Sie sind auf Seite 1von 12

FM-200

A UTC Fire & Security Company


Fire Suppression Agent
Effective: April 2007
K-90-1900

FEATURES
Non-Ozone Depleting Fast Acting
Safe for Total Flooding of Occupied Spaces Active Fire Suppression Agent
Clean No Residue to Clean Up UL Component Recognized
Non-Damaging to Hazard Contents FM Approved
EXTINGUISHING AGENT Underwriters Laboratories, Inc. (UL) and Factory Mutual
FM-200 (1,1,1,2,3,3,3-heptafluoropropane) is a com- Research Corporation (FMRC).
pound of carbon, fluorine and hydrogen (CF3CHFCF3). It USE
is colorless, odorless and electrically non-conductive. It FM-200 is used in total flooding fire suppression systems.
suppresses fire by a combination of chemical and physi- It is stored in steel containers, and is super-pressurized
cal mechanisms without affecting the available oxygen. with nitrogen to aid in expelling the agent. The discharge
This allows personnel to see and breathe, permitting time is 10 seconds or less. The maximum fill density of
them to leave the fire area safely. FM-200 has acceptable the agent storage is 70 lb./ft. . 3

toxicity for use in occupied spaces when used as speci-


fied in the United States Environmental Protection
Agency (EPA) Significant New Alternative Policy (SNAP) Table 1. FM-200 Physical Properties
program rules. Although FM-200 is considered non-toxic Chemical Formula CF3CHFCF3
to humans in concentrations necessary to extinguish Molecular Weight 170.03
most fires, certain safety considerations should be
Freezing Point -204F (-131C)
observed when applying and handling the agent. The dis-
Boiling Point at 1 Atm. 2.6F (-16.4C)
charge of FM-200 may create a hazard to personnel from
the undecomposed agent itself and from the decomposi- Critical Temperature 215.1F (101.7C)

tion products which result when the agent is exposed to Critical Density 38.76 lb./ft.3 (621 kg/m3)

fire and other hot surfaces. Exposure to the agent is gen- Critical Pressure 422 PSIA (29.0 bar absolute)
erally of less concern than is exposure to the decomposi- Critical Volume 0.0258 cu.ft./lb. (1.61 L/kg)
tion products. Unnecessary exposure to the agent or the Ozone Depletion Potential 0
decomposition products should be avoided.
TOXICITY Table 2. FM-200 Fire Protection Properties
In tests, the acute toxicity of FM-200 was shown to be
equivalent to that of Halon 1301. FM-200 has been evalu- Cup Burner Concentration (n-Heptane) 6.70% v/v
ated for cardiac sensitization through test protocols Use Concentration for n-Heptane 8.00% v/v
approved by the US EPA. The EPAs SNAP Program Use Concentration for Acetone 8.30% v/v
classifies FM-200 as acceptable for use as a total flood-
Use Concentration for Isopropanol 9.00% v/v
ing agent in occupied spaces. Refer to the SNAP pro-
gram rules for more information. Use Concentration for Toluene 7.00% v/v

Use Concentration for Class A (Surface Fires)* 6.25% v/v


CLEANLINESS
FM-200 is clean, leaves no residue, thereby eliminating *Note: Automatic only per NFPA 2001.

costly after-fire clean-up, and keeping expensive down-


time to a minimum. Most materials such as steel, stain- Table 3. FM-200 Toxicity Properties
less steel, aluminum, brass, and other metals as well as
plastics,rubber and electronic components are unaffected NOAEL
9.00%
(No Observable Adverse Effect Level)
by exposure to FM-200.
LOAEL
10.50%
APPROVALS (Lowest Observable Adverse Effect Level)

FM-200 agent complies with the NFPA Standard 2001:


Standard for Clean Agent Fire Extinguishing Systems,
EPA SNAP Program (Significant New Alternate Policy), FM-200 is a registered trademark of the Great Lakes Chemical Corporation.

This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes Kidde Fire Systems
no responsibility for the products suitability for a particular application. The product must be A UTC Fire & Security Company
properly applied to work correctly. 400 Main Street
If you need more information on this product, or if you have a particular problem or question, Ashland, MA 01721
contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000.
Ph: 508.881.2000
K-90-1900 Rev AB 2007 Kidde-Fenwal Inc. Printed in USA Fax: 508.881.8920
www.kiddefiresystems.com
FM-200 Component Description
Cylinder Valve A UTC Fire & Security Company

Effective: April 2007


K-90-2080

FEATURES
For Use with UL Listed, ULC Listed and See Kidde Manual 90-FM200M-021
FM Approved Systems for USCG Approval

P/N: 90-1X0000-000 TECHNICAL DATA


Working Pressure: 360 to 609 PSIG
Proof Pressure: 1000 PSIG
CAP
Burst Pressure: 2000 PSIG
Temperature Range: 1F to 130F

BODY
Equivalent Length in Schedule 40 Pipe
SLAVE CYLINDER
ACTUATION PORT
1/8" NPT 1" 16.7' of 1"
A
SAFETY 2" 28.0' of 2"
DISC
PRESSURE 2" 3.5' of 2"
GAGE

B
SAFETY CHAIN ACTUATION PORT

VENT HOLE
CONTROL HEAD MATERIALS
CONNECTION
Valve Body: Brass
DISCHARGE
Piston: Brass
PISTON
OUTLET PORT Finish: Natural
Seat: Rubber
SUPERVISORY
PRESSURE
SAFETY SWITCH
CAP CONNECTION
SEAT

Valve
Part Number A B C D E F
Size

90-140000-000 1" 7.63" 4.83" 5.22" 754-900 PSI 242461 9.9 lb.

90-150000-000 2" 8.80" 5.32" 6.28" 798-972 PSI 264925 15 lb.

90-160000-000 2" 10.04" 6.30" 6.61" 798-972 PSI 264929 24 lb.

FM-200 is a registered trademark of the Great Lakes Chemical Corporation.

This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes Kidde Fire Systems
no responsibility for the products suitability for a particular application. The product must be A UTC Fire & Security Company
properly applied to work correctly. 400 Main Street
If you need more information on this product, or if you have a particular problem or question, Ashland, MA 01721
contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000.
Ph: 508.881.2000
K-90-2080 Rev AB 2007 Kidde-Fenwal Inc. Printed in USA Fax: 508.881.8920
www.kiddefiresystems.com
FM-200 Component Description
A UTC Fire & Security Company
Pressure Operated Control Head
Effective: January 2009
K-90-5010

FEATURES
For Use with UL, ULC and FM Approved Systems See Kidde Manual 90-FM200M-021 for
USCG Approval

P/N: 878737

1.00" HEX
1/8"-27 NPT
PRESSURE INLET

PISTON

2.19"
SWIVEL NUT

SET
OPERATED 1.250-18
UNEF-3B

1.50" HEX

MATERIAL
Body (Retaining Nut and Piston): Brass

FM-200 is a registered trademark of the Great Lakes Chemical Corporation.

This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes Kidde Fire Systems
no responsibility for the products suitability for a particular application. The product must be A UTC Fire & Security Company
properly applied to work correctly. 400 Main Street
If you need more information on this product, or if you have a particular problem or question, Ashland, MA 01721
contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000.
Ph: 508.881.2000
K-90-5010 Rev AC 2009 Kidde-Fenwal Inc. Printed in USA Fax: 508.881.8920
www.kiddefiresystems.com
FM-200 Component Description
Cylinder and Valve Assembly, A UTC Fire & Security Company
200 lb. (90.7 kg) Capacity Effective: April 2007
K-90-2040

FEATURES
For Use with UL Listed, ULC Listed See Kidde Manual 90-FM200M-021
and FM Approved Systems for USCG Approval

ORDERING INFORMATION

Part Number Description

90-100200-101 STD

90-100201-101 w/LLI

MATERIALS
Valve Body: Brass
Cylinder: Steel, Painted Red

Notes:
1. The safety cap must be installed on the valve outlet
at all times, except when the cylinders are con-
nected to the system piping, or being filled. The
safety cap must not be removed from its chain.
2. See K-90-2070 for additional information.

FM-200 is a registered trademark of the Great Lakes Chemical Corporation.

This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes Kidde Fire Systems
no responsibility for the products suitability for a particular application. The product must be A UTC Fire & Security Company
properly applied to work correctly. 400 Main Street
If you need more information on this product, or if you have a particular problem or question, Ashland, MA 01721
contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000.
Ph: 508.881.2000
K-90-2040 Rev AB 2007 Kidde-Fenwal Inc. Printed in USA Fax: 508.881.8920
www.kiddefiresystems.com
FM-200 Component Description
Cylinder and Valve Assembly,
350 lb. (158.7 kg) Capacity Effective: August 2012
K-90-2050

FEATURES
For Use with UL Listed, ULC Listed See Kidde Manual 90-FM200M-021
and FM Approved Systems for USCG Approval

ORDERING INFORMATION
VALVE OUTLET
Part Number Description
30
90-100350-001 STD

90-100351-001 w/LLI

PLAN VIEW
MATERIALS
SAFETY CAP CYLINDER VALVE Valve Body: Brass
LIQUID LEVEL
Cylinder: Steel, Painted Red
INDICATOR (LLI)
LIFTING
LUGS

CYLINDER

58.36" 53.14"
CYLINDER
NAMEPLATE

16.00" DIA

Notes:
1. The safety cap must be installed on the valve outlet
at all times, except when the cylinders are con-
nected to the system piping, or being filled. The
safety cap must not be removed from its chain.
2. See K-90-2070 for additional information.

Kidde is a registered trademark of Kidde-Fenwal Inc. All other trademarks are the property of their respective owners.

This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes Kidde Fire Systems
no responsibility for the products suitability for a particular application. The product must be 400 Main Street
properly applied to work correctly. Ashland, MA 01721
If you need more information on this product, or if you have a particular problem or question, Ph: 508.881.2000
contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000.
Fax: 508.881.8920
K-90-2050 Rev AC 2012 Kidde-Fenwal Inc. www.kiddefiresystems.com
FM-200 Component Description
A UTC Fire & Security Company
Pressure Operated Switch
Effective: September 2010
K-90-5180

FEATURES
For Use with UL Listed, ULC Listed and See Kidde Manual 90-FM200M-021 for
FM Approved Systems USCG Approval

P/N: 81-486536-000
STEM SHOWN IN SET POSITION-
PULL UP ON STEM TO MANUALLY
OPERATED OPERATED OPERATE SWITCH
SET SET

0.375"
PRESSURE OPERATED SWITCH
WIRING 3P.D.T. 8 COVER SCREWS
4.00" SCREW TO RESET
PUSH STEM TO SET POSITION
TERMINALS U
15 AMP. 125 V.AC L 10 AMP.250 V.AC
3/4HP250 VAC
PT. NO. 486536
FM

TO RESET
KIDDE-FENWAL, INC.
400 MAIN STREET
ASHLAND, MA 01721

PUSH STEM TO SET POSITION

15 AMP 125 VAC


4.00" 10 AMP 250 VAC
3/4 HP 1-2-3 PH 125-480 VAC
FRONT VIEW
COVER REMOVED
1/2 SUPPLY PIPE WITH UNION
FRONT VIEW

OPERATED
SET
NC NC NC
BOX 3 EACH SIDE
1/2 CONDUIT
SWITCH 3PDT KNOCKOUTS C C C

COVER
NO NO NO

GASKET NPT FEMALE,


CONNECT TO SYSTEM PRESSURE INLET
PIPING
SIDE SECTION WIRING DIAGRAM

NOTES:
The switch may be mounted in any position; how- Contact Ratings (3 PDT):
ever, the preferred installation is upright, as shown. 15 Amp @125 Vac
Any load connection to the switch must not exceed 10 Amp @ 250 Vac
the switch rating, and shall utilize a suitable protec- 3/4 HP @ 250 Vac
tion device (i.e., circuit breaker, fuse). 1, 2 or 3 Phase

FM-200 is a registered trademark of the Great Lakes Chemical Corporation.

This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes Kidde Fire Systems
no responsibility for the products suitability for a particular application. The product must be A UTC Fire & Security Company
properly applied to work correctly. 400 Main Street
If you need more information on this product, or if you have a particular problem or question, Ashland, MA 01721
contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000.
Ph: 508.881.2000
K-90-5180 Rev AC 2010 Kidde-Fenwal Inc. Printed in USA Fax: 508.881.8920
www.kiddefiresystems.com
FM-200 Component Description
A UTC Fire & Security Company
Electric Control Head
Effective: April 2007
K-90-8010

FEATURES
For Use with UL Listed, ULC Listed and
FM Approved Systems

P/N: 8901XX

FM-200 is a registered trademark of the Great Lakes Chemical Corporation.

This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes Kidde Fire Systems
no responsibility for the products suitability for a particular application. The product must be A UTC Fire & Security Company
properly applied to work correctly. 400 Main Street
If you need more information on this product, or if you have a particular problem or question, Ashland, MA 01721
contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000.
Ph: 508.881.2000
K-90-8010 Rev AB 2007 Kidde-Fenwal Inc. Printed in USA Fax: 508.881.8920
www.kiddefiresystems.com
FM-200 Component Description

Cylinder Mounting Straps
Effective: April 2007
K-90-8130

FEATURES
For Use with UL Listed, ULC Listed and
FM Approved Systems

CYL. O.D. A B C D E F
PART CYL.
NO. SIZE
in. mm in. mm in. mm in. mm in. mm in. mm in. mm

283945 10, 20 7.07 1.80 6.48 165 9.62 244 8.62 219 1.00 25 2.78 71 .437 11.1

283934 40, 70 9.00 229 8.16 207 11.69 297 10.69 272 1.00 25 3.50 89 .437 11.1

292971 200 13.60 345 13.09 332 17.06 433 15.44 392 1.75 44 6.06 154 .625 15.9
pre-3/98

235317 125, 200 12.75 324 12.93 329 16.18 411 14.56 370 1.75 44 5.59 142 .625 15.9

281866 350 16.00 406 15.5 394 19.5 495 17.88 454 1.75 44 6.06 154 .625 15.9

294651 600 22.00 559 21.56 548 25.75 654 24.12 613 1.75 44 10.25 260 .625 15.9

236125 900 24.00 610 23.75 603 27.75 705 26.00 660 1.75 44 12.13 308 .625 15.9

MATERIALS
Steel, Painted Black SAE 1020

FM-200 is a registered trademark of the Great Lakes Chemical Corporation.

This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes Kidde Fire Systems
no responsibility for the products suitability for a particular application. The product must be A UTC Fire & Security Company
properly applied to work correctly. 400 Main Street
If you need more information on this product, or if you have a particular problem or question, Ashland, MA 01721
contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000.
Ph: 508.881.2000
K-90-8130 Rev AB 2007 Kidde-Fenwal Inc. Printed in USA Fax: 508.881.8920
www.kiddefiresystems.com
600 lb. FM-200 Cylinder
P/Ns 90-100600-100 and 90-100601-100
Effective: July 2013
K-90-9043

FEATURES
3-Inch Discharge Valve FM Approved
Optional Liquid Level Indicator UL Listed
Optional Low-Pressure Switch (P/N 06-118263-001) TC Approved

DESCRIPTION listed below and performed upon the occurrence of any


Kidde FM-200 600 lb. cylinders store FM-200 super-
event which might affect the reliability of the system.
pressurized with dry nitrogen to 360 psig at 70F (2.48
Mpa at 21C). The cylinders are painted red and are
equipped with a 3-inch pressure differential valve, pres-
sure gauge, optional liquid level indicator and optional
low-pressure switch assembly. The safety burst disc is
also located on the cylinder head.
OPERATION
The agent storage container discharges when the actua-
tion assembly operates, causing the pressure differential
valve to open. All of the Kidde actuators may be used to
actuate the 600 lb. cylinder. The only exception is the
48650001, which is not compatible with this cylinder
valve.
INSTALLATION
The container is installed in a vertical position with the
valve assembly pointing up. Interconnection to discharge
piping is 3-inch NPT. Interconnection can be via a 3-inch
flex hose (P/N 06-118225-001) or via a suitably pressure
rated groove style fitting.
The container is secured in place by a mounting bracket
(P/N 294651), which must be fixed to a solid wall or strut
assembly. After the container is securely mounted it is
connected to discharge piping per the directions in the
design manual.
An optional cylinder supervisory pressure switch (P/N 06-
118262-001) can be installed on the cylinder valve in the
field if required. This cylinder supervisory pressure switch
has a 1/8-inch NPT connection, which is used on the 3-
inch valve only. For cylinder valves manufactured prior to
May 1, 2013, use supervisory pressure switch P/N 06-
118263-001.
QUARTERLY INSPECTION
ORDERING INFORMATION 1. Check the pressure gauges of each agent storage
The part number for ordering the 600 lb. FM-200 cylinder container. If the pressure gauge indicates a loss in
without liquid level indicator is 90-100600-100. The part pressure of 10% or more, then it shall be recharged
number for ordering the 600 lb. FM-200 cylinder with liq- or replaced. Pressure varies with temperature, and
uid level indicator is 90-100601-100. this must be taken into account when checking the
MAINTENANCE pressure gauge. In the range of 55F to 85F (13C
According to NFPA standards the following inspection to 29C) the change is approximately 3 psi per
and/or maintenance procedure must be scheduled as degree F.
2. Check all components, including supporting hard- DIMENSIONS
ware, and tighten, repair or replace as required.
3. Replace any component if at all in doubt of its ability
to perform properly.
SEMI-ANNUAL INSPECTION
Qualified personnel are to determine the amount of agent
in all containers. The optional liquid level indicator may
be used to measure agent supply and compare it to the
original net weight which is marked on the container
label. If the measured net weight is less than 95% of the VALVE ORIENTATION
PLAN VIEW
original charged weight the container should be
recharged or replaced.
Inspect all piping, fittings and nozzles for looseness, dirt
or other damage. All outlet piping must be clean and free
of dirt, chips, fillings and other foreign material that may
cause the system to become inoperative or ineffective at 58 50.5
(1478 mm) (1282 mm)
the time of discharge.
SPECIFICATIONS SAFETY BURST
DISC ASSEMBLY

90-100600-100 90-100600-100
Part Number
90-100601-100 90-100601-100

Fill range (lb.) 258-600 Fill range (kg) 117-272

Height (in.) 58 Height (mm) 1478

Diameter (in.) 22 Diameter (mm) 559

Internal volume 8.68 Internal volume 0.246


(cu. ft.) (cu m) 22
(559 mm)

Empty weight 362 Empty weight 164


(lb.) (kg)

Temperature 32F to 130F Temperature 0C to 54C


ACCESSORIES
range range
Description Part number
Safety relief 800 to 975 psig Safety relief 5.5 to 6.7 Mpa
burst range burst range
3-inch stainless steel flexible hose 06-118225-001
Construction DOT 4BW-500 Construction OT 4BW-500
specification specification 3-inch swing check valve 06-118058-001

Cylinder bracket WK-294651-000

Cylinder supervisory pressure switch 06-118262-001*

*
For cylinder valves manufactured prior to May 1, 2013 use
supervisory pressure switch P/N: 06-118263-001.

This literature is provided for informational purposes only. KIDDE-FENWAL, INC.


assumes no responsibility for the products suitability for a particular application.
The product must be properly applied to work correctly.
If you need more information on this product, or if you have a particular problem or
question, contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 400 Main Street
Ashland, MA 01721
881-2000.
Tel.: 508-881-2000
K-90-9043 Rev AC 2013 Kidde-Fenwal Inc. Fax: 508-881-8920
www.kiddefiresystems.com
900 lb. FM-200 Cylinder
P/Ns 90-100900-001 and 90-100901-001
Effective: July 2013
K-90-9044

FEATURES
Large Capacity FM-200 Cylinder FM Approved
3-Inch Discharge Valve UL Listed
Optional Liquid Level Indicator TC Approved
Optional Low-Level Switch (P/N 06-118263-001)

DESCRIPTION
Kidde FM-200 900 lb. cylinders store FM-200 super-

pressurized with dry nitrogen to 360 PSIG at 70F (2.48


Mpa at 21C). The cylinders are painted red and are
equipped with a 3-inch pressure differential valve, pres-
sure gauge, optional liquid level indicator and optional
low-pressure switch assembly. The safety burst disc is
also located on the cylinder head.
OPERATION
The agent storage container discharges when the actua-
tion assembly operates, causing the pressure differential
valve to open. All of the Kidde actuators may be used to
actuate the 900 lb. cylinder. The only exception is the
48650001, which is not compatible with this cylinder
valve.
INSTALLATION
The container is installed in a vertical position with the
valve assembly pointing up. Interconnection to discharge
piping is 3-inch NPT. Interconnection can be via a 3-inch
flex hose (P/N 06-118225-001) or via a suitably pressure
rated groove style fitting.
The container is secured in place by a mounting bracket
(P/N 236125), which must be fixed to a solid wall or strut
assembly. After the container is securely mounted, it is
connected to discharge piping per the directions in the
Design, Installation, Operation and Maintenance Manual
(P/N 90-FM200M-000).
An optional cylinder supervisory pressure switch (P/N 06-
118262-001) can be installed on the cylinder valve in the
field if required. This cylinder supervisory pressure switch
has a 1/8-inch NPT connection, which is used on the 3-
inch valve only. For cylinder valves manufactured prior to
May 1, 2013, use supervisory pressure switch P/N 06-
118263-001.
ORDERING INFORMATION
The part number for ordering the 900 lb. FM-200 cylinder
without the liquid level indicator is 90-100900-001. The
part number for ordering the 900 lb. FM-200 cylinder with
liquid level indicator is 90-100901-001.
MAINTENANCE DIMENSIONS
According to NFPA standards, the following inspection
and/or maintenance procedure must be scheduled as
listed below and performed upon the occurrence of any
event which might affect the reliability of the system.

QUARTERLY INSPECTION
1. Check the pressure gauges of each agent storage
container. If the pressure gauge indicates a loss in VALVE ORIENTATION
PLAN VIEW
pressure of 10% or more, then it shall be recharged
or replaced. Pressure varies with temperature, and
this must be taken into account when checking the
pressure gauge. In the range of 55F to 85F (13C
70
to 29C) the change is approximately 3 PSI per (1789 mm)
degree F (0.2 bar per degree C).
2. Check all components, including supporting hard- 62
(1566 mm)
ware, and tighten, repair or replace as required.
3. Replace any component if at all in doubt of its ability
SAFETY BURST
to perform properly. DISC ASSEMBLY
SEMI-ANNUAL INSPECTION
Qualified personnel should determine the amount of
agent in all containers. The optional liquid level indicator
may be used to measure agent supply and compare it to
the original net weight which is marked on the container
label. If the measured net weight is less than 95% of the
original charged weight the container should be
recharged or replaced. 24
(610 mm)
Inspect all piping, fittings and nozzles for looseness, dirt
or other damage. All outlet piping must be clean and free
of dirt, chips, fillings and other foreign material that may ACCESSORIES
cause the system to become inoperative or ineffective at
the time of discharge. Description Part number

SPECIFICATIONS 3-inch stainless steel flexible hose 06-118225-001

3-inch swing check valve 06-118058-001


90-100900-001
90-100901-001 Cylinder bracket 06-236125-001
Part Number
imperial metric Cylinder supervisory pressure switch 06-118262-001*
Fill range 390-900 lb. 178-408 kg
*
For cylinder valves manufactured prior to May 1, 2013 use
Height 70 in. 1789 mm supervisory pressure switch P/N: 06-118263-001.
Diameter 24 in. 610 mm

Internal Volume 13.0 cu. ft. 0.368 cu. m

Empty Weight 505 lb. 229 kg


o o
Temperature Range 32 F to 130 F 0 C to 54oC
o

Safety Relief
800 to 975 PSIG 5.5 to 6.7 Mpa
Burst Range

Construction
DOT 4BW-500 DOT 4BW-500
Specification

This literature is provided for informational purposes only. KIDDE-FENWAL, INC.


assumes no responsibility for the products suitability for a particular application.
The product must be properly applied to work correctly.
If you need more information on this product, or if you have a particular problem or
question, contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 400 Main Street
Ashland, MA 01721
881-2000.
Tel.: 508-881-2000
K-90-9044 Rev AD 2013 Kidde-Fenwal Inc. Fax: 508-881-8920