Sie sind auf Seite 1von 3

D R I V E S &

S W I T C H G E A R

D esigned to detect, locate and analyze insulating systems faults and winding
dissymmetry, Surge Comparison Test Machines (SCTM) offer the best diagnostic
capability as a single test in detecting the type of fault and often the cause of defect.

Inspection (testing) stators of AC


induction machines - Part 2
In Part 1 (VECTOR, October 2005 issue) by C.D. Pitis, Femco Mining Motors
some tests were presented, including
insulation resistance (Megger and
PI) test, tan delta test, resistance and
may not reach the rated or required performed. The SCTM is capable of
impedance tests. Some characteristic
output voltage. This occurs on low gradually increasing the voltage to the
profiles with comments were given desired test level:
impedance motors or on motors that
relating to situations when a correct
are too large for the SCTM capability. Utest = [2 x Unom + 1000] x k
dispersion of test results is required.
One of the SCTM working conditions where k = 1 for old windings, or k = 2
These should help repairers to detect
is related to motor rated voltage. for new windings before impregnation,
hidden defects, thus improving their
For example, for a motor with or k = 1,7 after impregnation.
performance by extending electric motor
Unom = 3,3 kV 50 Hz, the SCTM has to
life expectancy. By increasing the test voltage in steps
deliver a minimum test voltage of:
Surge Comparison Test (increments), the leakage current can
Utest = [2 x 3300 + 1000] x 2 be monitored to observe any sharp
Machines (SCTM)
= 11 000 V12 000 V increase, and to avoid a possible
These are non-destructive tests. The insulation breakdown (Fig. 1).
Minimum test inductance is another
manufacturer/repairer/operator need criterion. For large formed coils
to train themselves in the process, Estimated interval of insulation
with low inductance (outside the breakdown
as no specific literature is generally stator), the resonant frequency in
available. the surge test circuit ranges between Fig. 1. Shows the incipient insulation
Choosing a SCTM 0,11,5 MHz. This requires high breakdown graph test for an 830 kW,
f r e q u e n c y- r e s p o n s e m e a s u r i n g 6,6 kV motor at 12 C in January 2002.
Sometimes the full output of an SCTM equipment and flexibility, and is one of
the most difficult applications of surge Up to a test voltage of 6,0 kV DC
comparison testing. Special boosters (point B), the insulation resistance has
are required to test inductances of a constant slope equal to 90 M.
L = 0,4 H. Above 6 kV, a change in slope can be
noticed, with the insulation resistance
The maximum pulse energy (MPE) is also
becoming 60 M at 9 kV (point C).
related to motor size. For example a
5 MW 11 V motor needs a SCTM with Above this value, insulation breakdown
MPE = 11 while a 150 kW 525 V motor is expected if a Hipot test is performed
needs MPE = 0,3. (Point D) estimated 40 M. Corrected
values of insulation resistance at 40 C
Links between the SCTM and a PC temperature are:
enable a superior test approach with the
ability to do customised tests, and store - Point B: 10,0 M
profiles, statistics, history, trends, etc. - Point C: 6,7 M
DC step voltage test - Point D: 4,5 M
Fig. 1: Estimated interval of
Most electrical associations recommend The minimum recommended value of
insulation breakdown.
this procedure. The test should be
insulation resistance is:
performed after a PI test has been
November 2005 - Vector - Page 25
Electromagnetic distortions on
fitted coils surge test.
Some insulation faults can be related to
the wave pattern measured during the
above surge (impulse) test.
A short-circuit between turns involves
reduced values of R and C i.e.
the time constant will be reduced,
giving only slight damping of the
Fig. 3: output wave, but the output V will be
reduced because of a higher value
down at a prescribed test value. The of absorbed current (shifting peak);
test voltage is less than rated dielectric Faulty insulation to earth, or
strength. If the insulation fails under test, inadequate adhesion of insulation
it becomes known that the insulation to film to copper, will increase the value
Fig. 2: Monitoring trends of DC
ground was unreliable. of leakage current, thus reducing the
step voltage tests.
Surge (impulse) test output V, while the damping will be
insignificant.
Rmin =[1 + 6600/1000] Switching of loads and lightning strikes
are known to cause high voltage Small damping and wave shifts for
= 7,6 M at 6,6 kV one or a group of coils whilst the
surges. The first few turns of the stator
The motor came in for repair as a of an electric motor can experience coils are in very good condition can
result of the insulation test trend results voltage surges up to 10 times the actual be related to damaged lamination
monitored since 1992, as plotted in operating voltage of the motor. Studies insulation or iron core hot spots
Fig. 2. have shown that a very rapid surge may (Fig. 4).
be distributed across the first 10% of the Surge comparison test (SCT)
Converted values of insulation
stator winding.
resistance at 40 C over the The SCT is the only means devised to
years had the following trend: The surge test applies a high voltage stress, test and analyse the integrity of
May 1992: 130 M, impulse into a coil, groups or phase(s). the interturn, intercoil or interphase
The SCTM capacitors and the winding insulation, and subject them to higher
June 1997: 37 M, circuit form a complex R-L-C circuit, stresses than ground insulation. In a
Feb. 1998: 33 M, giving a damped oscillation with a SCT, two identical high voltage and high
frequency much higher than the mains frequency pulses are simultaneously
Feb. 2001: 10 M. frequency (50 Hz). As the impulse imposed on two phases, as two
In 2001, the full test voltage was not propagates, it locates the insulation separate R-L-C circuits, and the induced
weakness. Whilst raising the output reflections of both pulses are displayed,
applied due to high leakage current
voltage, the waveform peaks of the superimposed upon each other. A faulty
i.e. 980 A. Weak insulation will show circuit will give a different trace wave
declining M values as the voltage is traces must be observed. They will begin
to flutter or fluctuate just prior to any pattern. A useful chart presents a typical
increased. winding fault in Fig. 5.
breakdown of insulation. Such failure
Before stripping, the stator was re-tested on a diamond coil is presented in Fig.3 On large machines due to the possible
in the workshop. The insulation recovered (red arrow) compared to a healthy existence of physical non-symmetry
slightly, possibly due to internal dipole coil (blue arrow), where peak flutters are on the input, unbalanced inductances
re-orientation by relaxation. present prior to dielectric break down. and/or capacitances could be present.
The maximum voltage based on the worst- These could produce wave distortion
The DC step voltage test is not performed
case distribution of a surge in the winding and/or separation.
to break-down the insulation, but to
ensure that the insulation does not break is 1,5 x the winding operating voltage. Waveform analysis
SCT waveforms provide signatures,
patterns or traces that serve:
To determine the precise output
voltage during SCT;
To observe any differences in the
impedances of the two windings
during SCT.
The differences in recorded waveforms
may be:
Static or permanent separation, in
proportion with the test voltage;
Dynamic separation, starting from a
Fig. 4: Transformer effect of the specific voltage level, and showing
hot spots on laminations. wave instability or flickering.

November 2005 - Vector - Page 26


Three types of separations are typically noted (Fig. 5):
Only at the beginning of the wave form;
Difference in the peaks (change in amplitude);
Change in amplitude and frequency (phase shift).
Separation at the beginning of a waveform and changes in amplitude can
be related to tester ability.
Phase shift indicates short-circuits. If the wave pattern changes and
becomes erratic, then intermittent shorting or arcing is occurring in one
of the windings under test.
Steady separation of the traces indicates solid shorts, or incorrect turns
count, or wrong connection.
Large stators with parallel windings may show little or no separation for
shorted or open windings, the inductance change caused by these faults
being undetectable. As a result, it is critical to perform a SCT on each of
the parallel windings individually.
Conclusions
A insulating system is an assembly of insulating materials associated with
conductors and supporting the structural parts of the stator winding of a
motor.
Experience gained by testing a large variety of stators will always allow
a better evaluation and failure prediction. The author found that a
stethoscope is a very useful tool in identifying the exact point of discharging
on SCT.
Further tests will be presented in Part 3 of the article, in a subsequent issue
of VECTOR.
Contact Dan Pitis, Femco Mining Motors,
Fig. 5: Wave shapes of typical winding faults. Tel (012) 250-2101, danpit@femco.co.za

November 2005 - Vector - Page 28

Das könnte Ihnen auch gefallen