Beruflich Dokumente
Kultur Dokumente
50Hz
OPERATION AND MAINTENANCE MANUAL
CCNC : 70739206IBPL
Rev : D
Date : August 2005
AIR COMPRESSOR GROUP
BONDED WARRANTY & REGISTERED START UP
Warranty
The Company warrants that the equipment manufactured by it and delivered hereunder will be free of defects in
material and workmanship for a period of twelve months from the date of placing the Equipment in operation or eighteen
months from the date of shipment from the factory, whichever shall first occur. The Purchaser shall be obligated to
promptly report any failure to conform to this warranty, in writing to the Company in said period, whereupon the
Company shall, at its option, correct such nonconformity, by suitable repair to such equipment or, furnish a replacement
part F.O.B. point of shipment, provided the Purchaser has stored, installed, maintained and operated such Equipment
in accordance with good industry practices and has complied with specific recommendations of the Company.
Accessories or equipment furnished by the Company, but manufactured by others, shall carry whatever warranty the
manufacturers have conveyed to the Company and which can be passed on to the Purchaser. The Company shall
not be liable for any repairs, replacements, or adjustments to the Equipment or any costs of labor performed by the
Purchaser or others without Companys prior written approval.
The effects of corrosion, erosion and normal wear and tear are specifically excluded. Performance warranties are
limited to those specifically stated within the Companys proposal. Unless responsibility for meeting such performance
warranties are limited to specified tests, the Companys obligation shall be to correct in the manner and for the period
of time provided above.
THE COMPANY MAKES NO OTHER WARRANTY OR REPRESENTATION OF ANY KIND WHATSOEVER,
EXPRESSED OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES OF MERCHANTABILITY
AND FITNESS FOR A PARTICULAR PURPOSE, ARE HEREBY DISCLAIMED.
Correction by the Company of nonconformities whether patent or latent, in the manner and for the period of time
provided above, shall constitute fulfillment of all liabilities of the Company for such nonconformities whether based on
contract, warranty negligence, indemnity, strict liability or otherwise with respect to or arising out of such Equipment.
The purchaser shall not operate Equipment which is considered to be defective, without first notifying the Company
in writing of its intention to do so. Any such use of Equipment will be at Purchasers sole risk and liability.
Note that this is IngersollRand standard warranty. Any warranty in force at the time of purchase of the compressor
or negotiated as part of the purchase order may take precedence over this warranty.
21 MAINTENANCE
27 TROUBLE SHOOTING
The contents of this manual are considered to be proprietary and The intended uses of this machine are outlined below and examples
confidential to IngersollRand and should not be reproduced without of unapproved usage are also given, however IngersollRand cannot
the prior written permission of IngersollRand. anticipate every application or work situation that may arise.
Nothing contained in this document is intended to extend any IF IN DOUBT CONSULT SUPERVISION.
promise, warranty or representation, expressed or implied, regarding
the IngersollRand products described herein. Any such warranties or
other terms and conditions of sale of products shall be in accordance This machine has been designed and supplied for use only in the
with the standard terms and conditions of sale for such products, which following specified conditions and applications:
are available upon request. . Compression of normal ambient air containing no known or
detectable additional gases, vapours. or particles
. Operation within the ambient temperature range specified in the
This manual contains instructions and technical data to cover GENERAL INFORMATION section of this manual.
routine operation and scheduled maintenance tasks by operation and
maintenance staff. Major overhauls are outside the scope of this
manual and should be referred to an authorised IngersollRand service The use of the machine in any of the situation types listed in
department. table 1:
a) Is not approved by IngersollRand,
b) May impair the safety of users and other persons, and
The design specification of this machine has been certified as c) May prejudice any claims made against IngersollRand.
complying with E.C. directives. Any modification to any part is
absolutely prohibited and would result in the CE certification and
marking being rendered invalid. TABLE 1
Use of the machine to produce compressed air for:
All components, accessories, pipes and connectors added to the a) direct human consumption
compressed air system should be: b) indirect human consumption, without suitable filtration and purity
. of good quality, procured from a reputable manufacturer and, checks.
wherever possible, be of a type approved by IngersollRand.
. clearly rated for a pressure at least equal to the machine maximum Use of the machine outside the ambient temperature range
allowable working pressure. specified in the GENERAL INFORMATION SECTION of this manual.
. compatible with the compressor lubricant/coolant.
. accompanied with instructions for safe installation, operation and Use of the machine where there is any actual or foreseeable risk of
maintenance. hazardous levels of flammable gases or vapours.
THIS MACHINE IS NOT INTENDED AND MUST NOT BE
Details of approved equipment are available from IngersollRand USED IN POTENTIALLY EXPLOSIVE ATMOSPHERES,
Service departments. INCLUDING SITUATIONS WHERE FLAMMABLE GASES OR
VAPOURS MAY BE PRESENT.
The use of nongenuine spare repair parts other than those Use of the machine fitted with non IngersollRand approved
included within the IngersollRand approved parts list may create components.
hazardous conditions over which IngersollRand has no control.
Therefore IngersollRand does not accept any liabilitity for losses Use of the machine with safety or control components missing or
caused by equipment in which nonapproved repair parts are installed. disabled.
Standard warranty conditions may be affected.
WARNING: Electrical shock risk. WARNING Pressurised vessel. WARNING Hot surface.
WARNING Pressurised component or WARNING Air/gas flow or Air discharge. Do not breathe the compressed air from this
system. machine.
Use fork lift truck from this side only. RESET Do not use fork lift truck from this side.
Read the Operation and Maintenance manual Do not operate the machine without the guard Lifting point.
before operation or maintenance of this being fitted.
machine is undertaken.
INSIDE PACKAGE
VIEW TOP
WARNING! Compressed air must not be used for a direct feed to any form of
Hazard that CAN cause DEATH, SEVERE INJURY or substantial breathing apparatus or mask.
property damage if ignored. Instructions which must be followed
The discharged air contains a very small percentage of compressor
precisely to avoid injury or death. lubricant and care should be taken to ensure that downstream
CAUTIONS! equipment is compatible.
Cautions call attention to instructions which must be followed If the discharged air is to be ultimately released into a confined
precisely to avoid damaging the product, process or its surroundings. space, adequate ventilation must be provided.
NOTES When using compressed air always use appropriate personal
Notes are used for supplementary information. protective equipment.
BREATHING AIR PRECAUTION All pressure containing parts, especially flexible hoses and their
IngersollRand air compressors are not designed, intended or couplings, must be regularly inspected, be free from defects and be
approved for breathing air. Compressed air should not be used for replaced according to the Manual instructions.
breathing air applications unless treated in accordance with all
applicable codes and regulations. Compressed air can be dangerous if incorrectly handled. Before
doing any work on the unit, ensure that all pressure is vented from the
system and that the machine cannot be started accidentally.
Ensure that the operator reads and understands the decals and All safety valves located in the separator tank must be checked
consults the manuals before maintenance or operation. periodically for correct operation.
Ensure that the Operation and Maintenance manual is not removed Do not overpressurize the receiver tank or similar vessels beyond
permanently from the machine. design limits.
Ensure that maintenance personnel are adequately trained, Do not use a receiver tank or similar vessels that fail to meet the
competent and have read the Maintenance Manuals. design requirements of the compressor. Contact your distributor for
assistance.
Do not point air nozzles or sprayers toward anyone.
Do not drill into, weld or otherwise alter the receiver tank or similar
Compressed air and electricity can be dangerous. Before vessels.
undertaking any work on the compressor, ensure that the electrical
supply has been isolated and the compressor has been relieved of all
pressure.
Materials
Wear eye protection when operating or servicing compressor. The following substances are used in the manufacture of this
All persons positioned near to operating machinery should be machine and may be hazardous to health if used incorrectly:
equipped with hearing protection and given instructions on its use in . preservative grease
accordance with workplace safety legislation. . rust preventative
. compressor coolant
Make sure that all protective covers are in place and that the
canopy/doors are closed during operation. AVOID INGESTION, SKIN CONTACT AND INHALATION OF
FUMES
The specification of this machine is such that the machine is not
suitable for use in flammable gas risk areas.
Installation of this compressor must be in accordance with Transport
recognised electrical codes and any local Health and Safety Codes. When loading or transporting machines ensure that the specified
The use of plastic bowls on line filters can be hazardous. Their lifting and tie down points are used.
safety can be affected by either synthetic lubricants, or the additives Lifting equipment must be properly rated for the weight of the
used in mineral oils. Ingersoll Rand recommends that only filters with
metal bowls should be used on a pressurised system. compressor.
Compressed air
Compressed air can be dangerous if incorrectly handled. Before Electrical
doing any work on the unit, ensure that all pressure is vented from the Keep all parts of the body and any handheld tools or other
system and that the machine cannot be started accidentally. conductive objects, away from exposed live parts of the compressor
electrical system. Maintain dry footing, stand on insulating surfaces
and do not contact any other portion of the compressor when making
WARNING adjustments or repairs to exposed live parts of the compressor
Imposing a normal or emergency stop on the compressor will electrical system.
only relieve presure upstream of the minimum pressure valve on
top of the separator tank.
If maintenance work is required downstream of this valve, ensure WARNING
that all pressure is relieved at the process vent point external to Any electrical connections or adjustments should only be
the compressor made by a suitably qualified electrician
Ensure that the machine is operating at the rated pressure and that Close and lock all access doors when the compressor is left
the rated pressure is known to all relevant personnel. unattended.
All air pressure equipment installed in or connected to the machine Do not use extinguishers intended for Class A or Class B fires on
must have safe working pressure ratings of at least the machine rated electrical fires. Use only extinguishers suitable for class BC or class
pressure. ABC fires.
SSR UP5 11, UP5 15, UP5 18, UP5 22 http://air.irco.com
SAFETY 7
Attempt repairs only in clean, dry, well lighted and ventilated areas.
Connect the compressor only to electrical systems that are
compatible with its electrical characteristics and that are within its rated
capacity.
Condensate disposal
As waste water regulations vary by country and region it is the
responsibility of the user to establish the limitations and regulations in
their particular area. IngersollRand and its associated distributors are
happy to advise and assist in these matters.
For further information, consult Material Data Sheets CPN
88303979 for ULTRAPlus Coolant.
The above information contains data supplied in support of United
Kingdom Control of Substances Hazardous to Health (C.O.S.H.H.)
regulations.
LEGEND
CABLE KM3 Contactor (star)
L1 L3 Mains terminals PS Pressure switch
PE Main earth terminal TM2 Runon Timer
E1 Earth terminal, Main motor 1SV Valve, solenoid (Load) N.C.
E2 Earth terminal, Control transformer 3SV Valve, solenoid (Blowdown) N.O.
E3 Earth terminal, Instrument panel LT3 Fault lamp
E4 Earth terminal, PS MM Main motor
E5 Earth terminal, 1SV FU13 Fuses
E6 Earth terminal, 3SV RST Reset
T1 Transformer, control supply EDV Electric drain valve (Option)
LT1 Power on lamp VAR Varistor
HATS Temperature switch, Discharge
MOL Motor overload
ES Switch, emergency stop NOTES
ROTATION
VIEW REAR
VIEW LEFT
VIEW RIGHT
VIEW FRONT
KEY
B Compressor and cooling air intake Fork lift hole covers must be installed after unit is in place to
reduce noise and ensure proper cooling of package)
C Starter box
H 4 slots 15 (0.6) x 25 (1.0)
D Cooling air exhaust
ROTATION
VIEW RIGHT
VIEW TOP
VIEW REAR
VIEW BOTTOM
KEY
ROTATION
VIEW RIGHT
VIEW TOP
VIEW REAR
VIEW BOTTOM
KEY
NOTES
KEY CAUTION
The use of plastic bowls on line filters and other plastic air line
1. Compressor components can be hazardous. Their safety can be affected by
2. Air Receiver either synthetic coolants or the additives used in mineral oils.
Ingersoll Rand recommends that only filters with metal bowls
3. Air Dryer should be used on any pressurised system.
4. Compressed air filters
5. System demand points
CAUTION
NOTE Before starting machine remove shipping bolt and discard
Items [2] to [5] are optional or may be existing items of plant. Refer
to your IngersollRand distributor / representative for specific
recommendations.
CAUTION
The standard compressor unit is not suitable for operation in
temperatures liable to cause freezing as Condensate water is
LOCATION IN THE PLANT liable to be produced in the after cooler and receiver where fitted.
MOTOR
Nominal power 15kW (20hp) 18,5kW (25hp) 22kW (30hp)
Speed 1475 RPM
IP rating IP55
Frame 160L 180M 180L
Insulation class F
COOLING SYSTEM
Air cooled
Cooling air flow 42.5m3/min (1500cfm) 55.2m3/min (1950cfm) 55.2m3/min (1950cfm)
Maximum P in air ducts 12.7mmH2O (1/2 inWg)
Cooling air outlet T 17_C (30_F) 16_C (28_F) 20_C (35_F)
Compressed air outlet T 16_C (28_F) 16_C (28_F) 17_C (30_F)
GENERAL DATA
Residual coolant content 3 mg/m3 (3ppm) 3 mg/m3 (3ppm) 3 mg/m3 (3ppm)
Separator vessel capacity 17 (3.75 UK gallon)
(Litres)
Coolant capacity 13 (2.9 UK gallon)
(Litres)
Sound pressure level to 68 dB(A) 68 dB(A) 69 dB(A)
CAGIPNEUROP
Weight base mount unit 509 kg (1122 lbs) 532 kg (1173 lbs) 540 kg (1190 lbs)
Weight 500 Litre Receiver 730 kg (1610 lbs) 753 kg (1660 lbs) 761 kg (1678 lbs)
mounted
Weight 750 Litre Receiver 801 kg (1766 lbs) 824 kg (1817 lbs) 832 kg (1834 lbs)
mounted
MOTOR
Nominal power 11kW (15hp) 15kW (20hp) 18,5kW (25hp)
Speed 1475 RPM
IP rating IP55
Frame 160L 180M 180L
Insulation class F
COOLING SYSTEM
Air cooled
Cooling air flow 42.5m3/min (1500cfm) 55.2m3/min (1950cfm) 55.2m3/min (1950cfm)
Maximum P in air ducts 12.7mmH2O (1/2 inWg)
Cooling air outlet T 13_C (24_F) 17_C (30_F) 16_C (28_F)
Compressed air outlet T 14_C (26_F) 16_C (28_F) 16_C (28_F)
GENERAL DATA
Residual coolant content 3 mg/m3 (3ppm) 3 mg/m3 (3ppm) 3 mg/m3 (3ppm)
Separator vessel capacity 17 (3.75 UK gallon)
(Litres)
Coolant capacity 13 (2.9 UK gallon)
(Litres)
Sound pressure level to 68 dB(A) 68 dB(A) 69 dB(A)
CAGIPNEUROP
Weight base mount unit 509 kg (1122 lbs) 532 kg (1173 lbs) 540 kg (1190 lbs)
Weight 500 Litre Receiver 730 kg (1610 lbs) 753 kg (1660 lbs) 761 kg (1678 lbs)
mounted
Weight 750 Litre Receiver 801 kg (1766 lbs) 824 kg (1817 lbs) 832 kg (1834 lbs)
mounted
1. If a circuit breaker is selected it should only be a magnetic trip type, Feeder cables/wires should be sized by the customer/electrical
set above the anticipated starting current of the machine, but below the contractor to ensure that the circuit is balanced and not overloaded by
maximum prospective fault current for the circuit. The circuit breaker other electrical equipment. The length of wiring from a suitable
or fuseable disconnect must be capable of breaking the prospective electrical feed point is critical as voltage drops may impair the
fault current at its terminals. performance of the compressor.
2. PVC/PVC Type Calculated using the following conditions:
Feeder cables / wires connections to isolator or disconnect should
be tight and clean.
NOTE CAUTION
All data applies to standard product only. Ensure that the motor rotates in the correct direction as
indicated by direction arrows, and on drawing.
Cooling air is moved through the coolers by the cooling fan and The compressor load control system is automatic onoff line. The
discharged from the machine. compressor will operate to maintain a set discharge line pressure and
is provided with an auto restart system for use in plants where the air
demand varies sufficiently to allow a compressor to shut down and
save power. Significant system volume will assist this and is
recommended.
WARNING
When the unit stops running as the result of low air demand,
normally indicated by auto restart light, it may restart and return
to load at any time.
CAUTION
This unit is not designed or intended to operate when
contaminated with silicone. Lubricants, greases or other items
containing silicone should not be used on this unit.
KEY
3. EMERGENCY STOP
When depressed will stop the compressor immediately. The Power 4. Turn on electrical isolator or disconnect. The Power on (5) indicator
on indicator will remain illuminated. The emergency stop button must will light, indicating that line and control voltages are available.
be released before the compressor can be restarted.
5. Check direction of rotation at initial start or following interruption in
power supply.
4. START/STOP
When switched to the ON position will cause the unit to start and run
in a loaded condition if there is a demand for air. If there is no demand,
the machine will run unloaded before stopping automatically. WARNING
When switched to the OFF position, will unload and stop the unit if Make sure that all protective covers are in place.
it is running. If the unit is in auto restart it will prevent the unit from Cooling air flow exhaust may contain flying debris. Safety
restarting when there is a demand for air. Protection should be worn at all times to avoid injury.
8. RESET BUTTON
Press button to reset the control system following compressor trip.
http://air.irco.com SSR UP5 11, UP5 15, UP5 18, UP5 22
20 OPERATING INSTRUCTIONS
NORMAL/EMERGENCY STOPPING
1. Switch the ON/OFF switch (4) to the OFF position. The compressor
will unload and stop.
2. Press EMERGENCY STOP button (3) and the compressor will stop
immediately.
CAUTION
After shutdown never allow unit to stand idle with pressure in
receiver/separator system.
If the air filter Check the Condition of filter. Change the air
indicator locks into filter if needed. Dusty environments require
the red position more frequent replacement or, optional high
before the 3000 dust filter CAUTION: Before beginning any work on the compressor, open,
hour/1 year change lock and tag the main electrical disconnect and close the isolation
(The indicator sould be checked with unit
out period valve on the compressor discharge. Vent pressure from the unit
stopped.)
by slowly unscrewing the coolant fill cap one turn. Unscrewing
First 150 hours Change the coolant filter. the fill cap opens a vent hole, drilled in the cap, allowing pressure
to release to atmosphere. Do not remove the fill cap until all
Each month or 100 Remove and clean package prefilter, pressure has vented from the unit. Also vent piping by slightly
hours replace if needed opening the drain valve. When opening the drain valve or the
coolant fill cap, stand clear of the valve discharge and wear
Check the cooler(s) for build up of foreign appropriate eye protection.
matter. Clean if necessary by blowing out
with air or by pressure washing.
Each year or Change the coolant filter.
Ensure that maintenance personnel are properly trained,
3000 hours
competent and have read the Maintenance Manuals.
Check scavenge screen for blockage, clean
if required.
Prior to attempting any maintenance work, ensure that:
Change the separator cartridge.
. all air pressure is fully discharged and isolated from the system. If
Change the Air Filter element. the automatic blowdown valve is used for this purpose, then allow
enough time for it to complete the operation.
Take coolant sample for fluid analysis.
Change the package prefilter. . the machine cannot be started accidently or otherwise.
Check the inlet valve flapper, recondition as
necessary.
. all residual electrical power sources (mains and battery) are
Visual Check of Drive Belts and tensioning isolated.
gas spring.
Pressure vessel Separator vessel and air receiver when Prior to opening or removing panels or covers to work inside
inspection fitted. a machine, ensure that:
frequency may be Fully inspect all external surfaces, and
otherwise defined by fittings. Report any excessive corrosion,
. anyone entering the machine is aware of the reduced level of
local or national mechanical or impact damage, leakage or
protection and the additional hazards, including hot surfaces and
legislation. other deterioration.
intermittently moving parts.
Every two years or Change drive belt and gas spring.
9000 hours
Replace the Ultra Plus Coolant at whichever . the machine cannot be started accidently or otherwise.
interval occurs first.
Check and replace all items included within Prior to attempting any maintenance work on a running
3000 hour service machine, ensure that:
. appropriate personal protective equipment is worn. 9. Replace and tighten oil fill cap.
1. Stop the machine, electrically isolate and vent all trapped pressure.
3. Remove the cartridge from the housing; place it in a sealed bag and CAUTION
dispose of it safely. This unit is not designed or intended to operate when
contaminated with silicone. Lubricants, greases or other items
containing silicone should not be used on this unit.
4. Clean the mating face of the housing.
5. Remove the new IngersollRand replacement cartridge from its COOLER CLEANING PROCEDURE
protective package. 1. Stop the machine, electrically isolate and vent all trapped pressure.
6. Apply a small amount of lubricant to the cartridge seal. 2. Remove the top cover to obtain access to the cooler.
SETTING THE PRESSURE SWITCH (1PS) TO CHECK THE LOWER SET POINT
TO CHECK THE MAXIMUM DISCHARGE PRESSURE Observe the line pressure fall and note the point at which the
(Pressure switch upper trip point) pressure switch closes (and loads the compressor).
Slowly close the isolation valve located adjacent to the compressor.
Observe the rise in pressure and ensure that the pressure switch TO ADJUST THE UPPER SET POINT
opens (and unloads the compressor) at the correct Maximum
discharge pressure. Remove the transparent cover and turn the adjuster [1]. The red
pointer will move. Turn the adjuster anticlockwise to increase the set
point or clockwise to decrease it.
The maximum discharge pressure is shown on the machine data plate.
TO ADJUST THE LOWER SET POINT
DO NOT exceed these figures.
Remove the transparent cover and turn the adjuster [2]. The green
pointer will move. Turn the adjuster anticlockwise to increase the set
point or clockwise to decrease it.
NOTE
The pressure switch scale is a guide only. Use the machine
pressure gauge to verify the upper and lower set points.
1. Stop the machine, electrically isolate and vent all trapped pressure.
3. Fit a 1/2 square drive wrench in the tension cam located above the
airend (access from front door). Turn clockwise 1/4 turn to Position II
to release gas strut tension on the belts.
4. Using a small screwdriver under the spring clip, ease the ball ends
off the spherical studs at the ends of the gas strut.
5. Replace the gas strut and the studs at the same time by removing
and replacing the studs then pushing the new gas strut firmly onto the
studs until it clicks into place.
6. Turn the tension cam clockwise 1/4 turn to Position III to raise and
support the airend. Place a block of wood or similar under the separator
tank for support.
9. Spin the drive to check alignment of the belt ribs on the pulleys
(sheaves).
A. Gas strut.
C. Tension cam.
NOTES:
Must be carried out by a competent electrician.
This work is recommended to be carried out only by an IngersollRand authorized service technician.
NOTES:
Must be carried out by a competent electrician.
This work is recommended to be carried out only by an IngersollRand authorized service technician.
fr
PARTS MANUAL
da
CATALOGUE DE PICES DTACHES RESERVEDELSKATALOG
nl RELAY OPTION
ONDERDELENKATALOGUS sv RESERVDELSKATALOG
de ERSATZTEILLISTE no RESERVEDELSKATALOG
it LISTA RICAMBI
4 99295362 1 Blower
18.5, 22kW / 15, 18.5kW HA
99295354 1 Blower
11, 15kW / 11kW HA
10 22071815 1 Fuse
2A 500V
C23
50 Hz STAR DELTA
550v 11, 22 kW
(18.5kWHA)
Service Items
C23 Star Delta 400V 15kW (11kWHA) C43/C37 Star Delta 220V 18.5kW (15kWHA)
550V 1122kW (18.5kWHA)
39250998 2 Contactors
39252036 3 Contactors C43
C23
39251061 1 Contactor
39255591 1 Relay, overload C37
39251319 2 Coil 39251079 1 Relay, overload
C23
39251319 1 Coil
C37
C37/C23 Star Delta 220V 15kW (11kWHA) 39251327 1 Coil
400V 18.5, 22kW (15, 18.5kWHA) C43
39251061 2 Contactors
C37 C60/C43 Star Delta 220V 22kW (18.5kWHA)
39252036 1 Contactor 39251004 2 Contactors
C23 C60
OPTIONS MANUAL
Intellisys Option
High Dust Option
Outdoor Module Option
PORO Option
This manual is provided to cover instructions and technical data The intended uses of this machine are outlined below and examples
for additional options to the standard UP compressor range. It is of unapproved usage are also given, however IngersollRand cannot
provided as a SUPPLEMENT to the standard operators and parts anticipate every application or work situation that may arise.
manuals and should NOT be used for the operation of the
complete machine.
IF IN DOUBT CONSULT SUPERVISION.
WARNING: Electrical shock risk. WARNING Pressurised vessel. WARNING Hot surface.
WARNING Pressurised component or WARNING Air/gas flow or Air discharge. Do not breathe the compressed air from this
system. machine.
Use fork lift truck from this side only. RESET Do not use fork lift truck from this side.
Read the Operation and Maintenance manual Do not operate the machine without the guard Lifting point.
before operation or maintenance of this being fitted.
machine is undertaken.
Installation of this compressor must be in accordance with AVOID INGESTION, SKIN CONTACT AND INHALATION OF
recognised electrical codes and any local Health and Safety Codes. FUMES
WARNING
Imposing a normal or emergency stop on the compressor will
only relieve presure upstream of the minimum pressure valve on
top of the separator tank.
If maintenance work is required downstream of this valve, ensure
that all pressure is relieved at the process vent point external to
the compressor
Ensure that the machine is operating at the rated pressure and that
the rated pressure is known to all relevant personnel.
WARNING
Any electrical connections or adjustments should only be
made by a suitably qualified electrician
Close and lock all access doors when the compressor is left
unattended.
Do not use extinguishers intended for Class A or Class B fires on
electrical fires. Use only extinguishers suitable for class BC or class
ABC fires.
Attempt repairs only in clean, dry, well lighted and ventilated areas.
Connect the compressor only to electrical systems that are
compatible with its electrical characteristics and that are within its rated
capacity.
Condensate disposal
As waste water regulations vary by country and region it is the
responsibility of the user to establish the limitations and regulations in
their particular area. IngersollRand and its associated distributors are
happy to advise and assist in these matters.
For further information, consult Material Data Sheets CCN
88303979 for ULTRAPlus Coolant.
The above information contains data supplied in support of United
Kingdom Control of Substances Hazardous to Health (C.O.S.H.H.)
regulations.
STARTING
2. Turn off electrical isolator.
Press Start [24]. The compressor will start and then load
automatically.
18 L.E.D.Not used.
INSTRUMENT PANEL FUNCTION
1 PACKAGE DISCHARGE PRESSURE L.E.D.
This will illuminate when the display indicates the package 19 DISPLAY SELECT BUTTON
discharge pressure. Press to index through compressor operating conditions. The
corresponding L.E.D. will illuminate adjacent to display.
This is used to select alternative status displays (after
2 AIREND DISCHARGE TEMPERATURE L.E.D. approximately 5 minutes, the display defaults to the package discharge
This will illuminate when the display indicates the airend discharge pressure). Depressing this button in the set point routine will cause exit
temperature. to checking machine for 2 seconds, then ready to start.
9 UNLOAD L.E.D. The arrow keys are also used to select pressure bands 1 (Y) or 2
This will illuminate when the compressor is running in unload mode. (B) during normal operation of the compressor.
By bleeding off a small amount from the regulator valve, which AIR FILTER
energises the Modulate Solenoid Valve, a reduction in the air signal The air filter is dirty or blocked and should be replaced.
to the pneumatic cylinder on the inlet valve allows the cylinder to
trim the inlet valve position as dictated by changing line pressure.
Modulation begins when the compressor reaches about 94% of the SEPARATOR ELEMENT
rated line pressure and is factory set to modulate down to The separator element is dirty or blocked and should be replaced.
approximately 70% of rated capacity.
AIREND TEMPERATURE
If the air demand decreases to a level below the 70% modulated The airend temperature reaches 97% of the high airend
output, the line pressure will increase slightly to the upper limit of the temperature set point (i.e. 106C (223F)).
pressure setting, when the compressor then changes to the Off line
control position and operates with the receiver vented.
FAILED CALIBRATION
During calibration routine, a 10% of scale error has been detected.
Ensure that the separator is completely blowndown and repeat
calibration.
EMERGENCY STOP
The emergency stop button is engaged.
OPTION
Revision C
85584282
KEY
1 15 22137293 1 Panel
2 39252937 2 Block, end stop *16 39191648 1 Plug
11 position
3 22074058 3 Block, terminal
*17 39191655 1 Plug
4 22076988 17 Block, terminal 16 position
5 22071823 5 Block, terminal
*18 39186101 1 Plug
Fuse
4 position
6 22074041 1 Block, terminal ground
*19 39191630 1 Plug
7 39252911 1 Block, terminal ground 5 position
1 15 22137293 1 Panel
2 39252937 2 Block, end stop *16 39191648 1 Plug
11 position
3 22074058 3 Block, terminal
*17 39191655 1 Plug
4 22076988 17 Block, terminal 16 position
5 22071823 5 Block, terminal
*18 39186101 1 Plug
Fuse
4 position
6 22074041 1 Block, terminal ground
*19 39191630 1 Plug
7 39252911 1 Block, terminal ground 4 position
1 15 22137293 1 Panel
2 39252937 2 Block, end stop *16 39191648 1 Plug
11 position
3 22074058 3 Block, terminal
*17 39191655 1 Plug
4 22076988 17 Block, terminal 16 position
5 22071823 5 Block, terminal
*18 39186101 1 Plug
Fuse
4 position
6 22074041 1 Block, terminal ground
*19 39191630 1 Plug
7 39252911 1 Block, terminal ground 5 position
9 35275494 1 Hub
10 39108949 2 Locknut
11 22396618 1 Instructions
13 39133467 8 Mount
14 95785192 1 Nipple
15 39146733 1 Plug
16 39203443 1 Suppressor
19 35246131 1 Terminal
OPTIONAL
MODULATION FIELD RETROFIT
SUPPLEMENTARY
OPERATORS INSTRUCTION
PARTS CATALOGUE
http://air.irco.com en
2 FOREWORD AND SAFETY
TAG
WARNING
Failure to adhere to these recommendations can
KEY LOCK
result in mechanical failure, property damage and
serious injury or death.
en http://air.irco.com
GENERAL INFORMATION 3
MODULATION CONTROL ACS CONTROL (INTELLISYS w/ MODULATION OPTION ONLY)
For those plants which have relatively high constant air demand For compressors supplied with IntellisysR control and modulation
relative to the compressor capacity, the recommended control mode is option, ACS control will allow the compressor to automatically switch
modulation. between online/offline and modulation control, depending on air
demand.
The modulation control system retains the features of the online /
offline control, but also provides for throttling of the inlet flow up to the If the air demand has decreased to a level below the 60 percent
offline air pressure setpoint value. modulated output, the line pressure will increase slightly to actuate the
IntellisysR. The compressor will then shift to the offline control
By applying line pressure to an adjustable modulator valve, the position, and operate unloaded with the compressor vented.
throttling position of the inlet valve is controlled, thus allowing the
modulator to trim the inlet valve position as dictated by the line It is sometimes desirable to begin modulation at a higher pressure than
pressure. the standard factory setting, thereby increasing the modulated capacity
at the time the IntellisysR is actuated. Refer to Figure 1 for modulated
The modulating pressure range is about 4 psig (0.3 BAR) and the capacities available when this is done.
modulator normally should be set to straddle the compressor rated
pressure. Modulation begins when the line pressure reaches about 99 The compressor will then operate to deliver full capacity air to the plant
percent of the compressor rated pressure and continues as/if the line system. If the plant air system pressure rises to that of the IntellisysR
pressure rises. Modulation becomes stable when the compressor offline set point, pressurized air will be sent to the inlet valve causing
output equals the plant air demand. When the modulation is at the it to close, and to the blowdown valve, causing it to open.
factory setting, the maximum capacity reduction will be approximately
60 percent of the compressor rated capacity (as indicated in Figure 1). The compressor will continue to run unloaded, but since pressure
levels have reduced, it will do so with a minimum power draw.
Capacity control of machines supplied with electropneumatic control
and the modulation option can be manually switched from The IntellisysR has a fixed minimum differential of 10 psi between the
online/offline to modulation (MOD) via the control mode switch (SS) offline air pressure setting and the online air pressure setting. The
located adjacent to the pressure switch. differential may be increased by adjusting the online air pressure
setting of the IntellisysR.
The automatic control selector (ACS) is designed to continuously
monitor the plant air demand and select either the online/offline, or
the modulate control mode whichever is most desirable at any time
during an operating day.
It allows the compressor to operate in its most efficient mode thereby
reducing power costs.
MODULATE TO
% OF RATED PRESSURE
94% CAPACITY When the compressor operates in the online/offline control mode,
the length of time the compressor remains in the offline condition is
MODULATE TO an indication of the plant air demand. IntellisysR controller is sensing
85% CAPACITY and awaiting a sufficient line pressure decrease before signaling a shift
to the online mode. If the offline time period is relatively short,
thereby indicating a high demand for air, it is preferable to shift the
MODULATE TO control system to upper range modulation.
72% CAPACITY The IntellisysR does this, and does it automatically if the compressor
unloads 3 times within a 3 minute time period.
If later, the plant demand decreases, and even under modulate control
MODULATE TO
the line pressure reaches the setting of the IntellisysR controller, and
60% CAPACITY
the control shifts to the offline mode, the time in this mode will still be
monitored. A long offline time period indicates a low plant air
demand, indicating the desirability of operating in the online/offline
mode.
% OF RATED LINE PRESSURE The IntellisysR then does this, and does it automatically if the
compressor operates unloaded for more than 3 minutes.
http://air.irco.com en
4 PARTS CATALOGUE
en http://air.irco.com
PARTS CATALOGUE 5
http://air.irco.com en
6 PARTS CATALOGUE
UP6 1530 (60Hz), UP5 1122kW (50Hz) STANDARD CONTROL w/ MODULATION
15 92368687 2 Screw
16 39155346 1 Tee * Not illustrated
http://air.irco.com en
10 INSTALLATION
MODULATION KIT INSTALLATION INSTRUCTIONS UP6 1530 (60Hz), UP5 1122kW (50Hz)
1. Remove the top panels and open the starter box and compressor 9. Modulation Kit Solenoid Wiring:
access panels.
2. Attach the tube fittings and shuttle valve to the solenoids per the Intellisys Control 60Hz
assembly drawing. The nipple (95946059) and shuttle valve
a. Attach solenoid cable assemblies to 5SV and 6SV.
(39127261) are installed in the 6SV OUT port.
b. Connect leads 10 to BTS11.
Solenoid valve identification: c. Connect leads 2 to Intellisys terminal J55.
5SV 54774302
6SV 22163307 d. Connect the ground leads to the starter panel ground.
(The selector switch is not used on Intellisys models.)
3. Attach the solenoid valves to the solenoid bracket with M4 screws
(96743182). Standard Control 60Hz and 50Hz
a. Install the onoff line / modulation selector switch on the starter
4. Attach the solenoid bracket to the blower shroud using the existing box side in the approximate location shown on assembly
extruded holes and M6 selfthreading screws (92368687). drawing. (The selector switch is not used on Intellisys models.)
5. Assemble the regulator valve (39199476/39199489) and bulkhead b. Attach solenoid cable assemblies to 5SV and 6SV.
fitting (54514583) as shown on the assembly drawing.
c. Connect the selector switch to terminal 10 on the starter panel
using 16 AWG wire.
6. Install the bulkhead fitting / regulator valve assembly to the air baffle
in the approximate location as shown on the assembly drawing. d. Connect leads 10 to the selector switch.
e. Connect leads 2 to terminal 2 on the starter panel.
7. Remove and discard the existing tubing from 3SV (blowdown
f. Connect the ground leads to the starter panel ground.
solenoid) to 1SV (load/unload solenoid).
5SV OUT to regulator valve IN (through the bulkhead d. Connect the ground leads to the starter panel ground.
connector)
(The selector switch is not used on Intellisys models.)
Regulator valve OUT tee to shuttle valve IN *
Shuttle valve OUT to 1SV (load/unload solenoid) IN * 10.Replace top panels. Close starter box and compressor access
panels.
* Route tubing through the opening at the bottom of the air baffle.
en http://air.irco.com
12 OPERATING INSTRUCTIONS
LOCKNUT
ADJUSTING SCREW
en http://air.irco.com