Beruflich Dokumente
Kultur Dokumente
! WARNING:
Do not store or use gasoline or other
flammable vapors and liquids in the
vicinity of this or any other appliance.
Improper installation, adjustment,
alteration, service or maintenance can
cause injury, property damage, or
death. Refer to this manual. For
assistance or additional information
consult a qualified dealer or service
agency. To avoid personal injury or
property damage, ask a service
technician to inspect the furnace and
to replace any part of the control
system which has been under water.
! CAUTION:
SECTION 1. OWNER
No user serviceable parts inside
INFORMATION control panel. DO NOT OPEN.
OPERATING INSTRUCTIONS
• All power supply switches for furnace and
Before Operating System outside unit (if installed) are turned on.
• Furnace door is closed and properly latched.
Before operating your heating/cooling system
(see Figure 1), make sure that: Refer to the owner’s manual supplied with the
optional heat pump or air conditioner for further
• Control panel covers are closed.
information.
• Blower and/or relay control plugs are
plugged in.
• Fan switch is set to “AUTO” (E2EH units
only).
• Circuit breakers are in “ON” position.
Temperature Selector
10 20 30 Temperature
50 60 70 80 90 Scales
Fan Switch
(optional sub-base)
Blower Selector
Switch (EH only)
Blower
A/C or H/P
Relay Box
(optional)
Circuit Breakers
Data Label
Control Panel
Cover (left)
E 2 EB - 010 H - A
Product Type
E - Electric Furnace Options
A - A/C Ready
Generation
2 - Second Series
Electrical Code
Product Identifier H - 240-1-60
EH - Heat Only Primary Capacity
EB - A/C Blower Equipped 010 - 10 kw 012 - 12 kw
015 - 15 kw 017 - 17 kw
020 - 20 kw 023 - 23 kw
Model Identification
2
for several hours with all air registers open.
! CAUTION: 2. With system on, check temperature in all
rooms.
For optional A/C or H/P systems, 3. Partially close registers in rooms that are
always wait at least five minutes after too warm (in heating mode) or too cool (in
the system shuts off before restarting cooling mode) and in rooms that are infre-
quently occupied.
the system. Observe this procedure
4. Re-check room temperature and adjust
when operating the system per the registers as needed.
following instructions.
To Shut Off System
To Operate System in Cooling 1. Make sure blower selector switch is on
“Auto”.
Mode 2. Set thermostat temperature selector to low-
NOTE: The “FAN ON/FAN AUTO” (fan switch) est temperature setting, OR...
and “HEAT/OFF/COOL” (system switch) are 3. For thermostats with optional sub-base (see
located either on your thermostat (if it’s supplied Figure 1, Item 2) or for systems with relay
with a sub-base) or on the relay box added to box, set system switch to “OFF.”
your furnace.
3
3. Have a qualified serviceman inspect all Optional air conditioners and heat pumps are
furnace components and field wiring and listed by Underwriters’ Laboratories (UL) or
clean and service heating system as Environmental Testing Laboratories (ETL) and
needed. If this furnace was installed with certified by ARI and the Canadian Standards
aluminum power supply wiring, have ser- Association (CSA), or Warnock Hersey or ETLC.
viceman periodically check all connections These cooling systems include energy-saving
to prevent possible equipment failure and/ components to provide maximum cooling per-
or fire hazard. Do not attempt any service formance at electrical energy usage levels es-
function yourself which requires opening tablished by federal standards. Refer to the
furnace control panel covers. operation instruction label on your furnace for
the optional air conditioning equipment approved
BEFORE YOU CALL A SERVICEMAN for your heating appliance.
1. Make sure thermostat temperature selec-
tor is set above room temperature for heat- SECTION 2.
ing or below room temperature for cooling. INSTALLER INFORMATION
If thermostat is equipped with heating/cool-
ing sub-base, make sure system switch GENERAL
(see Figure 1, Item 2) is set to “HEAT” for
furnace operation or set to “COOL” for These instructions and specifications are pri-
optional air-conditioning operation. marily intended to assist qualified individuals
2. Check main household service panel to experienced in the proper installation of home
see if appropriate circuit disconnect(s) for heating and air conditioning appliances. Some
appliance power supply is on. local codes require licensed personnel for the
3. Refer to instructions under Before Operat- installation and service of this type of equip-
ing System for pre-operation checks. ment. Approved installation, operation, and
4. Refer to instructions under Before Each maintenance of this central heating system
Heating Season for maintenance proce- appliance must be in accordance with the listed
dures and recommended service checks. specifications contained in these instructions
5. Refer to owner’s manual provided with and other documents supplied with the furnace
optional air conditioner or heat pump (if and/or optional air conditioning equipment. Refer
installed) for service and maintenance. to local authorities having jurisdiction for further
information.
NOTE: All servicing of this heating appliance
other than the normal maintenance described in Before beginning installation, read these in-
this section must be done by authorized trained structions thoroughly. Follow all warnings and
service personnel. Do not open the control cautions in the instructions and on the unit.
panels (see Figure 1, Item 1) at any time.
Improper installation, service adjustment, or
Please specify the complete model and serial maintenance can cause explosion, fire, electri-
numbers shown on the furnace data label (see cal shock or other conditions which may result in
Figure 1, Item 1) for all warranty service and personal injury or property damage. Unless
when ordering replacement parts or optional otherwise noted in these instructions, use only
equipment. Refer to the replacement parts list factory-authorized kits and accessories when
provided with the furnace for part numbers. modifying this product.
4
For typical non-ducted return air downflow 2. Record furnace model number and serial
applications, an air-conditioner or heat-pump number (see furnace data label) for future
coil can be installed by mounting the coil directly reference.
on top of the furnace without adding sheet metal 3. Carefully read all instructions supplied with
cavities or cutting and trimming wood panels. optional equipment to be installed with
furnace.
A return air grille for closet or alcove installations
is available. For downflow alcove installations, CODES, SPECIFICATIONS, AND
the grille (with frame provided) may be attached REQUIREMENTS
to the top of the furnace and all paneling and trim
flushed to it. This installation provides an ac-
cess door for future installation of NORDYNE Furnace Codes
air conditioning or heat pump coils on top of the Installation and wiring of this furnace, as well as
furnace. the design and construction of the home duct
system, must be in accordance with one or more
Power entrance for all models may be through of the following codes:
the right side or through the bottom of the unit • HUD MANUFACTURED HOME CON-
(when viewing the unit in a downflow position). STRUCTION AND SAFETY STANDARD
(Title 24, Part 3280)
UNIT CHECKOUT • American National Standards (ANSI)
Before installing this furnace: A119.11, C1-NFPA 7 (National Electrical
1. Inspect unit for possible shipping damage. Code)
If shipping damage is found, file claim with • CANADIAN STANDARDS (C.S.A.) Z240.6.1,
transportation company. and Z240.9.1.
Accessibility for Servicing Minimum of 18" (46 cm) required in front of unit.
Minimum Clearance to 0" from all surfaces of furnace cabinet, ducts,
Combustibles optional coil housing and plenum connector.
No separate subbase required for installations on
combustible flooring.
2 2
Minimum return air 200 in. (1290 cm ) heating only*
opening required (total free
2 2
area) 235 in (1516 cm ) A/C or H/P up to 4-ton installed.*
2 2
390 in. (2516 cm ) A/C or H/P up to 5 ton installed.
*or return air grille and frame assembly
p/n 902989 or wall mount grille p/n 902999.
Use return air grille and frame assembly P/N 902989-
Return air grille or equivalent for alcove installation.
Use wall mount return air grilled P/N 902999- or
(closet or alcove installation) equivalent for closet installation.
2 2
155 in. (1000 cm ) must be added for
5-ton A/C or H/P system.
Table 1. Miscellaneous Listings & Installation Requirements
5
All local codes having jurisdiction shall also • Wiring materials located in return duct sys-
apply. tem must conform to NEC Article 300-22(c).
• Gas piping must not run in or through return
Air Duct Codes and Specifications air duct system.
• If return air opening is located below top of
Air ducts must be installed in accordance with
furnace, a minimum clearance must be pro-
National Fire Protection Association standards
vided between opening and furnace (see
NFPA 90A and NFPA 90B, these instructions,
“Accessibility for servicing” in Table 1).
and all applicable local codes.
• Materials: Air ducts must be aluminum, tin
plate, galvanized sheet steel, or other ap- Closed-Off Space Requirements
proved materials for outlet or return air ducts. Living space not served by, and closed off from,
• Construction: Snap-Lock or Pittsburgh-Lock the return air ducts to the furnace by doors,
seams are preferred. All other types of sliding partitions, and other means must be
seams must be made tight to prevent leak- provided with permanent, uncloseable open-
age. ings in the doors or partitions to allow air to
• Sizing: Supply duct system must be designed return to the furnace from all parts of the home.
for proper air distribution. Static pressure Return air grilles, with a minimum open area of
measured externally to furnace shall not ex- one square inch for every five square feet of
ceed static pressure rating listed on furnace living space closed off from the furnace, must be
nameplate. provided in the door or room partition.
• Location of Openings: Duct system must be
designed so that no supply registers are OPTIONAL EQUIPMENT
located in duct system directly below furnace.
Contact your nearest NORDYNE distributor for
a complete list of electric furnace accessories.
Return Air Codes and
Requirements Return Air Grille
Non-ducted return air systems may be used for A return air grille and frame assembly (see
closet or alcove installations. Figure 2) is available for use in non-ducted
return air installations. In downflow alcove in-
NOTE: Applicable installation codes may limit stallations, the grille and frame assembly may
the furnace to installation in a single-story resi- be mounted directly to the top of the furnace. In
dence only. Furnace installations other than closet installations, a wall mount grille is avail-
closet or alcove installations require ducted able for attachment to a door or wall.
return air systems.
Optional Automatic Furnace
Air return to the furnace must have a minimum
free area opening (see Table 1). Damper #901083 -
Furnace may (not required) be equipped with
Acceptable floor or ceiling return air systems for the optional automatic damper when a pack-
closet installations with return air entering aged air conditioner is installed and connected
through an opening in the closet floor or ceiling to the warm air duct system. This damper pre-
must meet all of the following requirements: vents cooled air from discharging through the
• Return air opening into closet, regardless of furnace cabinet, causing excessive cooling of
its location, must not be smaller than size the immediate area. Refer to instructions sup-
specified on unit data label. plied with the damper for details.
• If located in floor of closet, return air opening
must be provided with means of preventing Multi-Speed Blower Conversion
its inadvertent closure by a flat object placed Package (4 or 5 ton):
over opening.
• Materials located in return air duct system Upgrade blower packages are available for
must have a flame-spread classification of adding air conditioning or heat pump systems.
200 or less. See furnace “Options and Compatibility” label
• Noncombustible pans having 1" upturned for systems available.
flanges must be located beneath openings in
a floor-return duct system.
6
8 Item
Number
7 (See Fig. 1) Description
1 4-Speed Blower
4 27" 4 Ton - See Notes: 1 & 5
(686 mm) 5 Ton - See Note: 1
2 A.C./H.P. Relay Control
See Note: 1
3 Cabinet Insulation Kit
1 See Notes: 1 & 5
2
4 "A"-Coil Conversion Kit
29"
See Note: 2
(737 mm) 5 Coil Cabinet
3
See Note: 3
6 Upflow Stand
See Note: 4
23
(603 3/4" 20" 7 A/C and H/P Indoor Coils
mm) m)
(508 m 8 Return Air Grille and
Frame Assembly
20"
(508
Cabinet mm
Insulation ) Notes:
1) For A/C and H/P use.
2) Includes coil filters.
3) For upflow or downflow installations.
29" 4) For upflow A/C or H/P installations (includes
(737 mm) one filter; use filter from furnace to
complete filtering system in this accessory).
5) Standard in EB models.
5 Coil Cabinet
20" 11/16"
(50
8m (17 mm)
m) 20-1/8"
(511 mm)
3"
(76 mm)
14"
(357 mm)
)
mm
" (603
233/4
Filters (one obtained Figure 3. Optional Rear Mounting Plate
from furnace) (P/N 389080)
6 Upflow Stand
7
Electric Furnace Models E2EH E2EB
8
010H 012H 015H 017H 020H 023H 010H 012H 015H 017H 020H 023H 023H 5 Ton
Rated Heating Output, Btuh
(see note1) 35,000 41,000 53,000 57,000 70,000 75,000 35,000 41,000 53,000 57,000 70,000 75,000 75,000
Watts (Total kw, Heating Elements
and Blower) 10.4 12.0 15.4 16.6 20.4 22.0 10.4 12.0 15.4 16.6 20.4 22.0 22.0
Supply Voltage 240 Volts/60Hz/1-Phase
Heating Elements, No.(Total kw) 2 (10.0) 2 (11.6) 3 (15.0) 3 (16.2) 4 (20.0) 4 (21.6) 2 (10.0) 2 (11.6) 3 (15.0) 3 (16.2) 4 (20.0) 4 (21.6) 4 (21.6)
Blower: Wheel Size 10.5" Dia., 8" Wide 10.5" Dia., 8" Wide 11" Dia., 8" W
Motor Speeds, H.P. Rating, Amps 2 Speed, 1/5 Hp, 2.0 Amps 4 Speed, 1/3 Hp, 2.9 Amps 4 Spd, 3/4 Hp, 3.8 Amps
Test ESP, in. w.c. Max 0.3
Optional Cooling Available with factory
2.0 - 3.0 ton (see note 3) 2.0 - 4.0 ton (see note 4) 2.0 - 5.0 Ton
installed blower
Optional Heat Pump Available with
2.0 - 3.0 ton (see note 3) n/a (see note 3) 2.0 - 4.0 ton (see note 4) 2.0 - 5.0 Ton
factory installed blower
Air Filter (Standard) 16" x 20" x 1" (nominal)
Furnace Dimensions Width - 20" (508 mm) Height - 29" (737 mm) ( see note 2) Depth - 24-1/2" (623 mm)
1. Heating output rated at listed voltage. For outputs at voltages other than 3. The factory installed blower for the EH models can be replaced with a multi-
240V, multiply Btuh rating by the following factors: x 0.92 (230V), x 0.84 speed blower allowing the units to accept up to 4 or 5 tons of air conditioning
(220V), x 0.75 (208V) or heat pump.
2. Height is 56" with return air grille installed, 58" with coil cabinet and 72" with 4. The factory installed blower for the EB models can be replaced with a multi-
coil cabinet and upflow stand. speed blower allowing the units to accept up to 5 tons of air conditioning or
heat pump.
FLOOR CAVITY
OPENING TO DUCT
A= 13-1/4" (337 mm) TOP VIEW
B= 10-3/4" (274 mm)
WITH PLATE (C) REMOVED 19”
Reducer (483 mm)
OPENING BECOMES
Felt Seal 13-1/4” x 13-1/4”
(483 mm)
C A
19"
Corner X
Spacers
2-3/8" MIN
(60 mm)
Furnace
Outline
14-1/2"
(368 mm)
17"
14-1/2"
(432 mm)
(368 mm)
16-5/8"
23-3/4" (422 mm)
(603 mm)
OptionaL
Supply Wire
Entrance
For 3" (76 mm)
3-3/4" Optional
(95 mm) A/C Or H/P
Refrigerant
Line
Opening
TABS
Narrow Duct
DUCT
2. BEND BOTTOM TABS OVER Duct
AND ONTO THE UNDER-
NEATH DUCT SURFACE
Figure 10. Alternate Plenum
Figure 9. Plenum Connector Installation A Connector Installation B
STEP 1. STEP 2.
Fold Back Flap "B" Fold Back Flap"B"
Cut
Lines Duct
Cut- Out "B" Cut- Out "B"
Area "A" Area"A"
"A" "A"
"B"
"B"
Top of Duct
Fold Back Flap"B"
Fold Back Flap "B"
STEP 3. STEP 4.
Bend Plenum Connector Tabs Up Staple Folded Duct
and Over- (along length of duct) Flap (typ) to side of
Plenum Connector
Duct Duct
Flap "B" Duct
Coil Air
Filters
27"
(686 mm)
56"
(1423 mm)
A/C or H/P
Coil
29"
Wall-Mount
24 3/4"
( 737 mm) Return Air Grille
(629 mm)
Closet
Door
20"
(508 mm)
Floor
Figure 12. Typical Alcove Installation Figure 13. Typical Closet Installation
11, area “A”), bend the plenum tabs and 1. Cut return air opening in desired position in
secure them directly to the duct. door or wall, preferably above top of fur-
4. At area “B”, bend the plenum tabs up and nace. Refer to Table 1 for return air opening
back over, around the plenum connector requirements.
(see Figure 11, step 3). 2. Insert four fasteners, securing grille to door
5. Fold/form the duct flap against the side of or wall.
the plenum connector and attach as shown
(see Figure 11, Step 4). Use at least three Furnace Installation
staples on each duct flap OR... if a 2X 1. Install 240V supply circuit(s) and 24V wir-
block/joist is not provided, use at least two ing to closet or alcove (see Figure 14 for
sheet metal fasteners on each duct flap. appropriate locations).
6. Tape the duct flap edges with an approved 2. Remove refrigerant line knockouts in fur-
tape for a leak-free joint. nace only when installing indoor coil of an
air conditioner or heat pump system, or for
Alcove Installation hook-up of a VentilAire accessory when the
1. Cut alcove rough openings to minimum furnace is used in the upflow position. Refer
dimensions shown in Figure 12. to instructions supplied with accessory
2. Attach frame assembly with four fasteners equipment.
(provided or equivalent) into pre-punched 3. Remove unit front door and slide back until
holes on top of furnace (see Figure 5). bottom slots in rear of unit engage with both
3. At manufacturers discretion, if additional tabs of optional rear mounting plate, OR...
securement is required attach each side of If mounting plate is not used, an equivalent
frame assembly to alcove opening using method of securing the rear of the unit may
holes provided. be used as long as it prevents displace-
4. Attach return air grille to frame assembly by ment during transport if used in a manufac-
hooking grille over flange on top of frame tured home.
and into channel on bottom. NOTE: The furnace does not need to be hard up
against the rear mounting plate. The tabs will
Closet Installation engage into the slots and allow approximately
1/2” of furnace front to back and right to left.
NOTE: For closet installations, the return air
grille mounting frame is not used since the fur-
nace is located inside the closet (see Figure 13).
13
trances
Low Voltage Wire En
Power
Supply
Wire Refrigerant
Entrances Line
Knockouts
Power
Supply Blower Selector
Wire Switch (EH Only)
Refrigerant Entrances
Line Knockouts
Blower Selector
Tie Down Tab
Tie-Down Tab
Switch (EH Only) (See Inset) Low Voltage
Wire Entrances
DOWNFLOW INSTALLATION UPFLOW INSTALLATION
Figure 14. Downflow and Upflow Installations
4. Secure front of unit with one or more fas- NOTE: Refer to the instructions supplied with
teners at mounting hole(s) provided or at any additional accessories for further installa-
tie-down tab (see Figure 14). tion details.
5. See Electrical System Installation to com-
plete furnace installation. Filtering Methods - Non-Ducted Return Air
1. Without optional upflow stand: (see Figure 16)
TYPICAL INSTALLATION OF -install a filter with a minimum unrestricted
UPFLOW SYSTEMS medium area of 324 square inches below
the coil cabinet/furnace assembly that is
The following steps describe installation in- accessible for monthly cleaning or replace-
structions for an overhead supply duct system ment by the homeowner
with a return air system that can be either over
the floor (non-ducted) or through the floor 2. With optional upflow stand: (see Figure 15)
(ducted). -stand must use two filters; one is supplied
with the stand and the other MUST be
NOTES: removed from the furnace and placed in the
• Before installing this furnace, consider all stand - see upflow stand instructions for
clearances for the installation and future ser- additional details.
vicing of the furnace. Refer to Table 1.
• The 2 Wire Relay Control is NOT recom- Filtering Methods - Ducted Return Air
mended for upflow applications, instead, the 1. Install a filter with a minimum unrestricted
AC/HP Relay Control (4-7 wire) should be medium area of 324 square inches below
used when converting some models to ac- the coil cabinet/furnace assembly that is
cept an air conditioner. See Relay Control accessible for monthly cleaning or replace-
installation instructions for further details. ment by the homeowner
14
Over-the-Floor Return Air System
Upflow Duct
(Non-Ducted) Connector
1. If floor underneath furnace is made of com-
bustible material, locate a pan fabricated of
non-combustible material with 1" upturned
flanges under furnace return air opening Furnace
(see Figure 16). Ensure that return air
passage has no openings through support-
ing structure that would permit flame or hot
gases to travel from space below up into
space above supporting structure.
2. Use optional upflow stand with filters or
construct a suitably braced mounting plat-
form in closet (see Figure 15 or 16).
3. Install 240V supply circuit(s) and 24V wir-
ing to closet (see Figure 14 for appropriate
locations). Upflow Stand
4. Position optional coil cabinet onto upflow
stand or mounting platform and secure with Filters
three or more fasteners.
5. Position furnace in upflow mode onto coil
cabinet and secure with two or more fasteners.
6. Use optional upflow duct connector or field Figure 15. Over-the-Floor Return Air
supplied connector to attach furnace to System with Upflow Stand
overhead supply duct. (see Figure 15)
7. Install return air grille in closet preferably at Coil Cabinet
same level as upflow stand or below mount-
ing platform (see Figure 16).
15
REAR WALL OF ENCLOSURE
CENTER LINE
1 3/4" MIN
(45 mm)
17 1/2" Furnace
18 5/8" (445 mm) Outline
(474 mm)
14"
23 3/4" (356 mm)
(604 mm)
3 1/8"
(80 mm)
For Optional
A/C Or H/P
3/4"
(20 mm) 5 3/4" 3"
(147 mm) (73 mm)
Furnace
Outer Door 20"
(508 mm)
16
4. Insert supply service wire(s) through cable
connector(s) and connect wires to circuit
breakers (Figures 18 and 19).
! WARNING:
NOTE: To install single-circuit kit, perform To avoid personal injury or property
step 5. If single-circuit kit installation is not damage, make certain that the motor
necessary, go to step 6. leads cannot come into contact with
5. To install single-circuit kit:
non-insulated metal components of the
a. Loosen lugs at supply side of circuit
breakers. unit.
b. Remove cover from single-circuit kit (if
supplied). Selecting Blower Speed
c. Insert metal buss bars of kit into lugs of
See Table 5 for the lowest speed approved for
circuit breaker.
the heating output of the unit. Since the blower
d. Tighten lugs securely (45 in.-lbs.
leads connect to the control box, blower speed
recommended).
selection is accomplished through use of the
6. Connect service ground wire(s) to ground-
proper color-coded blower lead located inside
ing lug(s) provided. One ground is required
the control box. The speed(s) set by the factory
for each supply circuit used.
may be different from that shown on the wiring
diagrams. See the unit control box for blower
speed(s) set at factory.
Circuit Breaker
Bracket Optional
Circuit Single Circuit
Breaker Adaptor Kit
Wire
60A
OFF
ON
Assemblies
(Factory
Installed) Supply Service
60A
OFF
ON
Wire Connection
With Single Circuit
Adaptor Kit
Circuit Breaker
Bracket
Circuit
Breaker
Wire
60A
OFF
Assemblies
ON
ON
Without Single
Circuit Adaptor Kit
17
Installing Control Circuit Wiring
! IMPORTANT: NOTE: Installation of a five-wire thermostat
circuit is recommended to provide for future
If a relay box is installed, blower speeds addition of a heat/cool thermostat.
for heating and cooling are set inside 1. Install the 24V control-circuit cable through
the relay box (see instructions plastic bushing at either side of furnace.
included with relay box). The blower a. For models without a relay box, connect
speed inside the furnace control box wires to furnace at blower plug pigtails (see
must be set to low or medium-low. wiring diagrams). Secure all connections
Never change to a heating speed lower with wire nuts.
b. For units with a relay box installed, make
than that shown in Table 5. wiring connections at relay box low-voltage
terminal board. (See relay box installation
Changing Blower Speed instructions.)
E2EH: The selected heating blower lead is 2. Route control circuit wiring to wall
thermostat and outdoor section, if installed.
attached to the wire lead attached to terminal 2
(See relay box installation instructions if
of the blower selector switch.
applicable.)
a. Remove blower lead from the wire lead off
3. Set anticipator per Table 8 or per the
of terminal 2.
b. Choose desired speed. marking on the unit.
4. See the back cover of this manual for E2EB
c. Attach new blower lead to wire lead off
thermostat connections.
terminal 2 of blower selector switch.
18
Sizes*
Model Max Over- Min. 75°C Copper Low-Voltage
E2EH/ Supply Total Current Circuit Thermostat Wire
E2EB- Circuit Amperes Rating Ampacity Wire Size Ground Size Size
010 Single 45.5 60 57 6 10
012 Single 52.1 70 65 6 8
Dual "A" 28.0 40 35 8 10 2-Wire
"B" 24.2 30 30 10 10 system max
wire lengths :
015 Single 66.3 90 83 4 8 24 Ga. = 55’
Dual "A" 45.5 60 57 6 10 22 Ga. = 90’
"B" 20.8 30 26 10 10 20 Ga. = 140’
18 Ga. = 225’
017 Single 71.3 90 89 3 8
Dual "A" 48.8 60 61 6 10 4 or more-Wire
"B" 22.5 30 28 10 10 system max
wire lengths :
020 Single 87.1 125 109 2 6
24 Ga. = 25’
Dual "A" 45.5 60 57 6 10 22 Ga. = 45’
"B" 41.7 60 52 6 10 20 Ga. = 70’
18 Ga. = 110’
023 Single 93.8 125 117 1 6
Dual "A" 45.5 60 57 6 10
"B" 48.3 60 60 6 10
* All wire sizes for copper conductors only, based on NEC Table 310-16. Equivalent wiring may be used per NEC.
Table 6. Electrical Specifications
NOTES:
1) See unit data label for recommended supply wire sizes. 5) If any wire in this unit is to be replaced it must be CB-A CB-A
2) Thermostat anticipator setting: 0.20 Amps. replaced with 105°C thermoplastic copper wire of Grey 5
Black 4 IFM
3) To change blower speeds on units without a relay box refer the same gauge. Blue 3
to installation instructions. 6) Not suitable for use on systems exceeding 120V to Yellow 2 H C 6 Org.
Red 1 L
4) Refer to furnace and/or relay box installation for thermo- ground. IFS
stat connections. IFS
7) This wire is used with some accessories. See acces-
sory Installation Instructions for further details.
Seq 1 E LS
C
BLACK BLOWER Seq 1 Top - 10.0
1 SWITCH H L
WHITE
2 (See
GREY
Figure 20. E2EH 010 Wiring Diagrams
RED
ORANGE Transformer
BLACK
RED
BROWN
1 2 3
6 5 4 3 2 1
24V
4 5 6
BLOWER Seq
SPEED
Fuse 2
SELECTOR
6 5 4 3 2 1 1 2 3 4 1
BLUE
YELLOW
RED
LEADS 4 5 6
BLACK
White Pig-Tail 3
TRANSFORMER
WHITE
240V
24V
RED
GRAY
RED
GRD Ground
Supply
BLACK Legend:
Line
BLACK Circuit A
60A
OFF
IFM – Fan Motor
ON
Voltage
TOP ELEMENT, 10.0 KW
M1
CIRCUIT
CB – Circuit Breaker
M2
2
BREAKER E – Heater Element
BLACK 4
M4 M3 IFS – Fan Switch
GREY ELEMENTS 3 1
LIMIT
! WARNING: Seq – Sequencer
SEQUENCER
IFR – Fan Relay
BLACK
RED
Switch circuit breakers to LS – Limit Switch
RED the OFF position beore – Fan Plug
servicing the furnace. – Control Plug
NOTES:
CB-B CB-B
1) See unit data label for recommended supply wire sizes. 5) If any wire in this unit is to be replaced it must be
2) Thermostat anticipator setting: 0.20 Amps. replaced with 105°C thermoplastic copper wire of
3) To change blower speeds on units without a relay box refer the same gauge. E
to installation instructions. 6) Not suitable for use on systems exceeding 120V to
4) Refer to furnace and/or relay box installation for thermo- ground.
stat connections. 7) This wire is used with some accessories. See CB-A CB-A
accessory Installation Instructions for further details. Grey
Black
5
IFM
4
Blue 3
Yellow 2 H C 6 Org.
IFS Red 1 L
IFS
BLOWER
C
Figure 21. E2EH 012 Wiring Diagrams
SWITCH E LS
BLACK 1
Legend:
WHITE
H L (See Note 7) Seq 1 Top - 11.6
GREY
YELLOW 2 IFM – Fan Motor
3
RED
CB – Circuit Breaker 240V
ORANGE
LEADS 3
4 5 6 – Fan Plug
BLUE
240V WHITE
BLACK
60A
OFF
24V Single
ON
RED
GRAY Supply
BLACK
(standard)
60A
OFF
ON
TOP ELEMENT, 11.6 KW GRD Ground
CIRCUIT
M2 M1 BREAKERS
OR
M4 M3 4 2
1 Circuit B
Line
! WARNING:
60A
3 Voltage
ON
OFF
GREY ELEMENTS
LIMIT
Dual
Ground
SEQUENCER BLACK
GRD
Supply Switch circuit breakers to
RED
Line (optional)
Circuit A the OFF position beore
60A
OFF
RED Voltage
ON
BLACK
GRD Ground servicing the furnace.
21
22
to installation instructions. 6) Not suitable for use on systems exceeding 120V to Seq 2 Bottom -
5.0/5.4
4) Refer to furnace and/or relay box installation for thermo- ground.
CB-A CB-A
stat connections. 7) This wire is used with some accessories. See acces- Grey 5
Black 4 IFM
sory Installation Instructions for further details. Blue 3
Yellow 2 H C 6 Org.
IFS Red 1 L
IFS
BLOWER C
WHITE
GREY
SWITCH
BLACK (See Note 7)
1 Seq 1 LS
Figure 22. E2EH 015, 017 Wiring Diagrams
H E
RED
2 L
YELLOW Seq 1 Top -
3
ORANGE 10.0/10.8
240V
BLACK
1 2 3
! WARNING:
RED
4 5 6 Transformer
BROWN
6 5 4 3 2 1
Switch circuit breakers to 24V
BLOWER Fuse Seq
SPEED 6 5 4 3 2 1 1 2 3 the OFF position beore 4
2
1
YELLOW
SELECTOR 4 5 6
servicing the furnace.
BLUE
LEADS
RED
TRANSFORMER
240V BLACK Line
WHITE Circuit B
60A
Voltage
ON
OFF
24V
GREY RED
RED GRD Ground Dual
BLACK
BLACK
BLACK
Supply
Circuit A Line
60A
ON
OFF
BLACK Voltage
M1 TOP ELEMENT, 10.0/10.8 KW
M2
GRD Ground
Legend:
2 CIRCUIT
4
M4 M3 BREAKERS
OR IFM – Fan Motor
3 1
GREY
RED
CB – Circuit Breaker
GREY
BOTTOM ELEMENT, 5.0/5.4 KW E – Heater Element
M6 M5
IFS – Fan Switch
WHITE
60A
Single
OFF
ON
ELEMENTS Seq – Sequencer
LIMITS
Supply IFR – Fan Relay
BLACK RED
(optional) LS – Limit Switch
60A
SEQUENCER
OFF
ON – Fan Plug
Ground
GRD
– Control Plug
NOTES: CB-B CB-B
1) See unit data label for recommended supply wire sizes. 5) If any wire in this unit is to be replaced it must be
2) Thermostat anticipator setting: 0.40 Amps. replaced with 105°C thermoplastic copper wire of
3) To change blower speeds on units without a relay box refer the same gauge. Seq 2 E LS
to installation instructions. 6) Not suitable for use on systems exceeding 120V to Seq 2 Top -
4) Refer to furnace and/or relay box installation for thermo- ground. 10.0/11.6
CB-A CB-A
stat connections. 7) This wire is used with some accessories. See Grey 5
IFM
accessory Installation Instructions for further details. Black
Blue
4
3
Yellow 2 H C 6 Org.
IFS Red 1 L
IFS
BLOWER C
WHITE
GREY
SWITCH
(See Note 7)
Figure 23. E2EH 020, 023 Wiring Diagrams
BLACK 1 Seq 1 E LS
H
2 L
YELLOW Seq 1 Btm - 10.0
RED
3
ORANGE
! WARNING: 240V
BLACK
1 2 3
RED
BROWN
4 5 6 Transformer
BLOWER
6 5 4 3 2 1
Switch circuit breakers to 24V
SPEED
SELECTOR 6 5 4 3 2 1 1 2 3 the OFF position beore Fuse
2
Seq
LEADS 1
YELLOW
RED 4 5 6
RED
BLACK
White Pig-Tail Seq
2
GREY 3
RED RED Red Pig-Tail Grey Pig-Tail
FUSE (See Note 7)
VIOLET ORANGE RED
TRANSFORMER RED
240V BLACK Line
WHITE BLACK Circuit B
60A
Voltage
ON
OFF
24V
GRAY
RED GRD Ground Dual
BLACK RED
Supply
Circuit A Line
60A
ON
OFF
Voltage
M6 M5
4 2 BREAKERS
OR Legend:
GREY
M8 M7
IFM – Fan Motor
BLACK
BLACK
3 1
ELEMENTS
RED CB – Circuit Breaker
60A
Single
OFF
ON
WHITE BOTTOM ELEMENT, 10.0 KW
E – Heater Element
M2 M1
Supply
4 2
(optional)
IFS – Fan Switch
M4 M3
60A
OFF
Seq – Sequencer
ON
3 1
ELEMENTS
SEQUENCER
LIMITS
GRD
Ground IFR – Fan Relay
RED
GREY BLACK
LS – Limit Switch
– Fan Plug
– Control Plug
23
24
NOTES:
Red Jumper Wire
1) See unit data label for recommended supply wire sizes. 5) If any wire in this unit is to be replaced it must be CB-A (See note 8)
CB-A
2) Thermostat anticipator setting: 0.20 Amps. replaced with 105°C thermoplastic copper wire of Grey 5
Black 4 H IFM
3) To change blower speeds on units without a relay box refer the same gauge. IFR Blue 3 MH
6) Not suitable for use on systems exceeding 120V to Yellow ML C 6 Org.
to installation instructions. Red
2
L
IFR 1
4) Refer to furnace and/or relay box installation for thermo- ground.
stat connections. 7) This wire is used with some accessories. See acces-
sory Installation Instructions for further details.
Seq 1 E LS
GREEN
WHITE
H
GREY
MH 240V
ML
Figure 24. E2EB 010 Wiring Diagrams
L
Transformer
RED
ORANGE
YELLOW
24V
BLACK
BLUE
1 2 3
RED
BLACK 4 5 6
Fuse Seq
2
BLOWER 6 5 4 3 2 1 4 1
1
SPEED
5 2 BLOWER
RELAY SELECTOR White Pig-Tail
3 6 4 6 5 4 3 2 1 1 2 3
LEADS
YELLOW
Green Pig-Tail
BLACK
BLUE
BLACK
Grey Pig-Tail
Red Pig-Tail 5 IFR
GREEN
GREY 3
VIOLET RED
FUSE
ORANGE
TRANSFORMER
GREY
240V WHITE
24V
GREY
RED
GRD Ground
Supply
RED Legend:
BLACK
BLACK Circuit A
Line IFM – Fan Motor
60A
OFF
ON
Voltage
TOP ELEMENT, 10.0 KW CB – Circuit Breaker
GREY
M2 M1 E – Heater Element
CIRCUIT
BLACK 4 2 Seq – Sequencer
M4 M3
3 1
BREAKER
! WARNING: IFR – Fan Relay
ELEMENTS LIMIT LS – Limit Switch
SEQUENCER
Switch circuit breakers to – Fan Plug
BLACK
RED the OFF position beore – Control Plug
RED servicing the furnace.
NOTES: CB-B CB-B
1) See unit data label for recommended supply wire sizes. 5) If any wire in this unit is to be replaced it must be
2) Thermostat anticipator setting: 0.20 Amps. replaced with 105°C thermoplastic copper wire of
3) To change blower speeds on units without a relay box refer the same gauge. E
to installation instructions. 6) Not suitable for use on systems exceeding 120V to
4) Refer to furnace and/or relay box installation for thermo- ground. Red Jumper Wire
(See note 8)
CB-A
stat connections. 7) This wire is used with some accessories. See acces- Grey
CB-A
5
sory Installation Instructions for further details. Black
Blue
4 H IFM
MH
IFR 3
Yellow 2 ML C 6 Org.
C
Switch circuit breakers to
WHITE
GREEN
E
GREY
H LS
Figure 25. E2EB 012 Wiring Diagrams
MH
the OFF position beore ML
L Seq 1 Top - 11.6
servicing the furnace.
RED
ORANGE 240V
YELLOW
BLACK
BLACK Transformer
BLUE
1 2 3
RED
4 5 6
24V
6 5 4 3 2 1
BLOWER Fuse Seq
1 5 2 SPEED 2
BLOWER 4 1
3 6 4 RELAY SELECTOR 6 5 4 3 2 1 1 2 3
YELLOW
BLACK
LEADS
BLUE
BLACK
Green Pig-Tail
Grey Pig-Tail
GREEN Red Pig-Tail 5 IFR
GREY
RED 3
FUSE
VIOLET ORANGE RED
TRANSFORMER
GREY
240V WHITE
BLACK
60A
OFF
24V
Single
ON
RED
GREY
Supply
BLACK
(standard) Legend:
60A
OFF
ON
TOP ELEMENT, 11.6 KW IFM – Fan Motor
M2M1 Ground
CIRCUIT
BREAKERS
GRD
CB – Circuit Breaker
4 2 OR
E – Heater Element
GREY
M4 M3
ELEMENTS
3 1
Line Seq – Sequencer
Circuit B
60A
LIMIT Voltage
IFR – Fan Relay
ON
OFF
SEQUENCER Dual
BLACK
RED Ground LS – Limit Switch
GRD
Supply
RED – Fan Plug
Circuit A Line (optional)
60A
BLACK
OFF
Voltage
– Control Plug
ON
25
GRD Ground
26
stat connections. 7) This wire is used with some accessories. See acces- Grey
Black
5
4 H IFM
sory Installation Instructions for further details. IFR Blue
Yellow
3
2
MH
ML C 6 Org.
IFR Red 1 L
WHITE
GREEN
GREY
C
H
MH Seq 1 E LS
Figure 26. E2EB 015, 017 Wiring Diagrams
ML L
Top -
! WARNING: Seq 1
10.0/10.8
RED
240V
YELLOW
ORANGE
BLACK
BLACK 1 2 3
BLUE
Switch circuit breakers to Transformer
RED
4 5 6
6 5 4 3 2 1 1 2 3 4 1
LEADS
YELLOW
RED 4 5 6
BLUE
(See Note 7)
RED
3
VIOLET ORANGE RED
TRANSFORMER
240V BLACK Line
WHITE Circuit B
60A
Voltage
ON
OFF
BLACK
24V
GRAY
RED
RED
GRD Ground Dual
BLACK Supply
BLACK Circuit A Line
60A
ON
OFF
Voltage
BLACK TOP ELEMENT, 10.0/10.8 KW
M1
M2 CIRCUIT GRD Ground
M4 M3
4 2 BREAKERS
OR
Legend:
GREY 3 1 IFM – Fan Motor
RED
BOTTOM ELEMENT, 5.0/5.4 KW
CB – Circuit Breaker
M6 M5
E – Heater Element
60A
Single
OFF
ON
WHITE
ELEMENTS
LIMITS Supply Seq – Sequencer
BLACK RED (optional) IFR – Fan Relay
60A
OFF
ON
SEQUENCER LS – Limit Switch
GREY
GRD
Ground – Fan Plug
– Control Plug
NOTES: CB-B CB-B
1) See unit data label for recommended supply wire sizes. with 105°C thermoplastic copper wire of the same
2) Thermostat anticipator setting: 0.40 Amps. gauge. LS
Seq 2 E
3) To change blower speeds on units without a relay box refer 6) Not suitable for use on systems exceeding 120V to
Seq 2 Top -
to installation instructions. ground. 10.0/11.6
4) Refer to furnace and/or relay box installation for thermo- 7) This wire is used with some accessories. See acces- CB-A Red Jumper Wire
(See note 8) CB-A
Grey 5
stat connections. sory Installation Instructions for further details. Black 4 H IFM
IFR Blue 3 MH
5) If any wire in this unit is to be replaced it must be replaced Yellow
Red
2 ML
L
C 6 Org.
IFR 1
GREEN
WHITE
Seq 1 E LS
GREY
H
Figure 27. E2EB 020, 023 Wiring Diagrams
MH
ML
L
Seq 1 Btm - 10.0
RED
240V
ORANGE
! WARNING:
YELLOW
BLACK
Transformer
BLUE
1 2 3
RED
BLACK
4 5 6
24V
BLOWER 6 5 4 3 2 1 Switch circuit breakers to Fuse Seq
5 2 BLOWER SPEED
1
3 6 4
RELAY SELECTOR
6 5 4 3 2 1
the OFF position beore 4 1
BLACK
LEADS 1 2 3
servicing the furnace.
YELLOW
3
RED RED
FUSE
VIOLET ORANGE RED
TRANSFORMER RED
240V WHITE
BLACK
Line
BLACK Circuit B
60A
Voltage
ON
OFF
24V
RED
GREY
RED GRD Ground Dual
Supply
Circuit A Line
60A
ON
OFF
Voltage
BLACK TOP ELEMENT, 10.0/11.6 KW
BLACK
M6 M5
Ground
4 2 CIRCUIT GRD
Legend:
BREAKERS
GREY
M8 M7 OR
BLACK
BLACK
ELEMENTS
3 1 IFM – Fan Motor
RED CB – Circuit Breaker
BOTTOM ELEMENT, 10.0 KW
M2 M1 E – Heater Element
60A
Single
OFF
ON
4 2
Seq – Sequencer
WHITE
M4 M3
1 Supply
ELEMENTS 3
(optional)
IFR – Fan Relay
60A
LIMITS OFF LS – Limit Switch
ON
SEQUENCER RED
BLACK
GREY
Ground
– Fan Plug
GRD
– Control Plug
27
5-Wire Thermostat 4-Wire Thermostat
W Y RC RH G W Y R G
Wire Wire
nuts To A/C nuts To A/C
White
White
Green
Grey
Grey
Red
Red
e n
re
G
1 2 3 4 5 6 1 2 3 4 5 6
Green
White
Red
Unstripped
Wire Wires
nuts To
Wire A/C
nuts
White
Green
Grey
Grey
Red
1 2 3 4 5 6 1 2 3 4 5 6
¢7077166¤
707716C
707716C (Replaces 707716B)