The DeltaV SIS process safety system has the worlds first CHARMs Smart SIS Logic Solver, using the power of predictive
intelligence to increase the availability of the entire safety instrumented function in combination with the advantages of the
Emerson Electronic Marshalling solution.
www.DeltaVSIS.com
DeltaV SIS Product Data Sheet
October 2014 Page 2 DeltaV SIS with Electronic Marshalling
Benefits Reduces installed cost of system. DeltaV SIS
Electronic Marshalling helps reduce overall system costs
Optimized process reliability. Emerson has extended by eliminating internal cabinet cross wiring, reducing
the benefits of the PlantWeb architecture to safety overall footprint, simplifying SIF design, and reducing FAT
instrumented systems, with DeltaV SIS being a key activities. Electronic Marshalling provides separation
component of the Smart SIS solution. Research shows between I&E hardware installation schedules and SIF
that over 90% of all faults in SIS applications occur in field development. Wiring can begin earlier knowing any late
instruments and final elements. The DeltaV SIS process changes can be done without lifting a wire. The ability to
safety system has the worlds first Smart Logic Solver read any input on the LSN allows more efficient cabinet
using LS CHARMs.It communicates with intelligent field designs and accommodates late scope changes to add
devices using the HART protocol to diagnose faults before I/O anywhere. Adding additional SIF capacity does not
they cause spurious trips. This approach increases require re-wiring I/O. Simply read the I/O signals from the
process availability and reduces lifecycle costs. proper CSLS, without lifting a wire.
Flexibility to meet project needs. Whether you have Fully redundant communications. The CSLS
an isolated wellhead or a large emergency shutdown architecture is fully redundant. It starts with the two logic
(ESD) application, the DeltaV SIS system scales to solvers on a carrier. The carrier has redundant Safety
provide you with the safety coverage you need for your Nework Ports (SNPs) for communication with primary and
SIL 1, 2 and 3 safety functions. Each CHARMs Smart secondary LSN connections. There are two 24 VDC input
Logic Solver provides I/O processing, SIL 3-capable logic power connections. The carrier connects to the CHARMs
solving, and diagnostics. This means that processing base plates providing redundant power and
power is added as the system expands, and no additional communication buses to the LS CHARMs. If required for
processors will ever be required. Scan rate and memory availability you have the option to use redundant output LS
usage are constant and independent of system size. CHARM Terminal Blocks with or without internal 1 A
relays for both DTA and ETA service. Everything is
Modularity also provides isolation of safety instrumented redundant down to the individual channel.
functions (SIFs). This isolation eliminates single-points of
failure for improved availability and safety integrity. Field mounted capable hardware. All components of
the CSLS are rated for installation in Class 1/Div 2 or Zone
The DeltaV SIS system looks for new hardware every 2 hazardous locations. The extended operating
scan, so equipment can be added to a running system in temperature ranges and G3 environment rating allows
real time. Online addition of new logic solvers will not them to be installed in field mounted junction boxes. This
interrupt your process. further reduces the footprint required in central equipment
rooms, as well as reduces the overall wiring infrastructure
Simplified safety lifecycle management. The of traditional multi-core instrumentation cable.
DeltaV SIS CSLSs are SIL 3-rated for both simplex and
redundant architectures. Redundant pairs of CSLSs can Plug and Play I/O. The DeltaV SIS CSLS has been
be installed for increased process availability of your SIFs. designed for ease of use, both in physical installation and
its software tools. Components snap together with secure
I/O anywhere you need it. The DeltaV SIS CSLS DIN-rail latches and interlocking carrier connectors. Attach
provides an unprecedented flexibility in safety system I/O a series of 96 I/O channels to a DIN-rail in a matter of
topology. Using standard Ethernet infrastructure hardware minutes. Insert the LS CHARMs and auto sense the node
you can add safety related I/O anywhere you need it. to create the I/O definition automatically in your DeltaV
From a local I/O cabinet to remote enclosures miles away, SIS configuration database. LS CHARMs use a self keying
simply install the CSLS and connect it to the Local Safety system to automatically set a channel for a specific LS
Network (LSN). Each CSLS can read the input signals CHARM type. Users cannot mistakenly insert a LS
from any other CSLS on the same LSN every 50 ms, the CHARM into the wrong terminal block.
same as the inputs wired directly to its own LS CHARM
system. Field power is provided through a redundant 24VDC bus
to each LS CHARM, with up to 100 mA per LS CHARM.
Higher current Discrete Input Channels can be powered
through integrated power injection bus local to each
CHARM Base plate. LS Discrete Output terminal blocks
with integrated relays are also available for up to 1A
continuous load.
DeltaV SIS Product Data Sheet
October 2014 Page 3 DeltaV SIS with Electronic Marshalling
Product Description Logic Solver Switchover
In the event that a failure is detected in one of the CSLSs,
For Use in SIL 3 Applications the CSLS will automatically will go into a failed state. In
With a safe failure fraction (SFF) greater than 99%, both this condition, there is no impact to the partner CSLS or
simplex and redundant installations of the DeltaV SIS the physical outputs. The partner CSLS continues to read
CSLS meet the SIL 3 requirements of IEC 61508 with no inputs, execute logic and drive outputs. The transition from
restrictions. Redundant CSLSs increase availability, but redundant to simplex is completely bumpless.
because both simplex and redundant CSLSs provide
hardware fault tolerance and safe failure fraction to meet Both logic solvers in a redundant pair are monitored for
SIL 3 requirements, redundancy does not increase safety. integrity alarms at all times, and an integrity error in either
CSLS will notify the operator of a failure. Events that can
SIF-based Approach cause integrity alarms include:
The DeltaV SIS system design was based on IEC 61511
safety instrumented function (SIF) concept, where every Hardware failure within a logic solver
logic solver is a container for a small number of SIFs.
Unlike other system architectures, with modular logic Communications failure between a logic solver and the
solving architecture, the logic solver is no longer a single LSN
point of failure for the entire process. If failures were to
occur, only the equipment tied to the logic solver would be Communications failure between a redundant pair of logic
affected. solvers
The DeltaV SIS SIF-based approach does not mean that Removal of a logic solver from the carrier
all of the safety logic and I/O have to fit into one logic
solver. All input data is made available to every logic The health and status of both logic solvers and their
Solver on the Local Safety Network every 50ms the same channels are available in the Diagnostics Explorer.
as the local inputs on every CSLS.
When one CSLS of a redundant pair of logic solvers is
With DeltaV SIS logic solvers, neither the scan rate nor removed online, there is no disturbance to the process.
the execution of a SIF is altered by changes or additions When the missing CSLS is replaced with another, the new
to another SIF. DeltaV SIS logic solvers always execute CSLS completes its power-up self-tests before the active
deterministically, every 50 ms, regardless of how much I/O CSLS cross-loads the current database. In safe areas,
is running on the system. failed CSLSs can be replaced under power. In hazardous
areas, appropriate installation procedures must be
Redundancy followed.
The redundant logic solvers include two CSLSs installed
side-by-side on the CSLS Carrier. The CSLS Carrier has Online proof testing
redundant power and communication connections to the Online proof testing can be performed on a redundant pair
base plates that are wired to the field devices. Each CSLS of logic solvers. The desired proof-test interval is set in the
of the redundant pair has a separate power supply. configuration. The logic solvers perform the proof test
automatically, with a warning provided to the operator
No control strategy configuration is required to take before the automatic proof test is started.
advantage of CSLS redundancy because the DeltaV SIS
auto-sense capability automatically recognizes the Diagnostics
redundant pair of cards.
The DeltaV SIS logic solvers execute extensive self-
testing on a continuous basis to detect potential faults.
When redundancy is chosen, the two CSLSs run in
Faults detected by logic solver diagnostics can be
parallel at all times. Both read the inputs from the I/O
associated with the logic solver itself or associated with
terminals, both execute the logic and both drive the
field devices, field wiring, or other conditions not related to
outputs at the I/O terminals. There is no concept of
hardware.
primary and backup or master and slave, which is unlike
any other safety system.
DeltaV SIS provides standard alarms to annunciate faults
detected by logic solvers in the operator interface. No
The only difference between the two CSLSs is that one
special configuration is required. When a diagnostic alarm
communicates with the engineering and operator
occurs, it appears on the alarm banner of the operator
workstations as well as the dedicated local safety network
interface. The operator is shown the type of alarm (failed,
(LSN). This CSLS has the Active light illuminated. The
maintenance, etc.), as well as text for the active condition
other CSLS is communicating only with the LSN.
or Multiple conditions if more than one alert condition is
active for the particular alarm.
DeltaV SIS Product Data Sheet
October 2014 Page 4 DeltaV SIS with Electronic Marshalling
Sequence of Events Capability CHARM Base plate (DIN rail mounted with interleaving
power and bus connectors. Supports 12 LS CHARMS
With DeltaV SIS, events are automatically generated as
and their terminal blocks, as well as connection for
function blocks are executed within a module scan. Events
injected field power)
are time stamped with a resolution of <1 ms, and they are
recorded in the sequence that they occur in the Event
Chronicle. When using standard function blocks such as LS CHARM Terminal Block (removable terminal block
input blocks, voter blocks, and cause and effect blocks, a providing terminal connections to field wiring and physical
standard set of events are automatically generated without latch for LS-CHARM)
special configuration or programing required. For example,
I/O failures, trip limits, first outs, and other similar events LS CHARMs (Logic Solver Characterization Module for
are automatically time stamped by function blocks and each field signal. Provides basic analog to digital
recorded in the Event Chronicle. When a process variable conversion and signal isolation to the redundant
exceeds the trip limit, DeltaV SIS records the event along communication bus)
with the analog value and the trip condition.
Cable Extenders that provide flexibility in carrier mounting.
In general, when there is a plant event that triggers an
emergency shutdown from the SIS, one input will exceed I/O bus termination (provides bus terminations for
a trip limit on one scan and this will cause outputs to trip redundant I/O bus)
and more inputs will then change state. Sequence of
Events Recording has been used to find that first input that Labeling features for base plate and channel identification.
caused the trip by looking at all of the inputs in the plant.
With the DeltaV SIS system, the operator simply filters the
The CHARM Smart Logic Solver carrier is mounted to the
Event Chronicle for first out trips, and the first-out is clearly
top of a vertical DIN rail and up to eight CHARM Base
visible.
plates are mounted below it, snapping easily to the DIN
rail as they are connected to each other. The bus
If higher resolution is required for some channels then
termination assembly is attached at the bottom. A
they can be wired to both the DeltaV SIS Logic Solver and
standard DIN-rail lock is used to keep the entire assembly
also to a DeltaV Discrete Input Card for Sequence of
in place.
Events, which provides a resolution of 0.25 ms.
A pair of CHARM Smart Logic solvers installs on the
carrier and communicates over a redundant Ethernet
Integrated HART safety network with up to 15 other CSLSs and 1 SZ
Integrated HART I/O brings field diagnostics into the logic controller, allowing great flexibility and ease of system
solver. Field device diagnostics information is not just for expansion. Safety Network Ports are available for copper
pass-through to AMS Device Manager; it is available only.
inside the logic solver.
Only DeltaV SIS Smart Switches are supported on the
The DeltaV SIS logic solver can also generate HART Local Safety Network.
commands to initiate a partial stroke test in a digital valve
controller. The operators can initiate partial stroke tests Each baseplate is ordered with 12 terminal blocks:
manually from their operator workstations or they can be standard terminal blocks or fused injected power terminal
scheduled to occur automatically based on the specified blocks. Electronic Marshalling eliminates the need to
test interval. The results from these tests are captured and partition the I/O wiring to specific channels based on
integrated with the system event history. An alarm can be signal type. Simply connect field signal multi-cores in an
generated if a partial stroke test fails, alerting maintenance orderly fashion as desired. Install the appropriate LS
that there is a potential problem with a valve. CHARM to complete the field circuit and the signal is
ready to be used by the CSLS. No cross-wiring required.
DeltaV SIS Electronic Marshalling hardware
includes: Each LS CHARM acts as a circuit protection device and
field wiring disconnect. Signals are inherently current
CHARM Smart Logic Solver Carrier (DIN rail mounted and limited to protect against wiring faults to ground. Each LS
supports a redundant pair of CHARM Smart Logic Solvers, CHARM provides surge protection to meet industry
redundant 24 VDC power connectivity, and redundant standards in the area of EMC. Under extreme overvoltage
Ethernet Safety Network communication Ports) conditions due to incorrect field wiring, the LS CHARM will
act as a fuse to protect adjacent channels. Signal faults
CHARM Smart Logic Solver (provides redundant safety are thus isolated to the single LS CHARM.
logic processing and communication to up to 96 LS-
CHARMs
DeltaV SIS Product Data Sheet
October 2014 Page 5 DeltaV SIS with Electronic Marshalling
LS CHARMs can be partially ejected to a locked position LS DI 120 VAC Isolated
that disconnects the field wiring from the system to
perform field maintenance actions or to remove power to a LS DI 230 VAC Isolated
field device. Activating the LS CHARM latch ejects the LS
CHARM to the detent position. Closing the latch locks the All LS CHARMs have a bi-color Power/Integrity LED that
LS CHARM in place and isolates the field wiring for field indicates the health of the LS CHARM. The indications
work. provide clear, actionable instruction to the maintenance
personnel.
Baseplate extenders and cables provide great flexibility to
the LS CHARM installation in existing cabinets or in Green Solid: Normal Operation
custom enclosures. Cables are redundant, each carrying
24 VDC field power, 6.3 VDC LS-CHARM power and one
Green Blink: Normal awaiting configuration
of the communication busses.
Red Blink: Fault detected on wiring
Bus termination provides added robustness for the
communication bus and is installed at the end of the
physical bus. Red Solid: Internal Fault detected
Label features are available to identify channel usage and Discrete LS CHARMs have a Yellow LED to indicate the
Baseplate identification to help with maintenance. state of the field signal. (On = circuit is energized)
LS CHARMs can be added to any existing base plate All LS CHARMs meet ISA 71.04-1985 severity level G3
position and autosensed online. Additional CSLSs can be (harsh) corrosion specifications.
added online.
I/O Terminal Block Options
LS CHARM Types There are 9 different I/O terminal blocks available to meet
A variety of analog and discrete LS CHARMs are available the wiring needs of field signals.
to meet your specific requirements. The following LS
CHARMs are available starting with v12.3: Standard Terminal Block
LS DI 24 VDC low-side sense (dry contact) LS Redundant DTA Fused Injected Power Relay Terminal
Block
LS DI 24 VDC Isolated
LS Redundant DTA Relay Terminal Block
LS 24 VDC Power
LS Redundant ETA Relay Terminal Block
LS DO 24 VDC DTA
LS Redundant DVC Terminal Block
LS DO 24 VDC ETA
The Standard Terminal Block can be used with all LS
LS DVC HART DTA AI, DI, and RTD CHARMs types. For traditional wiring of
field instrumentation, the LS CHARMs provide loop power
LS DO 24 VDC Redundant DTA through the internally distributed 24 VDC field power.
Refer to specific LS CHARM specifications for wiring
information.
LS DO 24 VDC Redundant ETA
The LS Redundant DTA Relay Terminal Block can LS CHARM Standard Terminal Block
be used with the LS DO Redundant DTA CHARMs type.
Refer to specific LS CHARM specifications for wiring
The keying mechanism consists of two keying posts that
information
rotate and lock into the terminal block base. Each LS
CHARM type is assigned a unique key setting.
The LS Redundant ETA RelayTerminal Block can
be used with the LS DO Redundant ETA CHARMs type. The LS DVC Terminal Block, LS Redundant DTA Relay
Refer to specific LS CHARM specifications for wiring Terminal Block, LS Redundant ETA RelayTerminal Block
information and the LS Redundant DVC Terminal Block has fixed key
positions to prevent a mismatch in the field.
DeltaV SIS Product Data Sheet
October 2014 Page 7 DeltaV SIS with Electronic Marshalling
Hardware Specifications
Common Environmental Specifications (all components)
Operating temperature -40 to 70 C (-40 to 158 F)
Storage temperature -40 to 85 C (-40 to 185 F)
Relative humidity 5 to 95% , non-condensing
Protection rating IP 20, NEMA 12
Airborne contaminants ISA-S71.04-1985 Airborne Contaminants Class G3
Conformal coating
Shock 10 g -sine wave for 11 ms
Vibration 1mm Peak-to-Peak from 2 to 13.2 Hz; 0.7g from 13.2 to 150 Hz.
DeltaV SIS Product Data Sheet
October 2014 Page 8 DeltaV SIS with Electronic Marshalling
Input LS CHARMs
DeltaV SIS Product Data Sheet
October 2014 Page 13 DeltaV SIS with Electronic Marshalling
Output LS CHARMs
Simplified Circuit and Connection Diagrams for LS AI HART CHARM 0/ 4 to 20 mA Two Wire and Four Wire transmitters
DeltaV SIS Product Data Sheet
October 2014 Page 23 DeltaV SIS with Electronic Marshalling
LS RTD Input CHARM
Simplified Circuit and Connection Diagram for LS Thermocouple/mV CHARM with Thermocouple/mV Terminal Block
DeltaV SIS Product Data Sheet
October 2014 Page 27 DeltaV SIS with Electronic Marshalling
LS Analog Input 0-10 VDC Isolated CHARM
Specifications for LS AI 0-10 VDC Isolated CHARM
Sensor types Voltage device
Full Scale signal range See Table below
Accuracy See Table below
Input Impedance 10 M
Repeatability 0.05% of span
Resolution 24 bit A/D converter / Refer to the following table
Calibration None required
Common mode rejection 90dB at 50/60 Hz
Isolation Input channel galvanically isolated and factory tested to 1000
VDC
CHARM power req. 18 mA max @ 24 VDC
CHARM Heat Dissipation 0.40 Watts
Simplified Circuit and Connection Diagram for LS AI 0-10 VDC Isolated CHARM
Note: Installing a 250 range resistor across terminals 3 and 4 converts a 4-20 mA field signal to 1-5V input signal
DeltaV SIS Product Data Sheet
October 2014 Page 28 DeltaV SIS with Electronic Marshalling
LS Discrete Input NAMUR CHARM
Specifications for LS DI NAMUR CHARM
Sensor Types NAMUR Sensors, Dry Contacts, Dry contact with end of line
resistance
Detection level for On > 2.1 mA (<4 k)
Detection level for Off < 1.2 mA (>9 k)
Channel Impedance 1.5 K (approximate)
Wetting Voltage 12 Volts ( 5%)
Fault Detection capable NAMUR Sensors or field resistor pack
Guaranteed short circuit: <100
Guaranteed good status: 400 to 40 k
Guaranteed open circuit: > 75 k
Configurable channel types:
Discrete input Dry contact or discrete state sensor changing <2 Hz
Field Circuit Protection - 8 mA Current Limiting Circuit
- Field wiring disconnect
CHARM power req. 24 mA max @ 24 VDC
CHARM Heat Dissipation 0.51 Watts
Simplified Circuit and Connection Diagram for LS DI 24 VDC low-side sense CHARM
DeltaV SIS Product Data Sheet
October 2014 Page 30 DeltaV SIS with Electronic Marshalling
LS Discrete Input 24 VDC Isolated CHARM
Specifications for LS DI 24 VDC Isolated CHARM
Detection level for On > 10 VDC
Detection level for Off < 5 VDC
Wetting Current 6 mA @ 24 VDC
Input Impedance 4 K (approximately)
Isolation Galvanically isolated and factory tested to 1000 VDC
Configurable channel types:
Discrete input Dry contact or discrete state sensor changing <2 Hz
Field Circuit Protection - Recommend External Fuse at power source
- Field wiring disconnect
CHARM power req. 8 mA max @ 24 VDC
CHARM Heat Dissipation 0.32 Watts
Simplified Circuit and Connection Diagrams for LS DI 24 VDC Isolated CHARM with 3-wire DI Fused Injected Power Terminal
Block
DeltaV SIS Product Data Sheet
October 2014 Page 31 DeltaV SIS with Electronic Marshalling
LS 24 VDC Power CHARM
Specifications for LS 24 VDC Power CHARM
Device Type 24 VDC Power output
Detection level for On > 10 VDC
Detection level for Off < 5 VDC
Isolation Status read back circuitry is optically isolated and factory tested to
1000 VDC. Output power has no isolation from the injection point.
Field Circuit Protection - 2 Amp fuse located in Fused Injected Power Terminal Block
- Field wiring disconnect
CHARM power req. 8 mA max @ 24 VDC
Injected power req. 1.01 Amps max @ 24 VDC
CHARM Heat Dissipation 0.32 Watts
Simplified Circuit and Connection Diagrams for LS 24 VDC Power CHARM with Fused Injected Power Terminal Block
DeltaV SIS Product Data Sheet
October 2014 Page 32 DeltaV SIS with Electronic Marshalling
Simplified Circuit and Connection Diagrams for LS 24 VDC Power CHARM with Fused Injected Power Terminal Block -
powering 3-wire HART Transmitter connected to LS AI HART CHARM 0/ 4 to 20 mA
Simplified Circuit and Connection Diagrams for LS 24 VDC Power CHARM with Fused Injected Power Terminal Block -
powering 4-wire HART Transmitter connected to LS AI HART CHARM 0/ 4 to 20 mA
DeltaV SIS Product Data Sheet
October 2014 Page 33 DeltaV SIS with Electronic Marshalling
LS Discrete Output 24 VDC DTA CHARM
Specifications for LS 24 VDC DTA CHARM
Device Type 24 VDC Solenoid coils
ON-State Output rating 500 mA continuous @ 24 VDC. The power is derived from power
supplied to the CHARMs Smart Logic Solver Carrier
ON-State Current Limit Output inrush current limited to 580 mA
OFF-State Leakage Current 5 mA maximum.
Line Fault Detection Levels Guaranteed Short Circuit: < 10 Load
Guaranteed Good Status: 56 to 3.5 k Load
Guaranteed Open Circuit: > 20 k Load
Line Fault Test Timing 200 sec
Field Circuit Protection - 580 mA Current Limiting Circuit
- Field wiring disconnect
Field Power Common Shutoff Signal Logic low removes field power like in de-energize to trip applications
CHARM power req. 41 mA max @ 24 VDC
CHARM Heat Dissipation 1.3 W
Simplified Circuit and Connection Diagram for LS DVC HART DTA CHARM with LS DVC Terminal Block
DeltaV SIS Product Data Sheet
October 2014 Page 36 DeltaV SIS with Electronic Marshalling
LS Discrete Output 24 VDC Redundant DTA CHARM
Specifications for LS DO 24 VDC Redundant DTA CHARM
Device Type 24 VDC Solenoid coils
ON-State Output rating 500 mA continuous @ 24 VDC. The power is derived from power
supplied to the CHARMs Smart Logic Solver Carrier
ON-State Current Limit Output inrush current limited to 1.16 A
OFF-State Leakage Current 5 mA maximum.
Line Fault Detection Levels Guaranteed Short Circuit: < 10 Load
Guaranteed Good Status: 56 to 3.5 k Load
Guaranteed Open Circuit: > 20 k Load
Line Fault Test Timing 200 sec
Field Circuit Protection - 1.16 A Current Limiting Circuit
- Field wiring disconnect
Field Power Common Shutoff Signal Logic low removes field power from both partners like in de-energize to
trip applications
CHARM power req. 82 mA max.(109 mA when used with Relay Terminal block) @ 24 VDC
CHARM Heat Dissipation 2.6 W
DeltaV SIS Product Data Sheet
October 2014 Page 37 DeltaV SIS with Electronic Marshalling
Simplified Circuit and Connection Diagram for LS DO 24 VDC Redundant DTA CHARM with LS Redundant Terminal Block
DeltaV SIS Product Data Sheet
October 2014 Page 38 DeltaV SIS with Electronic Marshalling
Simplified Circuit and Connection Diagram for LS DO 24 VDC Redundant DTA CHARM with LS Redundant DTA Fused
injected Power Terminal Block
DeltaV SIS Product Data Sheet
October 2014 Page 39 DeltaV SIS with Electronic Marshalling
Simplified Circuit and Connection Diagram for LS DO 24 VDC Redundant DTA CHARM with LS Redundant DTA Relay
Terminal Block
DeltaV SIS Product Data Sheet
October 2014 Page 40 DeltaV SIS with Electronic Marshalling
LS Discrete Output 24 VDC Redundant ETA CHARM
Specifications for LS DO 24 VDC Redundant ETA CHARM
Device Type 24 VDC Solenoid coils
ON-State Output rating 500 mA continuous @ 24 VDC. The power is derived from power
supplied to the CHARMs Smart Logic Solver Carrier
ON-State Current Limit Output inrush current limited to 1.16 A
OFF-State Leakage Current 5 mA maximum.
Line Fault Detection Levels Guaranteed Short Circuit: < 10 Load
Guaranteed Good Status: 56 to 3.5 k Load
Guaranteed Open Circuit: > 20 k Load
Line Fault Test Timing 200 sec
Field Circuit Protection - 1.16 A Current Limiting Circuit
- Field wiring disconnect
Field Power Common Shutoff Signal Logic low removes field power from both partners like in de-energize to
trip applications
CHARM power req. 82 mA max.(109 mA when used with Relay Terminal block) @ 24 VDC
CHARM Heat Dissipation 2.6 W
DeltaV SIS Product Data Sheet
October 2014 Page 41 DeltaV SIS with Electronic Marshalling
Simplified Circuit and Connection Diagram for LS DO 24 VDC Redundant ETA CHARM with LS Redundant Terminal Block
DeltaV SIS Product Data Sheet
October 2014 Page 42 DeltaV SIS with Electronic Marshalling
Simplified Circuit and Connection Diagram for LS DO 24 VDC Redundant ETA CHARM with LS Redundant ETA
RelayTerminal Block
DeltaV SIS Product Data Sheet
October 2014 Page 43 DeltaV SIS with Electronic Marshalling
LS DVC HART Redundant DTA CHARM
Specifications for LS DVC HART Redundant DTA CHARM
Device Type Digital Vallve Controller
Nominal Signal Range (Span) 4 to 20 mA, (0 to 20 mA option)
Full Signal Range 0 to 24 mA
Accuracy over temperature range 2% of span (0 to 60 C)
5% of span (-40 to 70 C)
Resolution 12 bits
Calibration None required
Available field power 20 mA at 15 VDC supply into 250 min. to 600 max. load
Field Circuit Protection - 24 mA Current Limiting Circuit
- Field wiring disconnect
Field Power Common Shutoff Signal Logic low removes field power from both partners like in de-energize
to trip applications
CHARM power req. 86 mA max @ 24 VDC
CHARM Heat Dissipation 2.06 W
HART support HART v7 pass-through for AMS
HART v7 variable and device status available to control
HART data update rates 500 ms
DeltaV SIS Product Data Sheet
October 2014 Page 44 DeltaV SIS with Electronic Marshalling
Simplified Circuit and Connection Diagram for LS DVC HART DTA CHARM with LS Redundant DVC Terminal Block
DeltaV SIS Product Data Sheet
October 2014 Page 45 DeltaV SIS with Electronic Marshalling
LS Discrete Input 120 VAC Isolated CHARM
Specifications for LS DI 120 VAC Isolated CHARM
Detection level for On > 84 VAC
Detection level for Off < 34 VAC
Wetting Current 2 mA at 120 VAC
Input Impedance 60 K (approximately)
Maximum Input Voltage 130 VAC
Frequency 50/60 Hz
Isolation Each channel is optically isolated from the system at 250 VAC
Configurable channel types:
Discrete input Dry contact or discrete state sensor changing <2 Hz
Field Circuit Protection - Recommend External Fuse at power source
- Field wiring disconnect
CHARM power req. 8 mA max @ 24 VDC
CHARM Heat Dissipation 0.41 W
Simplified Circuit and Connection Diagrams for LS DI 120 VAC Isolated CHARM
Simplified Circuit and Connection Diagrams for LS DI 120 VAC Isolated CHARM with 3-wire DI Fused Injected Power Terminal
Block
DeltaV SIS Product Data Sheet
October 2014 Page 46 DeltaV SIS with Electronic Marshalling
LS Discrete Input 230 VAC Isolated CHARM
Specifications for LS DI 230 VAC Isolated CHARM
Detection level for On > 168 VAC
Detection level for Off < 68 VAC
Wetting Current 1 mA at 230 VAC
Input Impedance 240 K (approximately)
Maximum Input Voltage 250 VAC
Frequency 50/60 Hz
Isolation Each channel is optically isolated from the system at 250 VAC
Configurable channel types:
Discrete input Dry contact or discrete state sensor changing <2 Hz
Field Circuit Protection - Recommend External Fuse at power source
- Field wiring disconnect
CHARM power req. 8 mA max @ 24 VDC
CHARM Heat Dissipation 0.40 W
Simplified Circuit and Connection Diagrams for LS DI 230 VAC Isolated CHARM
Simplified Circuit and Connection Diagrams for LS DI 230 VAC Isolated CHARM with 3-wire DI Fused Injected Power Terminal
Block
DeltaV SIS Product Data Sheet
October 2014 Page 47 DeltaV SIS with Electronic Marshalling
System Compatibility
DeltaV SIS with Electronic Marshalling hardware requires:
SZ Controllers
LS-CHARMs
AC power filter/suppressor
DeltaV SIS Product Data Sheet
October 2014 Page 48 DeltaV SIS with Electronic Marshalling
Certifications
The following certifications are available for DeltaV SIS with Electronic Marshalling:
CE:
- EMC- EN 61326-3-1:2006
- LVD: Directive 2006/95/EC Aug 2007
FM:
CSA:
ATEX:
- ATEX 94/9/EC
- EN60079-0: 2009
- EN60079-15:2005
- EN60079-15:2010
IEC-Ex:
- IEC60079-0:2007
- IEC60079-15:2005
- IEC60079-15:2010
DeltaV SIS Product Data Sheet
October 2014 Page 49 DeltaV SIS with Electronic Marshalling
Certifications
DeltaV SIS with Electronic Marshalling will be submitted for the following certifications:
Marine Certifications:
FM (USA):
cFM (Canada):
ATEX:
IEC-Ex:
To locate a sales office near you, visit our website at: For large power, water, and wastewater applications
www.EmersonProcess.com/DeltaV contact Power and Water Solutions at:
Or call us at: www.EmersonProcess-powerwater.com
Asia Pacific: 65.6777.8211 Or call us at:
Europe, Middle East: 41.41.768.6111 Asia Pacific: 65.6777.8211
North America, Latin America: +1 800.833.8314 or Europe, Middle East, Africa: 48.22.630.2443
+1 512.832.3774 North America, Latin America: +1 412.963.4000
Emerson Process Management 2014. All rights reserved. For Emerson Process Management trademarks and service marks, go to:
http://www.emersonprocess.com/home/news/resources/marks.pdf.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be
construed as warrantees or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed
by our terms and conditions, which are available on request. We reserve the right to modify or improve the design or specification of such products at any time
without notice.
www.DeltaVSIS.com