all in doubt of its ability
SAFETY BURST
to perform properly. DISC ASSEMBLY
SEMI-ANNUAL INSPECTION
Qualified personnel should determine the amount of
agent in all containers. The optional liquid level indicator
may be used to measure agent supply and compare it to
the original net weight which is marked on the container
label. If the measured net weight is less than 95% of the
original charged weight the container should be
recharged or replaced. 24
(610 mm)
Inspect all piping, fittings and nozzles for looseness, dirt
or other damage. All outlet piping must be clean and free
of dirt, chips, fillings and other foreign material that may ACCESSORIES
cause the system to become inoperative or ineffective at
the time of discharge. Description Part number
Safety Relief
800 to 975 PSIG 5.5 to 6.7 Mpa
Burst Range
Construction
DOT 4BW-500 DOT 4BW-500
Specification