Contents
Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Application Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
General Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Catalog Numbering System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Dimensions and Terminal Data . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Product Description Incoming
from Switchboard
The Cutler-HammerT Maintenance Bypass Switch is a ULT 1008
listed device that provides a simple and effective means for bypass- UPS
Input Breaker
ing uninterruptible power supplies (UPS) while maintaining continuity
of power to the critical computer loads. A Maintenance Bypass Switch
is a requirement on every UPS installation in order to accommodate
UPS
the maintenance and testing of the UPS system. System
Application Description
The most typical applications of the Maintenance Bypass Switch are MBH
on Static or Rotary type UPS systems of 50 kVA or greater. Lockout
Circuit
Computer
Static UPS systems may require maintenance to the inductors or Loads
the capacitors that are needed for f ltering and SCR commutation.
Motor Generator systems, while extremely reliable, require more FIGURE 1. APPLICATION WITH STATIC UPS SYSTEM
maintenance to the mechanical moving parts. Bearings and
couplings need to be greased and examined to ensure proper
functioning. Incoming MBH
from Bypass
The Cutler-Hammer Maintenance Bypass Switch is the f rst to offer Switchboard
a UL 1008 listing. As a transfer switch it carries a 100% rating and is Critical
compatible with UPS systems up to 750 kVA at 480 volts. Loads
Normal Output
Features Lockout
Circuit Battery
UL 1008 listing File E131767.
Make-before-break electrical operation. Synchronous Synchronous
DC
Motor Generator
Lockout circuit to be wired into the UPS bypass authorization. Generator Motor
Pilot devices to show UPS position Normal and Bypassed.
Pilot device to show Lockout enabled.
FIGURE 2. APPLICATION WITH ROTARY UPS SYSTEM
Reliable manually initiated electrical operation.
High interrupting ratings are standard.
TABLE 1. KVA RATING, FULL LOAD CURRENT AND
Solid neutral connections are standard. MAINTENANCE BYPASS SWITCH SIZE CROSS-REFERENCE
CHART
Unauthorized bypass is prevented by the need of UPS system to 30 83.3 100 36.1 100
send the bypass authorized signal. 50 139 150 63 100
65 180 225 81 100
100% current ratings make selection to the UPS kVA ratings 75 208 225 90 100
easy to accomplish. 100 278 300 120 150
Use of high interrupting rating switches or breakers makes the 125 347 400 150 225
Maintenance Bypass Switches adaptable to systems with high 150 416 600 180 225
levels of available fault current. 200 555 600 240 300
225 625 800 271 300
250 722 800 301 400
General Specifications 300 833 1000 361 400
350 972 1000 420 600
Frequency 60 Hz.
400 480 600
Line characteristics: 450 540 600
500 601 800
Nominal line voltage +15%, -25%
600 720 800
Operating temperature: 750 902 1000
0C 70C
32F 160F
Storage temperature -20C 85C.
Humidity 95% noncondensing.
2 EATON Maintenance Bypass Switch Technical Data TD01602002E Effective: March 2016
TABLE 2. TRANSFER SWITCH EQUIPMENT CATALOG NUMBERING SYSTEM
MB H E FD A 3 0030 A S U
Transfer Mechanism
Note: To attain the maximum rating shown in the chart, when protected by an upstream breaker, the upstream device must have an
equivalent interrupting rating.
Detail A
E D
C TABLE 4. OUTLINE DIMENSIONS IN INCHES (MM) FOR NEMA 1
ENCLOSURE
AMPERES A B C D E F G H
100 150 22.88 13.13 22.74 22.62 24.50 9.78 10.28 32.31
1.75 (581.2) (333.5) (577.6) (574.5) (622.3) (248.4) (261.1) (820.7)
(44.5)
225 400 38.88 29.13 35.74 35.62 37.50 17.28 17.78 55.81
(987.6) (739.9) (907.8) (907.8) (952.5) (438.9) (451.6) (1417.6)
600 1000 38.88 29.13 49.74 49.62 51.50 17.28 17.78 55.81
H
F (987.6) (739.9) (1263.4) (1260.3) (1308.1) (438.9) (451.6) (1417.6)
1.25
(31.8) G
100 150 HFD (1) #14 1/0 (1) #14 1/0 (1) #14 1/0 (3) #14 1/0
225 300 HKD (1) #3 350 (1) #3 350 (1) #6 350 (3) #4 350
400 HLD (1) 4/0 600 (1) 4/0 600 (2) #1 500 (6) 250 350
600 NB (3) 3/0 400 (3) 3/0 400 (3) 3/0 400 (12) 4/0 500
800 NB (4) 4/0 500 (4) 4/0 500 (4) 4/0 500 (12) 4/0 500
1000 NB (4) 4/0 500 (4) 4/0 500 (4) 4/0 500 (12) 4/0 500
Eaton
Electrical Sector
1000 Eaton Boulevard Cleveland, OH 445122
United States
877-ETN CARE (877-386-2273) option 2, option 4, and then option 3
Eaton.com
2016 Eaton
All Rights Reserved
Printed in USA
Publication No. TD01602002E / TBG
March 2016