Thank you for purchasing the UT32A Digital Indicating Controller (Entry model). l Power Supply 30 Rear of
This operation guide describes the basic operations of the UT32A. The guide should Ensure that the instruments supply voltage matches the voltage controller
be provided to the end user of this product. of the power supply before turning ON the power.
Be sure to read this operation guide before using the product in order to ensure WARNING l Do Not Use in an Explosive Atmosphere
Do not operate the instrument in locations with combustible
Note
correct operation.
For details of each function, refer to the electronic manual. Before using the product, or explosive gases or steam. Operation in such environments If the instrument is moved from a location with low temperature and low humidity
refer to the table of Model and Suffix Codes to make sure that the delivered product constitutes an extreme safety hazard. Use of the instrument in to a place with high temperature and high humidity, or if the temperature changes
is consistent with the model and suffix codes you ordered. Also make sure that the environments with high concentrations of corrosive gas (H2S,
rapidly, condensation will result. Moreover, in the case of thermocouple inputs,
following items are included in the package. SOX, etc.) for extended periods of time may cause a failure.
l Do Not Remove Internal Unit measurement errors will result. To avoid such a situation, leave the instrument in the
The internal unit should not be removed by anyone other than new environment under ambient conditions for more than 1 hour prior to using it.
Digital Indicating Controller (the model you ordered)...............................x1
Set of Brackets.........................................................................................x1 YOKOGAWA's service personnel. There are dangerous high voltage
parts inside. Additionally, do not replace the fuse by yourself. Do not mount the instrument in the following locations:
Unit Label (L4502VZ)...............................................................................x1
l Damage to the Protective Construction
Tag Label (L4502VE)...............................................................................x1 Authorised Representative in the EEA Outdoors
Operation of the instrument in a manner not specified in the
(Only when ordered.) users manual may damage its protective construction. Yokogawa Europe BV. (Address: Euroweg 2 , 3825 HD Amersfoort, The Nether- Locations subject to direct sunlight or close to a heater
Operation Guide (this document).............................................................x5 (A3 size) lands) is the Authorised Representative of Yokogawa Electric Corporation for this Install the instrument in a location with stable temperatures that remain close to an
(Installation and Wiring, Initial Settings, Operations, and Parameters) Product in the EEA. average temperature of 23C. Do not mount it in locations subject to direct sunlight
Printed Manuals or close to a heater. Doing so adversely affects the instrument.
l Target Readers Locations with substantial amounts of oily fumes, steam, moisture, dust, or
This guide is intended for the following personnel; This instrument is an EMC class A product. In a domestic environ-
Model Description
corrosive gases
Engineers responsible for installation, wiring, and maintenance of the equipment. UT35A/UT32A Digital Indicating Controller Operation Guide (Standard code model) IM 05P01D31-11EN
ment this product may cause radio interference in which case the The presence of oily fumes, steam, moisture, dust, or corrosive gases adversely
UT35A/UT32A Digital Indicating Controller Operation Guide (Detailed code model) IM 05P01D31-15EN
Personnel responsible for normal daily operation of the equipment. user needs to take adequate measures.
UT35A/MDL, UT32A/MDL Controller (Mount on DIN Rail) Operation Guide IM 05P01D81-11EN affects the instrument. Do not mount the instrument in locations subject to any of
CAUTION (Standard code model) these substances.
1. Safety Precautions UT32A-D Digital Indicating Controller (Dual-loop type) Operation Guide IM 05P08D31-11EN Areas near electromagnetic field generating sources
UT32A-D/MDL Controller (Dual-loop type, Mount on DIN Rail) Operation Guide IM 05P08D81-11EN Do not place magnets or tools that generate magnetism near the instrument. If the
The following symbol is used on the instrument. It indicates the possibility of injury to
the user or damage to the instrument, and signifies that the user must refer to the users
2. Model and Suffix Codes UT35A/RSP, UT32A/RSP Digital Indicating Controller (Non-isolated RSP)
Operation Guide (Standard code model)
IM 05P01D31-81EN
instrument is used in locations close to a strong electromagnetic field generating
UT32A Digital Indicating Controller (Entry model) Operation Guide (Standard code model) IM 05P01F31-11EN source, the magnetic field may cause measurement errors.
manual for special instructions. The same symbol is used in the users manual on pages Locations where the display is difficult to see
Precautions on the Use of the UTAdvanced Series IM 05P01A01-11EN
that the user needs to refer to, together with the term WARNING or CAUTION. UT32A (Entry model) The instrument uses an LCD for the display unit, and this can be difficult to see
Optional
Electronic Manuals from extremely oblique angles. Mount the instrument in a location where it can be
Model Suffix code suffix Description You can download the latest manuals from the following website: seen as much as possible from the front.
Calls attention to actions or conditions that could cause serious code URL: http://www.yokogawa.com/ns/ut/im/ Areas close to flammable articles
Digital Indicating Controller (Power supply: 100-240 V
or fatal injury to the user, and indicates precautions that should be UT32A
AC) (provided with 2 DOs)
Model Description Absolutely do not place the instrument directly on flam-
taken to prevent such occurrences. UT35A/UT32A Digital Indicating Controller Operation Guide (Standard code model) IM 05P01D31-11EN mable surfaces. If such a circumstance is unavoidable
Type 1: -V Voltage pulse output type 150 mm
WARNING UT35A/UT32A Digital Indicating Controller Operation Guide (Detailed code model) IM 05P01D31-15EN
Basic -C Current output type and the instrument must be placed close to a flammable
control UT35A/MDL, UT32A/MDL Controller (Mount on DIN Rail) Operation Guide IM 05P01D81-11EN item, provide a shield for it made of 1.43 mm thick plated
-R Relay output type
(Standard code model) 150 mm 150 mm
Type 2: 0 None steel or 1.6 mm thick unplated steel with a space of at 150 mm
Calls attention to actions or conditions that could cause injury to UT35A/UT32A Digital Indicating Controller Users Manual IM 05P01D31-01EN
the user or damage to the instrument or property and indicates pre-
Functions 1 RS-485 communication (Max. 38.4 kbps, 2-wire/4-wire) (*1)
UT32A-D Digital Indicating Controller (Dual-loop type) Operation Guide IM 05P08D31-11EN least 150 mm between it and the instrument on the top,
cautions that should be taken to prevent such occurrences.
Type 3: Fixed code 0 None
UT32A-D/MDL Controller (Dual-loop type, Mount on DIN Rail) Operation Guide IM 05P08D81-11EN bottom, and sides.
-1 English (Default. Can be switched to other language by the setting.) UT32A-D, UT32A-D/MDL Digital Indicating Controller Users Manual IM 05P08D31-01EN Areas subject to being splashed with water
CAUTION
-2 German (Default. Can be switched to other language by the setting.) UT35A/RSP, UT32A/RSP Digital Indicating Controller (Non-isolated RSP) IM 05P01D31-81EN
Display language (*2)
AC -3 French (Default. Can be switched to other language by the setting.) Operation Guide (Standard code model)
-4 Spanish (Default. Can be switched to other language by the setting.) UT32A Digital Indicating Controller (Entry model) Operation Guide (Standard IM 05P01F31-11EN
code model) Be sure to turn OFF the power supply to the controller before in-
0 White (Light gray)
AC/DC Case color
1 Black (Light charcoal gray) UT32A Digital Indicating Controller (Entry model) Users Manual (Standard code model) IM 05P01F31-01EN stalling it on the panel to avoid an electric shock.
Fixed code -00 Always "-00" UTAdvanced Series Communication Interface (RS-485, Ethernet) Users Manual IM 05P07A01-01EN
The equipment wholly protected by double insulation or reinforced insulation. WARNING
/LP 24 V DC loop power supply UTAdvanced Series Communication Interface (Open Network) Users Manual IM 05P07A01-02EN
/DC Power supply 24 V AC/DC LL50A Parameter Setting Software Installation Manual IM 05P05A01-01EN
Optional suffix codes LL50A Parameter Setting Software Users Manual IM 05P05A01-02EN
Functional grounding terminals /CT Coating (*3)
Terminal cover Precautions on the Use of the UTAdvanced Series IM 05P01A01-11EN
(Do not use this terminal as a protective grounding terminal). /CV
YOKOGAWA ELECTRIC CORPORATION
General Specification
Note *1: When the /LP option is specified, the RS-485 communication of the Type 2 code 1 is 2-wire
system.
Network Solutions Business Division
Model Description 2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 JAPAN
*2: English, German, French, and Spanish are available for the guide display.
Identifies important information required to operate the instrument. *3: When the /CT option is specified, the UT32A does not conform to the safety standards (UL
UT35A/UT32A Digital Indicating Controller GS 05P01D31-01EN YOKOGAWA CORPORATION OF AMERICA
and CSA) and CE marking (Products with /CT option are not intended for EEA-market). UT35A/MDL, UT32A/MDL Controller (Mount on DIN Rail) GS 05P01D81-11EN Head office and for product sales
UT32A-D Digital Indicating Controller (Dual-loop type) GS 05P08D31-01EN 2 Dart Road, Newnan, Georgia 30265, USA
Warning and Disclaimer UT32A-D/MDL Controller (Dual-loop type, Mount on DIN Ral) GS 05P08D81-01EN YOKOGAWA EUROPE B.V.
(1) YOKOGAWA makes no warranties regarding the product except those stated in
LL50A Parameter Setting Software GS 05P05A01-01EN Headquarters
the WARRANTY that is provided separately. Euroweg 2, 3825 HD Amersfoort, THE NETHERLANDS
* The last two characters of the manual number and general specification number indicate the
(2) The product is provided on an "as is" basis. YOKOGAWA assumes no liability to language in which the manual is written.
www.yokogawa.com/ns
any person or entity for any loss or damage, direct or indirect, arising from the
use of the product or from any unpredictable defect of the product. All Rights Reserved, Copyright 2015 Yokogawa Electric Corporation
IM 05P01F31-11EN page 1/10
Mounting the Instrument Main Unit 4. Hardware Specifications Allowable signal source resistance:
TC or mV input: 250 or less
EN 55011 Class A, Group 1
KC marking:
Provide an instrumented panel steel sheet of 1 to 10 mm thickness. Effects of signal source resistance: 0.1 V/ or less Electromagnetic wave interference prevention standard, electromagnetic wave
After opening the mounting hole on the panel, follow the procedures below to install DC voltage input: 2 k or less protection standard compliance
the controller: Effects of signal source resistance: About 0.01%/100
1) Insert the controller into the opening from the front of the panel so that the
This instrument is for Measurement Category No.1.
Allowable wiring resistance:
Construction, Installation, and Wiring
Do not use it for measurements in locations falling under Measure-
terminal board on the rear is at the far side. RTD input: Max. 150 /wire (The conductor resistance between the three wires Dust-proof and drip-proof: IP66 (for front panel) (Not available for side-by-side
ment Categories No.2, No.3, and No.4.
2) Set the brackets in place on the top and bottom of the controller as shown in the WARNING shall be equal.) close mounting.)
figure below, then tighten the screws of the brackets. Take care not to overtighten Wiring resistance effect: 0.1C/10 Material: Polycarbonate (Flame retardancy: UL94V-0)
them. Allowable input voltage/current: Case color: White (Light gray) or Black (Light charcoal gray)
Internal Wiring TC, mV, mA and RTD input: 10 V DC Weight: 0.5 kg or less
II External dimensions (mm): 48 (W) 96 (H) 65 (depth from the panel face)
Panel Bracket III T V input: 20 V DC
Entrance IV O( I ) (Depth except the projection on the rear panel)
(top mounting hardware)
Cable
mA input: 40 mA
Outlet Noise rejection ratio: Installation: Direct panel mounting; mounting bracket, one each for upper and
Normal mode: 40 dB or more (at 50/60 Hz) lower mounting
Direction to insert the
controller Terminal board Common mode: 120 dB or more (at 50/60 Hz) Panel cutout dimensions (mm): 45+0.6/0 (W) 92+0.8/0 (H)
IEC/EN/CSAUL
Insert the controller Category
61010-1: 2001
EN 61010-2-030 Remarks
For 100-240 V AC, the power frequency can be set manually. Automatic Mounting attitude: Up to 30 degrees above the horizontal. No downward titling allowed.
into the opening at
Measurement For measurements performed on circuits not direct- detection is also available. Wiring: M3 screw terminal with square washer (for signal wiring and power wiring)
the front of the panel. No.1 O (Other)
Category I ly connected to MAINS.
For 24 V AC/DC, the power frequency can be set manually.
Insert a screwdriver into the
brackets to tighten the screws. No.2
Measurement Measurement For measurements performed on circuits directly Reference junction compensation error: Power Supply Specifications and Isolation
Category II Category II connected to the low-voltage installation.
1.0C (15 to 35C), 1.5C (-10 to 15C and 35 to 50C) Power supply:
Measurement Measurement For measurements performed in the building instal-
Appropriate
No.3
Category III Category III lation. Applicable standards: JIS/IEC/DIN (ITS-90) for TC and RTD Rated voltage: 100-240 V AC (+10%/-15%), 50/60 Hz
Bracket tightening torque: Measurement Measurement For measurements performed at the source of the 24 V AC/DC (+10%/-15%) (for /DC option)
(bottom mounting hardware) 0.25 Nm
No.4
Category IV Category IV low-voltage installation. Analog Output Specifications (Suffix code: -C) Power consumption: 15 VA (DC:7 VA, AC: 11 VA if /DC option is specified)
Number of outputs: Data backup: Nonvolatile memory
Input Specifications Control output: 1 Power holdup time: 20 ms (for 100 V AC drive)
Output type: Current output Withstanding voltage
Tighten the screws with appropriate tightening torque within 0.25 Universal Input (Equipped as standard) Current output: 4 to 20 mA DC or 0 to 20 mA DC/load resistance of 600 or less Between primary terminals and secondary terminals: 2300 V AC for 1 minute (UL, CSA)
Nm. Otherwise it may cause the case deformation or the bracket
Number of inputs: 1 Current output accuracy: 0.1% of span (5% of span for 1 mA or less) Between primary terminals and secondary terminals: 3000 V AC for 1 minute (CE)
damage. Between primary terminals: 1500 V AC for 1 minute
CAUTION Make sure that foreign materials do not enter the inside of the Input type, instrument range, and measurement accuracy: See the table below, The accuracy is that in the standard operating conditions: 232C, 5510%RH,
Instrument Range and power frequency at 50/60 Hz. Between secondary terminals: 500 V AC for 1 minute
instrument through the cases slit holes. Input Type Accuracy (Primary terminals: Power* and relay output terminals; Secondary terminals:
C F
-270.0 to 1370.0C -450.0 to 2500.0F 0.1% of instrument range 1 digit for Analog Output Specifications (Suffix code: -V) Analog I/O signal terminals, communication terminals and functional
K -270.0 to 1000.0C -450.0 to 2300.0F 0C or more grounding terminals.)
External Dimensions and Panel Cutout Dimensions -200.0 to 500.0C -200.0 to 1000.0F
0.2% of instrument range 1 digit for Number of outputs: *: Power terminals for 24V AC/DC models are the secondary terminals.
less than 0C
J -200.0 to 1200.0C -300.0 to 2300.0F 2% of instrument range 1 digit for Control output: 1 Insulation resistance: Between power supply terminals and a grounding terminal
UT32A Unit: mm (approx. inch) Output type: Voltage pulse output
48 (1.89) -270.0 to 400.0C -450.0 to 750.0F less than -200.0C of thermocouple K 20 M or more at 500 V DC
11 (0.43) 65 (2.56) Bracket Terminal cover T 1% of instrument range 1 digit for Voltage pulse output: Isolation specifications
0.0 to 400.0C -200.0 to 750.0F less than -200.0C of thermocouple T
20 (0.79) Use: Time proportional output
0.15% of instrument range 1 digit PV (universal) input terminal
for 400C or more On-voltage: 12 V or more/load resistance of 600 or more
B 0.0 to 1800.0C 32 to 3300F
5% of instrument range 1 digit for Off-voltage: 0.1 V DC or less Control (voltage pluse, analog) output terminal
less than 400C
105.2 (4.14)
Time resolution: 10 ms or 0.1% of output, whichever is larger Control relay (c-contact) output terminal
91.6 (3.61)
94.6 (3.72)
96 (3.78)
This product Contact rating: 250 V AC, 3 A 104 304 204 b 202
30 V DC, 3 A (resistance load) - 203
A hazardous A hazardous
105 305
voltage circuit voltage circuit B 203
UTs contact Relay CR filter
106 306
ALM (Equipped
Functional
insulation Reinforced insulation (Use one with a relay coil (Mount it directly Contact output as standard)
Current (mA) input Voltage (mV, V) input
rating less than the UTs to the relay coil 107 207
A hazardous A hazardous
contact rating.) terminal (socket).) External contact output (relay)
voltage circuit voltage circuit 108 208 - 203 + 202
Alarm-2 output UT
(PV low limit) 106 109 + 204 - 203
Reinforced insulation AL2
Common 107 110
Alarm-1 output 111
(PV high limit) 108 Factory default:
When connecting two or more crimp-on terminal lugs to the AL1 112 PV input type is
Common 109 undefined.
single terminal block, bend the crimp-on terminal lugs before
tightening the screw. Relay contact rating: 240 V AC, 1 A
CAUTION Note that the wiring of two or more crimp-on terminal lugs to the 30 V DC, 1 A (resistance load)
single high-voltage terminal of the power supply and relay, etc.
does not comply with the safety standard.
Power supply (Suffix code: Type1=-V or -C)
100-240 V AC power supply 24 V AC/DC power supply (24 V AC/DC power supply: Control output OUT
Provide electricity from a single-phase power supply. If the Optional suffix code /DC)
power is noisy, install an isolation transformer on the primary N N Current/voltage pulse output
110 - 110
side, and use a line filter on the secondary side. When measures
CAUTION L L + 207
against noise are taken, do not install the primary and secondary 111 + 111 0-20 mA DC,
power cables close to each other. 4-20 mA DC,
112 112 Voltage pulse (12 V)
If there is a risk of external lightning surges, use a lightning - 208
arrester etc. Allowable range:
For TC input, use shielded compensating lead wires for wiring. 100-240 V AC (+10%/-15%)
For RTD input, use shielded wires that have low conductor (free voltage)
50/60 Hz shared
resistance and cause no significant differences in resistance
between the three wires.
Since the control output relay has a life span (resistance load of
100,000 times), use the auxiliary relay to perform ON/OFF control.
The use of inductance (L) loads such as auxiliary relays, motors
and solenoid valves causes malfunction or relay failure; always
insert a CR filter for use with alternating current or a diode for
use with direct current, as a spark-removal surge suppression
circuit, into the line in parallel with the load.
After completing the wiring, the terminal cover is recommended
to use for the instrument.
(F)
3. Quick Setting Function (Setting of Input and Output) Operation for Setting
Operation UT32A To select the parameter setting
Press the displayedkey.
SET/ENTER as the initial value, press the Down arrow
Guide Digital Indicating Controllers (Entry Model) The Quick setting function is a function to easily set the basic function of the controller.
4. key to move to the next parameter.
Operation Guide l
Turn on the controller to start the Quick setting function. To change and set the parameter setting, press the SET/ENTER key to start the
tiona This function allows you to easily set the control type and input, and quickly start the OFF blinks.
Func ment setpoint blinking. The blinking stateallows
allowsyou
you
Initial Settings Enha
nce Blinking to to make changes (setting mode).
control action. For time proportional output, you can set the cycle time. Use the Up/Down/Left/Rightchange
arrow keys to change the setpoint. Press the SET/EN-
the setting.
The items (parameters) to be set by Quick setting function are as follows. TER key to register the setting.
(1) Control type (PID control, ON/OFF control)
(2) Input function (PV input type, range, scale (at voltage input), etc.) Making Settings Using Quick Setting Function
Select NO to return to
(3) Output function (cycle time)
to PID the
Example: Setting Press Up arrow
control andkey.
thermocouple the Operation Display. of 0.0 to
type K (range
This operation guide describes basic settings and operations of the UT32A. (6)
For details of each function, see the electronic manual.
The scrolling guide is displayed on PV display in the Parameter Setting Display. (1)
After turning on the controller, first decide whether or not to use the Quick setting function. 5. 500.0 0
C)
(4) For the detailed procedure andK1switching of displays, see "Flow of Quick Setting
This guide can be turned on/off with the Fn key. is displayed.
Operation in Initial Display Function" below. For the parameters to set, see the next page.
For details of the each function, refer to the electronic manual. User's manuals can be
downloaded or viewed at the following URL. (2) Press the SET/ENTER key while YES is displayed to start the Quick setting function.
(5)
http://www.yokogawa.com/ns/ut/im/ If you change YES to NO and press the SET/ENTER key, Operation Display will (1) Press the SET/ENTER key while YES for QSM (Quick setting mode) is displayed.
(3)
appear without starting the Quick setting function. (2) Set the control type parameter (CNT) to PID (PID control).
No. in figure (3) Set the PV input type parameter (IN) to K1 (-270.0 to 1370.0 0C).
Contents Name Description
Used to switch the Operation Displays. (4) Set the PV input Press the SET/ENTER
unit parameter (UNIT)key.
to C (Degree Celsius).
1. Names and Functions of Display Parts (1) DISP key
Press the key in the Operation Display to switch the provided
Operation Displays.
6.
(5) Set the maximum value of PV input range parameter (RH) to 500.0.
(6) Set the minimum value of PV input range parameter (RL) to 0.0.
2. Setup Procedure Press the key in the Menu Display or Parameter Setting Display
to return to the Operation Display. K1 has been
(7) Finally, EXIT is displayed. Change NO registered.
to YES and press the SET/ENTER key to
3. Quick Setting Function (Setting of Input and Output)
Hold down the key for 3 seconds to move to the Operation complete the setup. Operation Display appears.
4. Setting Alarm Type
Parameter Setting Display.
5. Setting Alarm Setpoint Hold down the key and the Left arrow key simultaneously for 3
(2) PARA key seconds to move to the Setup Parameter Setting Display.
Press the key in the Parameter Setting Display to return to the
1. Names and Functions of Display Parts Press the Down arrow key.
Menu Display. Press the key once to cancel the parameter set- Flow of Quick Setting Function
ting (setpoint is blinking).
7. The PV input unit parameter (UNIT)
SET/ENTER key In Quick setting mode, the parameter guide appears on PV display. is displayed.
Press the key in the Menu Display to move to the Parameter
This guide can be turned on/off with the Fn key. Initial value: C (Degree Celsius)
Setting Display of the Menu. Press the key in the Parameter
(1) Setting Display to transfer to the parameter setting mode (setpoint
is blinking), and the parameter can be changed.
(2) Press the key during parameter setting mode to register the setpoint.
(3) SET/ENTER key Up/Down/Left/Right arrow keys Power-on
(8) (3) Up/Down/Left/Right Press the Left/Right arrow keys in the Menu Display to switch
Press the Down arrow key.
arrow keys the Displays.
(4) Press the Up/Down/Left/Right arrow keys in the Parameter 8. The upper limit value of the setting
(9) Setting Display to switch the Displays. Quick setting starts
(5) range is displayed for the param-
Press the Up/Down arrow keys during parameter setting mode
eter RH (maximum value of PV
(6) (setpoint is blinking) to change a setpoint. 1. input range).
Press the Left/Right arrow keys during parameter setting mode
(setpoint is blinking) to move between digits according to the parameter.
(10)
(7) It is the communication interface for the adapter cable used when [NO]
(4) Light-loader interface setting and storing parameters from a PC. The LL50A Parameter
Setting Software (sold separately) is required. [YES] Press the SET/ENTER key.
(9)
Status indicator REM Lit when in remote mode (REM). 5.
(green and red) STOP Lit when in stop mode (STOP).
Position YES YES Position K1 is displayed. Finally, EXIT is displayed.
Lit when in manual mode (MAN).
MAN
Blinks during auto-tuning.
proportional
type?
proportional
type? 12. Press the SET/ENTER key to swtich to the
setting mode.
(10) Security indicator (red) Lit if a password is set. The setup parameter settings are locked. NO For Position proportional type NO Change NO to YES and press the SET/ENTER
Valve position Output setup key to complete the setup of the basic function.
adjustment Operation Display appears. The Quick setting
Press the SET/ENTER key. function continues in the NO state.
6.
Operation Display
Other setup Set the other parameters as needed. K1 has been registered.
Displays the measured
input value (PV).
PID tuning Adjust PID using auto-tuning or manually for PID control. Displays the target
setpoint (SP).
Press the Down arrow key.
(PV low limit) is registered. Alarm setpoint Output Alarm setpoint Output Press the SET/ENTER key.
Parameter Symbol Name of Parameter Setting Range Symbol
After the setup is completed,
CT
Control output cycle
time
0.5 to 1000.0 s press the DISP key once to Feedback input high limit (27) Fault diagnosis alarm (30) 6. The setpoint has been registered.
Burnout of PV input, ADC failure, RJC error.
return to the Operation Display. After the setup is completed, press
Stand-by action Feedback input low limit (28)
the DISP key once to return to the
FAIL (31)
Energized/De-energized Operation Display.
For the factory default, the contact output is turned ON in normal operation,
Latch action PV velocity (29) OFF at the time of FAIL. Control output: OFF or 0%, Alarm output: OFF
Note 1: Open/closed shows status of relay contact, and lit/unlit shows status of EV (event) lamp.
To change the alarm type, change the last 2 digits of the Note 2: Positive setpoint, Negative setpoint
5-digit value.
Stand-by action and excitation are turned on or off by Setting Display of Alarm Type Stand-by Action Initializing parameter values
selecting 1 or 0. (See Setting Display of Alarm Type. )
For the latch action, see User s Manual. C Normal Abnormal Parameters that you have changed can be initialized to factory default values or user
Treated
as normal The alarm output default values. For details, see Parameter Initialization in the Users Manual.
turns on.
PV low limit
Alarm type alarm setpoint Changing the parameter display levels
Without (0) or With (1) The alarm output does not turn on
Stand-by action in this region even if the PV valule This operation guide does not explain all the parameters. To display all the param-
Energized (0) / De-energized (1) is below PV low limit alarm setpoint.
eters, you need to change the parameter display level to professional setting mode.
Latch action (0/1/2/3/4)
See Users Manual. For details, see Setting Security Functions in the Users Manual.
Power-on Time
5. 6.
This operation guide describes key entries for operating the UT32A. The setpoint has been registered.
For operations using external contact inputs, see DI of 6. Terminal Wiring Diagrams Press the DISP key once to return to
in Installation and Wiring.
If you cannot remember how to carry out an operation during setting, press the DISP 1. Show the SP Display (Operation Display).
(This is an example of setting the target
the Operation Display.
key once. This brings you to the display (Operation Display) that appears at power-on.
The scrolling guide is displayed on PV display in the Parameter Setting Display. setpoint to 150.0). OFF blinks.
This guide can be turned on/off with the Fn key.
For details of the each function, refer to the electronic manual. User's manuals can be 2. Press the SET/ENTER key to start the
downloaded or viewed at the following URL. last digit of the setpoint blinking. Press the Up/Down arrow keys to display the required setpoint.
Blinking allows you to change the value.
http://www.yokogawa.com/ns/ut/im/ 7.
6.
SPNO. has been changed to 2.
To set the setpoint, use the
3. Left/Right arrow keys to move
Contents between digits and the Up/Down
arrow keys to increase and
1. Monitoring-purpose Operation Displays Available during Operation decrease the value. Blinks during the change.
2. Setting Target Setpoint (SP) 4. When the required value is displayed,
The setting range is 1 to 4 (represent group numbers) or R.
3. Performing/Canceling Auto-tuning press the SET/ENTER key to register
To perform auto-tuning for the PID of group 1, set the parameter AT to 1.
4. Selecting Target Setpoint Numbers (SPNO.) the setpoint.
To quit the auto-tuning, set the parameter to OFF.
5. Switching between AUTO and MAN
6. Switching between RUN and STOP 5. Switching between AUTO and MAN
7. Switching between REM (Remote) and LCL (Local) Press the SET/ENTER key.
8. Manipulating Control Output in Manual Mode AUTO and MAN switching can be performed using any of the following: (1) A/M key,
9. Troubleshooting
7. The setpoint has been registered. (2) Communication, and (3) User function key.
This starts auto-tuning. The figure below shows a direct operation using the A/M key.
1. Monitoring-purpose Operation Displays Available during Operation The limiter can be set to the output during auto-tuning.
For details, see Users Manual.
Operation Display Switching Diagram
SP Display
3. Performing/Canceling Auto-tuning During auto-tuning,
Displays the measured input value on PV display. The MAN lamp blinks.
Displays the target setpoint (SP) on Setpoint display (SP can be changed). The OUT symbol appears.
Auto-tuning should be performed after setting a target setpoint. MAN lamp is lit
OUT Display The output values at 100.0% and
Displays the measured input value on PV display.
Make sure that the controller is in automatic mode (AUTO) and in run mode (RUN)
0% appear alternately. in MAN mode.
Displays the control output value (OUT) on Setpoint display (OUT can be changed before auto-tuning. For setting to AUTO, see 5. Switching between AUTO and
in manual mode). MAN, and for setting to RUN, see 6. Switching between RUN and STOP. 8.
Displays the valves feedback input value (at 0 to 100% valve opening) in Position If the setpoint is known in advance or auto-tuning does not find any appropriate PID
proportional control. constants, set the PID manually. For setting the PID manually, see Users Manual. Each time you press the key,
AUTO and MAN is switched alternately.
The MAN lamp goes off, which means that
the auto-tuning completed normally. When AUTO is switched into MAN, the control output value in AUTO mode is held.
Do not perform auto-tuning for the following processes.
The controller can be operated manually from the hold value.
Tune PID manually.
If the manual preset output is set (MPON parameter OFF), the controller can be
Processes with fast response such as flow rate control and pres-
CAUTION operated manually from the arbitrary output value (MPO1 to MPO5 parameters).
sure control.
Processes which do not allow the output to be turned on and off
even temporarily.
4. Selecting Target Setpoint Numbers (SPNO.) 6. Switching between RUN and STOP
Processes which prohibit severe output changes at control
SP Display OUT Display valves (or other actuators). RUN and STOP switching can be performed using any of the following: (1) Parame-
(SP can be changed.) (OUT can be changed.) The following operating procedure shows an example of changing the target setpoint
Processes in which product quality can be adversely affected if number (SPNO.) from 1 to 2. Each SP has its PID group. The PID group set for the ter, (2) Communication, and (3) User function key.
PV values fluctuate beyond their allowable ranges. parameter PIDN (PID number selection) is used. For details of other switching methods and the display appearing when the operation
After showing the OUT Display, press the DISP key to show the following displays
is started, see Users Manual.
conditionally. For details, see Users Manual. 1. Show the Operation Display. When the controller is stopped, input and outputs are as follows:
SELECT Displays 1 to 5 (which appear when registered)
Analog Input Display (display only) (factory default: non-display)
PID Number Display (display only) (factory default: non-display) 1. Show the Operation Display. 2. PV input
Control output
Displays the PV value.
Displays the preset output value.
The preset output value is set for each PID group.
Alarm output Turns the output on in case of an alarm.
2. Hold down the PARA key for
3 seconds to display MODE menu.
Hold down the PARA key for
3 seconds to display MODE menu.
3.
Press the SET/ENTER key.
The parameter S.R (STOP/RUN switch)
is displayed.
3.
The parameter S.R (STOP/RUN switch)
is displayed. Press the Down arrow key until the parameter SPNO.
appears.
4.
Press the Down arrow key until the parameter AT appears.
The parameter SPNO. (SP number selection)
4. is displayed.
5.
Change the setpoint using IM 05P01F31-11EN page 7/10
Press the SET/ENTER key. the Up/Down arrow keys.
Blinks during the change.
Press the SET/ENTER key.
cording to the displayed value. Analog input terminal ADC error Faulty.
AD.ERR Normal indication (Note) Setup parameter (AD1.E)
PV input
Analog input terminal AD value error
Contact us for repair.
In stop mode (when the STOP lamp is lit), control output cannot be manipulated.
RJC.E Faulty.
(Displays RJC. Normal indication (Note) Universal input terminal RJC error Contact us for repair.
Setup parameter (AD1.E) Universal input terminal RJC error
E and PV PV input Set the parameter RJC to OFF to erase
Up arrow key: increases control alternately.)
Press the SET/ENTER key. error indication.
output. Check wiring and sensor.
Analog input terminal burnout error
3. Down arrow key: decreases Setup parameter (AD1.E)
PV input
Analog input terminal sensor burnout Error indication is erased in normal
operation.
control output. B.OUT Normal indication (Note) Check wiring and sensor of connected
The parameter S.R (STOP/RUN switch) Setup parameter (PV1.E) PV input burnout error Burnout of analog input connected to PV
analog input terminals.
is displayed. Error indication is erased in normal
operation.
Press the SET/ENTER key. Remedies if Power Failure Occurs Note: When an error occurs in input shown in Analog input display (Operation display), Setpoint display shows the same symbol as the PV display.
If the Operation Display does not appear after turning on the controllers power, check the procedures in the following flowchart. during Operations
If a problem appears to be complicated, contact our sales representatives.
Instantaneous power failure within 20 ms.
6. Is the controller A power failure is not detected. Normal
defective?
The REM lamp is lit. operation continues.
Yes
Power failure for less than about 5 seconds,
No Key No No No or for about 5 seconds or more.
Completely Display I/O signal Communication
inactive? operation failure? failure? failure?
Affects the "settings" and "operation status."
failure? * For details, see User's Manual.
Yes Yes Yes Yes Yes
NOTE
Check wiring of the Check the key lock Turn off power, and Check the I/O specifications Check the specifications
power terminals. setting. then turn it on again. of the controller. of the controller.
Operation
PV velocity alarm time
UT32A Menu symbol: (SP) setpoint 1 to 4
0.01 to 99.59 (minute.second) 1.00 HY.UP
default. The number of alarms can be changed using the setup parameter ALNO. 4: Overshoot suppressing function
Hold down the PARA key for 3 seconds to move from the Operation Display to the Op- (number of alarms). To change the number of SP groups or alarms, see User's Manual.
VTn (strong suppressing mode)
eration Parameter Setting Display. Press the DISP key once to return to the Operation HYn Note: Setpoints 2 and 3 must be
Use the following table to record SP and alarm setpoints.
used in PID control or PI control.
Display. Parameter n=1 n=2 n=3 n=4
DYNn Disabled in the following controls:
Operation Dsipaly n: alarm number 1) ON/OFF control, 2) PD control,
SP
3) P control.
Hold down PARA key for 3 sec. DISP key
SUB
PV-related Setting Parameter Do not use the function for the
control processes with response
PIDN
Menu Menu Menu END Menu symbol: (PVS) such as flow or pressure control.
key A1
key
Parameter Initial User Display 0: Normal
SET/ENTER key PARA key A2 Name of Parameter Setting Range Auto-tuning type 0
symbol value setting level (AT.TY) 1: Stability
A3
Menu Display and 0.0 % Anti-reset windup
Parameter Parameter Parameter Parameter Setting A4 of PV
-100.0 to 100.0% of PV input range (excess integration AUTO, 50.0 to 200.0% AUTO
Display are changed PV input bias input (AR) prevention)
key key key n: group number (BS) span (EUS)
in a circular pattern. range
EASY
SP-related Setting Parameter
Parameter Parameter Parameter span OFF: Disable
Output velocity limiter OFF
END END END (OPR) 0.1 to 100.0%/s
Menu symbol: (SPS) PV input filter OFF, 1 to 120 s OFF Select the output used in MAN mode
The parameter groups can be switched using , keys. (FL)
when switched from AUTO to MAN
Parameter Initial User Display
PID Setting Parameter
Move to the Setup Parameter Setting Display: Name of Parameter Setting Range mode.
symbol value setting level OFF: Hold the control output in AUTO
Hold down the PARA key and the Left arrow key simultaneously for 3 sec.
SP = Remote input x RT + Remote input bias mode (bumpless)
Menu symbol: (PID) STD
0.001 to 9.999 1: Use manual preset output 1 (output
Remote input ratio 1.000
(RT) (Displayed only in cases where the bump)
Parameter Initial User Display Manual preset output
Operation for Setting communication is specified.) Name of Parameter Setting Range 2: Use manual preset output 2 (output OFF
symbol value setting level (MPON) number selection
STD bump)
To select the parameter setting displayed as the initial value, press the Down arrow -100.0 to 100.0% of PV input range 0.0 % of 0.0 to 999.9% 3: Use manual preset output 3 (output
key to move to the next parameter. span (EUS) PV input Proportional band When 0.0% is set, it operates as 5.0% bump)
Remote input bias
(RBS) (Displayed only in cases where the range (P) 0.1%. 4: Use manual preset output 4 (output
To change and set the parameter setting, press the SET/ENTER key to start the set- communication is specified.) span bump)
point blinking. The blinking state allows you to make changes (setting mode). Use the Used to prevent SP from changing suddenly. Integral time
OFF: Disable
240 s 5: Use manual preset output 5 (output
(I) 1 to 6000 s bump)
Up/Down/Left/Right arrow keys to change the setpoint. Press the SET/ENTER key to SP ramp-up rate Set a ramp-up rate or ramp-down rate per OFF
(UPR) hour or minute. Set a time unit using the
register the setting. Derivative time
OFF: Disable
60 s to -5.0 to 105.0%
parameter TMU. 1 to 6000 s Manual preset output 1 Table
Note that there are some parameters which are not displayed depending on the model SP ramp-down rate OFF, 0.0 + 1 digit to 100.0% of PV input OFF
(D)
to 5
However, output is limited to the 0.0%
below
EASY output high limit and low limit.
and suffix codes, control type (CNT), etc. The parameters for professional setting mode (DNR) range span (EUS) -4.9 to 105.0%, (OL<OH) EASY (MPO1 to MPO5)
(LEVL: PRO) are not described in this manual. See Users Manual. Control output high limit In Heating/cooling control: 0.1 to 100.0%
HOUR: Ramp-up rate or ramp-down (OH) Use the following table to record the manual preset output setting value.
105.0% (OL<OH)
rate per hour
SP ramp-rate time unit HOUR
Operation Mode (TMU) MIN: Ramp-up rate or ramp-down
rate per minute Control output low limit
-5.0 to 104.9%, (OL<OH), SD: Tight
0.0%
Parameter n=1 n=2 n=3 n=4 n=5
(OL) shut MPOn
Menu symbol: (MODE) Tracking is performed when the mode
Enabled when integral time is OFF.
Parameter Initial User Display SP tracking selection
changes from Remote to Local. (The local
setpoint keeps track of the remote setpoint.)
ON The manual reset value equals the
50.0%
Zone Control Parameter
symbol
Name of Parameter Setting Range
value setting level (SPT) Manual reset
output value when PV = SP.
OFF, ON (MR) Menu symbol: (ZONE)
-5.0 to 105.0%
STOP: Stop mode
Causes the setpoint to keep track of the PV
RUN: Run mode In Parameter Initial User Display
STOP/RUN switch RUN so the setpoint automatically reverts to its STD Name of Parameter Setting Range
(S.R) Preset output (PO) is generated in ON/OFF symbol value setting level
original value at a preset rate of change.
STOP mode. control:
The UPR, DNR, and TMU are used in Hysteresis (in ON/OFF In ON/OFF control: 0.0 to 100.0% of Set reference points at which switch-
PV tracking selection OFF 0.5 % of ing is carried out between groups of 100.0%
LCL: Local mode (PVT) combination. Operating conditions: 1) MAN (HYS) control) PV input range span (EUS) to
REM: Remote mode AUTO, 2) STOP AUTO, 3) Power-on, PV input PID constants according to the given of PV Table
REMOTE/LOCAL switch LCL range Reference point 1 to 3
(Displayed only in cases where the 4) SP number change, 5) SP change temperature zone. input below
(R.L) span
communication is specified.) OFF, ON (RP1 to RP3) 0.0 to 100.0% of PV input range (EU) range
0.5 % (RP1 RP2 RP3)
OFF: Disable
1 to 4: Perform auto-tuning. Tuning
EASY
Alarm Function Setting Parameter Upper-side hysteresis
of PV EASY Hysteresis can be set for switching at
0.5 %
of PV
result is stored in the specified num- (in ON/OFF control)
input
Zone PID switching
AUTO-tuning switch OFF Menu symbol: (ALRM) (HY.UP) range
a reference point.
(AT) bered PID. hysteresis 0.0 to 10.0% of PV input range span
input
STD
(RHY) range
R: Tuning result is stored in the PID 0.0 to 100.0% of PV input range span
(EUS)
Parameter Initial User Display
for reference deviation. Name of Parameter Setting Range span (EUS) span
symbol value setting level 0.5 %
of PV Set a deviation from SP. The PID for
1 to 4 (Depends on the setup param- Set a 5-digit value in the following order. Lower-side hysteresis reference deviation is used if there
SP number selection 1 input
(SPNO.) eter SPGR. setting.) [Latch action (0/1/2/3/4)] + [Energized (in ON/OFF control) is a larger deviation than the preset
AL1, (HY.LO) range
(0) or De-energized (1)] + [Without (0) AL3: Reference deviation reference deviation. OFF
The PID group number being selected span
or With (1) Stand-by action] + [Alarm Latch (RDV) OFF: Disable
is displayed.
PID number 1 type: 2 digits (see below)] action (0) 0.0 + 1 digit to 100.0% of PV input
(PID) 1 to 4, R: PID group for reference
For latch action, see User's Manual. PV high Direct/reverse action RVS: Reverse action range span (EUS)
deviation RVS STD
Alarm type: 2 digits limit (01) (DR) switch DIR: Direct action
00: Disable Without For Zone control, set the setup parameter ZON (zone PID selection) to Zone PID se-
SELECT Parameter Alarm-1 to 4 type
Example: Alarm-1
01: PV high limit, 02: PV low limit
03: SP high limit, 04: SP low limit
Stand-by
action (0) Preset output
In STOP mode, fixed control output
0.0% EASY
lection.
Use the following table to record the reference point setting value.
Ener- (PO) can be generated.
Menu symbol: (CS) 05: Deviation high limit
06: Deviation low limit gized (0) Parameter n=1 n=2 n=3
Parameter Initial User Display to For the PID setting parameter, 4 groups are displayed for the factory default.
Name of Parameter Setting Range Alarm 07: Deviation high and low limits Table RPn
symbol value setting level
08: Deviation within high and low limits AL2, EASY The number of groups can be changed by the setup parameter PIDG. (number of PID
Latch action type below
Registered Setting range of a registered param- (AL1 to AL4) Energized/ 09: Target SP high limit AL4: groups). To change the number of PID groups, see User's Manual.
SELECT parameter 10 Table De-energize 10: Target SP low limit Latch
parameter eter. EASY If you are using two or more groups of PID parameters, use the following table to record their setting values.
to 19 below 11: Target SP deviation high limit action
symbol For details, see User's Manual. Stand-by
12: Target SP deviation low limit (0) Parameter n=2 n=3 n=4 R
action
13: Target SP deviation high and low limits Ener-
Parameter n=10 n=11 n=12 n=13 n=14 n=15 n=16 n=17 n=18 n=19 gized (0) P
14: Target SP deviation within high
CSn and low limits Without I
15: OUT high limit, 16: OUT low limit Stand-
D
For the registration of SELECT parameters, see User's Manual. 19: Analog input PV high limit by action
20: Analog input PV low limit (0) OH
29: PV velocity PV low
OL
30: Fault diagnosis limit (02)
31: FAIL MR
IM 05P01F31-11EN page 9/10
Setup Parameters Maximum value of PV
Depends on the input type.
- For temperature input -
Depends
on the
Key Action Setting Parameter AL1-AL2 Function Registration Parameter
(RH) input range
Set the temperature range that is input type Menu symbol: (KEY) Menu symbol: (ALM)
Hold down the PARA key and Left arrow key simultaneously for 3 seconds to move actually controlled. (RL<RH)
from the Operation Display or Operation Parameter Setting Display to the Setup Pa- - For voltage / current input - Parameter Initial User Display Parameter Initial User Display
Name of Parameter Setting Range Name of Parameter Setting Range
Set the range of a voltage / current symbol value setting level
rameter Setting Display. signal that is applied.
symbol value setting level
Press the DISP key once to return to the Operation Display. Depends OFF: Disable Set an I relay number. For the items
Minimum value of PV The scale across which the voltage/ other than below, see User's Manual.
on the A/M: AUTO/MAN switch AL1 function selection
Operation Dsipaly input range current signal is actually controlled Ex.) Set the number 4353 for AL1.S
4353
(RL) input type R/L1: REM/LCL switch (AL1.S)
should be set using the maximum
Hold down PARA key and S/R: STOP/RUN switch to use the alarm 1.
DISP key value of input scale (SH) and mini- Set OFF to disable the function.
Left arrow key simultaneously for 3 sec. AUTO: Switch to AUTO
mum value of input scale (SL).
MAN: Switch to MAN No function: OFF
(Input is always 0% when RL = RH.) EASY STD
REM1: Switch to REM Alarm 1: 4353, Alarm 2: 4354
Menu Menu Menu END 0: No decimal place LCL1: Switch to LCL Alarm 3: 4355, Alarm 4: 4357
key 1: One decimal place Depends User function key-n STOP: Switch to STOP AL2 function selection
key PV input scale decimal PID EASY 4354
2: Two decimal places on the (Fn) action setting RUN: Switch to RUN (AL2.S) AUTO (OFF) / MAN (ON) status: 4193
SET/ENTER key PARA key (SDP) point position 3: Three decimal places input type REM (ON) / LCL (OFF) status: 4194
AT: Auto-tuning
4: Four decimal places LTUP: LCD brightness UP STOP (ON) / RUN (OFF) status: 4195
Menu Display and FAIL (Normally ON) output: 4256
Parameter Parameter Parameter Depends LTDN: LCD brightness DOWN
Parameter Setting Maximum value of PV
on the BRI: Adjust LCD brightness
key key key Display are changed
in a circular pattern.
(SH) input scale
-19999 to 30000, (SL<SH), input type LCD: LCD backlight ON/OFF switch
LAT: Latch release
System Setting Parameter
Parameter Parameter Parameter | SH - SL | 30000 Depends
Minimum value of PV PID: PID tuning switch Menu symbol: (SYS)
END END END input scale
on the
(SL) input type Parameter Initial User Display
Display Function Setting Parameter
Name of Parameter Setting Range
symbol value setting level
OFF: Disable Depends
Move to the Operation Parameter Setting Display: PV input burnout action UP: Upscale on the Set how the controller should recover from
Hold down the PARA key for 3 sec. (BSL) DOWN: Downscale input type Menu symbol: (DISP) a power failure of 5 seconds or more.
CONT: Continue action set before
0.0 % of Parameter
Name of Parameter Setting Range
Initial User Display Restart mode CONT
(R.MD) power failure.
-100.0 to 100.0% of each input range PV input STD
symbol value setting level
PV analog input bias MAN: Start from MAN.
Operation for Setting (A.BS) span (EUS) range 0: Fixed in white AUTO: Start from AUTO.
span 1: Fixed in red
To select the parameter setting displayed as the initial value, press the Down arrow 2: Link to alarm 1 (Alarm OFF: white, Set time between power on and the in-
key to move to the next parameter. PV analog input filter OFF, 1 to 120 s OFF Alarm ON: red) Restart timer stant where controller starts computation. 0
STD
3: Link to alarm 1 (Alarm OFF: red, (R.TM) 0 to 10 s
To change and set the parameter setting, press the SET/ENTER key to start the set- (A.FL)
Alarm ON: white)
point blinking. The blinking state allows you to make changes (setting mode). Use the W: W-5% Re/W-26% Re(Hoskins Mfg.Co.). ASTM E988, WRE: W97Re3-W75Re25 4: Link to alarm 1 or 2 (Alarm OFF: Set preset output value when the
Up/Down/Left/Right arrow keys to change the setpoint. Press the SET/ENTER key to white, Alarm ON: red) input burnout or ADC error occurs.
register the setting. Input Range, SP Limiter Setting Parameter Active color PV display 5: Link to alarm 1 or 2 (Alarm OFF:
0
Manual output is prioritized when
switch red, Alarm ON: white) Input error preset output the input burnout occurs in MAN. 0
Note that there are some parameters which are not displayed depending on the Mod- Menu symbol: (MPV) (PCMD) (EPO)
6: PV limit (Within range: white, Out 0: Preset output
el and Suffix codes, control type (CNT), etc. The parameters for professional setting of range: red) 1: 0% output
Parameter Initial User Display 7: PV limit (Within range: red, Out of EASY
mode (LEVL: PRO) are not described in this manual. See Users Manual. symbol
Name of Parameter Setting Range
value setting level
2: 100% output
range: white)
8: SP deviation (Within deviation:
Control Function Setting Parameter
-: No unit Same Power frequency AUTO, 60: 60 Hz, 50: 50 Hz AUTO
C: Degree Celsius as PV white, Out of deviation: red) (FREQ)
Control PV input unit 9: SP deviation (Within deviation: red,
(P.UNI) -: No unit, - -: No unit, - - -: No unit input
Menu symbol: (CTL) Out of deviation: white) OFF: Disable
F: Degree Fahrenheit unit Quick setting mode ON
Parameter Initial User Display Set a display value when in PV limit (QSM) ON: Enable
Name of Parameter Setting Range 0: No decimal place PV color change high
symbol value setting level or SP deviation. 0 EASY
1: One decimal place Depends (PCH) limit Depe-nds on
Control PV input decimal -19999 to 30000 (Set a value within ENG: English, FRA: French
PID: PID control 2: Two decimal places on the Guide display language the model and
(P.DP) point position the input range.) (LANG) GER: German, SPA: Spanish
ONOF: ON/OFF control (1 point of 3: Three decimal places input type suffix codes
PV color change low limit Decimal point position depends on 0
Control type hysteresis) PID EASY 4: Four decimal places (PCL)
(CNT) the input type.
ONOF2: ON/OFF control (2 points of Password setting 0 (No password) to 65535 0
hysteresis) Depends 0: Disable (PASS)
Maximum value of
on the 1: OUT, 3: PV, 4: SP
(P.RH) control PV input range
Set a number of SP groups to use. input type STD Bar-graph display regis- 5: Deviation
(SPGR.)
Number of SP groups
1 to 4
4 -19999 to 30000, (P.RL<P.RH),
| P.RH - P.RL | 30000 Depends (BAR1) tration 6 to 16: Disable
5 Error and Version Confirmation Parameter (for display only)
Minimum value of control 18: PV terminals analog input
If set to SP group number selection, PV input range
on the 27: TSP, 28: TSP deviation Menu symbol: (VER)
allows PID constants to be selected (P.RL) input type
for each SP group. 1.0 % Parameter Display
100.0 % Name of Parameter Status record
If set to Zone PID selection, of PV symbol level
of PV Bar-graph deviation 0.0 to 100.0% of PV input range span
automatically selects PID constants SP high limit input
(BDV) display band (EUS)
according to the range set in the (SPH) input range STD Parameter error status
0.0 to 100.0% of PV input range (EU), range span (PA.ER)
Zone PID selection Reference point. 0 STD (SPL<SPH)
(ZON) 0: SP group number selection 1 0.0 % of
1: Zone PID selection (selection by PV) SP low limit PV input Guide display ON/OFF OFF: Nondisplay, ON: Display ON Option error status
2: Zone PID selection (selection by (SPL) (GUID) (OP.ER)
range
target SP) OFF: Disable
3: SP group number selection 2
4: Zone PID selection (selection by SP) Output Setting Parameter Economy mode
1: Economy mode ON (All indications
except PV display OFF) OFF
(AD1.E)
A/D converter error status 1
Menu symbol: (PV) Control output cycle time 0.5 to 1000.0 s 30.0 s EASY Least significant digital OFF: With least significant digit
(CT) OFF STD
(MLSD) mask of PV display ON: Without least significant digit DCU version EASY
Parameter
Name of Parameter Setting Range
Initial User Display (DCU)
symbol value setting level OUT current output 4-20: 4 to 20 mA, 0-20: 0 to 20 mA Method for least signifi-
4-20 STD
(OU.A) range 20-4: 20 to 4 mA, 20-0: 20 to 0 mA cant digital mask of PV 0: Rounding, 1: Rounding-off 0 STD
OFF: Disable ECU-1 version (E1-terminal area)
(MKTP) display (ECU1)
K1: -270.0 to 1370.0 0C / -450.0 to 2500.0 0F
K2: -270.0 to 1000.0 0C / -450.0 to 2300.0 0F RS-485 Communication Setting Parameter (E1-terminal Area)
K3: -200.0 to 500.0 0C / -200.0 to 1000.0 0F SELECT Display Setting Parameter (PARA)
Parameter version
J: -200.0 to 1200.0 0C / -300.0 to 2300.0 0F Menu symbol: (R485)
T1: -270.0 to 400.0 0C / -450.0 to 750.0 0F Menu symbol: (CSEL)
T2: 0.0 to 400.0 0C / -200.0 to 750.0 0F Parameter
Name of Parameter Setting Range
Initial User Display Product version
B: 0.0 to 1800.0 0C / 32 to 3300 0F symbol value setting level Parameter
Name of Parameter Setting Range
Initial User Display (H.VER)
symbol value setting level
S: 0.0 to 1700.0 0C / 32 to 3100 0F PCL: PC link communication
R: 0.0 to 1700.0 0C / 32 to 3100 0F PCLSM: PC link communication (with Register the operation parameter Serial number 1
N: -200.0 to 1300.0 0C / -300.0 to 2400.0 0F checksum) (except the Operation Mode) that is (SER1)
E: -270.0 to 1000.0 0C / -450.0 to 1800.0 0F
to SELECT Display-1 to -5 frequently modified to display it in the Table
LADR: Ladder communication OFF STD
L: -200.0 to 900.0 0C / -300.0 to 1600.0 0F CO-M: Coordinated master station registration Operation Display. below Serial number 2
U1: -200.0 to 400.0 0C / -300.0 to 750.0 0F (CS1 to CS5) OFF, 2301 to 5000 (SER2)
CO-S: Coordinated slave station
U2: 0.0 to 400.0 0C / -200.0 to 1000.0 0F Protocol selection MBASC: Modbus (ASCII) MBRTU For the setting range, see User's Manual.
PV input type
W: 0.0 to 2300.0 0C / 32 to 4200 0F
OFF
(PSL) MBRTU: Modbus (RTU)
Use the following table to record SELECT Display setting value. Parameter Display Level Parameter
(IN) PL2: 0.0 to 1390.0 0C / 32.0 to 2500.0 0F CO-S1: Coordinated slave station
P2040: 0.0 to 1900.0 0C / 32 to 3400 0F EASY (Loop-1 mode) Parameter n=1 n=2 n=3 n=4 n=5 Menu symbol: (LVL)
WRE: 0.0 to 2000.0 0C / 32 to 3600 0F CO-S2: Coordinated slave station
JPT1: -200.0 to 500.0 0C / -300.0 to 1000.0 0F CSn Parameter Initial User Display
(Loop-2 mode) Name of Parameter Setting Range
JPT2: -150.0 to 150.0 0C / -200.0 to 300.0 0F symbol value setting level
P-P: Peer-to-peer communication
PT1: -200.0 to 850.0 0C / -300.0 to 1560.0 0F
PT2: -200.0 to 500.0 0C / -300.0 to 1000.0 0F 600: 600 bps, 1200: 1200 bps Key Lock Setting Parameter Parameter display level
EASY: Easy setting mode
STD: Standard setting mode STD EASY
PT3: -150.00 to 150.00 0C / -200.0 to 300.0 0F 2400: 2400 bps, 4800: 4800 bps EASY (LEVL)
Baud rate 19200 Menu symbol: (KLOC) PRO: Professional setting mode
0.4-2V: 0.400 to 2.000 V (BPS) 9600: 9600 bps, 19200: 19.2k bps
1-5V: 1.000 to 5.000 V 38400: 38.4k bps Parameter Initial User Display * For Professional setting mode, see Users Manual.
Name of Parameter Setting Range
4-20: 4.00 to 20.00 mA NONE: None symbol value setting level
0-2V: 0.000 to 2.000 V Parity EVEN: Even EVEN Trademarks
0-10V: 0.00 to 10.00 V (PRI) ODD: Odd Communication write
OFF: Enable, ON: Disable OFF Our product names or brand names mentioned in this manual are
0-20 : 0.00 to 20.00 mA (COM.W) enable/disable
the trademarks or registered trademarks of Yokogawa Electric Corporation.
-1020: -10.00 to 20.00 mV Stop bit 1: 1 bit, 2: 2 bits 1 Adobe, Acrobat, and Postscript are either registered trademarks or trademarks
0-100: 0.0 to 100.0 mV (STP) Front panel parameter
OFF STD of Adobe Systems Incorporated.
(DATA) data (,) key lock
-: No unit, C: Degree Celsius OFF: Unlock, ON: Lock Modbus is a registered trademark of Schneider Electric.
PV input unit -: No unit, - -: No unit, - - -: No unit, C Data length 7: 7 bits, 8: 8 bits 8 We do not use the TM or mark to indicate these trademarks or
(UNIT) F: Degree Fahrenheit (DLN) Front panel A/M key lock OFF registered trademarks in this manual.
(A/M) All other product names mentioned in this manual are trademarks
Address 1 to 99 1 or registered trademarks of their respective companies.
(ADR)
IM 05P01F31-11EN page 10/10