Air System Sizing Summary for EPCC

Project Name: EPCC 07-20-2017


Prepared by: AAC 09:41AM

Air System Information


AirSystemName EPCC Number of zones 1
EquipmentClass PKG ROOF Floor Area 383.4 m
AirSystemType SZCAV Location Doha, Qatar

Sizing Calculation Information


CalculationMonths Jan to Dec Zone L/s Sizing Sum of space airflow rates
SizingData Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Totalcoilload 163.1 kW Load occurs at Jun 1500
Sensiblecoilload 149.1 kW OA DB / WB 45.4 / 30.5 C
CoilL/satJun1500 13214 L/s Entering DB / WB 22.6 / 16.5 C
MaxblockL/s 13214 L/s Leaving DB / WB 13.3 / 12.7 C
SumofpeakzoneL/s 13214 L/s Coil ADP 12.2 C
Sensibleheatratio 0.914 Bypass Factor 0.100
m/kW 2.4 Resulting RH 53 %
W/m 425.5 Design supply temp. 13.5 C
Waterflow@5.6Krise N/A Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


ActualmaxL/s 13214 L/s Fan motor BHP 6.94 BHP
StandardL/s 13199 L/s Fan motor kW 5.51 kW
ActualmaxL/(s-m) 34.47 L/(s-m) Fan static 250 Pa

Outdoor Ventilation Air Data


DesignairflowL/s 350 L/s L/s/person 18.42 L/s/person
L/(s-m) 0.91 L/(s-m)

Hourly Analysis Program v4.90 Page 1 of 9


Zone Sizing Summary for EPCC
Project Name: EPCC 07-20-2017
Prepared by: AAC 09:41AM

Air System Information


AirSystemName EPCC Number of zones 1
EquipmentClass PKG ROOF Floor Area 383.4 m
AirSystemType SZCAV Location Doha, Qatar

Sizing Calculation Information


CalculationMonths Jan to Dec Zone L/s Sizing Sum of space airflow rates
SizingData Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m) L/(s-m)
Zone 1 128.7 12554 12554 Jul 1600 16.2 383.4 32.74

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m) L/(s-m)
Zone 1
Technical Room 3 17.1 Jul 1600 1671 2.7 61.2 27.31
Pantry 1 7.0 Jul 1600 686 1.0 22.8 30.09
Switch Gear Room 1 70.2 Jul 1600 6854 7.2 177.0 38.72

Hourly Analysis Program v4.90 Page 2 of 9


Air System Design Load Summary for EPCC
Project Name: EPCC 07-20-2017
Prepared by: AAC 09:41AM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.4 C / 30.5 C HEATING OA DB / WB 10.6 C / 6.0 C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 20 m 1736 - 20 m - -
Wall Transmission 491 m 3183 - 491 m 1632 -
Roof Transmission 383 m 57129 - 383 m 13569 -
Window Transmission 20 m 1400 - 20 m 684 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 15 m 550 - 15 m 268 -
Floor Transmission 383 m 5225 - 383 m 0 -
Partitions 15 m 81 - 15 m 0 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 11502 W 11501 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 30855 W 30854 - 0 0 -
People 19 1329 942 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 3000 0 - 0 0
Safety Factor 10% / 5% 11599 47 0% 0 0
>> Total Zone Loads - 127587 990 - 16152 0
Zone Conditioning - 127461 990 - 2534 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 12864 L/s 0 - 12864 L/s 0 -
Ventilation Load 350 L/s 9705 13074 350 L/s 1776 0
Supply Fan Load 13214 L/s 5506 - 13214 L/s -5506 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 5% 6379 - 5% 808 -
>> Total System Loads - 149051 14063 - -388 0
Central Cooling Coil - 149051 14072 - 0 0
>> Total Conditioning - 149051 14072 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 3 of 9


Space Design Load Summary for EPCC
Project Name: EPCC 07-20-2017
Prepared by: AAC 09:41AM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' Technical Room '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.7 C / 30.4 C HEATING OA DB / WB 10.6 C / 6.0 C
OCCUPIED T-STAT 22.0 C OCCUPIED T-STAT 21.1 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 6 m 411 - 6 m - -
Wall Transmission 72 m 493 - 72 m 238 -
Roof Transmission 61 m 9241 - 61 m 2166 -
Window Transmission 6 m 429 - 6 m 205 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 3 m 112 - 3 m 54 -
Floor Transmission 61 m 834 - 61 m 0 -
Partitions 0 m 0 - 0 m 0 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 1836 W 1836 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 1000 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1000 0 - 0 0
Safety Factor 10% / 5% 1557 9 0% 0 0
>> Total Zone Loads - 17129 189 - 2663 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' Technical Room '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 36 0.317 - 250 - 121
WINDOW 1 4 3.339 0.811 286 298 137
S EXPOSURE
WALL 35 0.317 - 243 - 117
WINDOW 1 2 3.339 0.811 143 112 68
DOOR 3 1.703 - 112 - 54
H EXPOSURE
ROOF 61 3.371 - 9241 - 2166

Hourly Analysis Program v4.90 Page 4 of 9


Space Design Load Summary for EPCC
Project Name: EPCC 07-20-2017
Prepared by: AAC 09:41AM

TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' Pantry '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.7 C / 30.4 C HEATING OA DB / WB 10.6 C / 6.0 C
OCCUPIED T-STAT 22.0 C OCCUPIED T-STAT 21.1 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 2 m 451 - 2 m - -
Wall Transmission 23 m 166 - 23 m 76 -
Roof Transmission 23 m 3443 - 23 m 807 -
Window Transmission 2 m 143 - 2 m 68 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 2 m 75 - 2 m 36 -
Floor Transmission 23 m 311 - 23 m 0 -
Partitions 15 m 81 - 15 m 0 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 684 W 684 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 8 539 282 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 639 14 0% 0 0
>> Total Zone Loads - 7031 296 - 987 0

TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' Pantry '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
S EXPOSURE
WALL 13 0.317 - 89 - 43
DOOR 2 1.703 - 75 - 36
W EXPOSURE
WALL 10 0.317 - 76 - 33
WINDOW 1 2 3.339 0.811 143 451 68
H EXPOSURE
ROOF 23 3.371 - 3443 - 807

Hourly Analysis Program v4.90 Page 5 of 9


Space Design Load Summary for EPCC
Project Name: EPCC 07-20-2017
Prepared by: AAC 09:41AM

TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' Switch Gear Room '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.7 C / 30.4 C HEATING OA DB / WB 10.6 C / 6.0 C
OCCUPIED T-STAT 22.0 C OCCUPIED T-STAT 21.1 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 253 m 1765 - 253 m 840 -
Roof Transmission 177 m 26727 - 177 m 6264 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 4 m 150 - 4 m 72 -
Floor Transmission 177 m 2412 - 177 m 0 -
Partitions 0 m 0 - 0 m 0 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 5310 W 5310 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 27355 W 27354 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 6386 6 0% 0 0
>> Total Zone Loads - 70248 126 - 7176 0

TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' Switch Gear Room '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 117 0.317 - 799 - 387
E EXPOSURE
WALL 24 0.317 - 192 - 79
S EXPOSURE
WALL 113 0.317 - 774 - 374
DOOR 4 1.703 - 150 - 72
H EXPOSURE
ROOF 177 3.371 - 26727 - 6264

Hourly Analysis Program v4.90 Page 6 of 9


System Psychrometrics for EPCC
Project Name: EPCC 07-20-2017
Prepared by: AAC 09:41AM

June DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 45.4 0.02162 350 400 9705 13074
Vent - Return Mixing Outlet 22.6 0.00927 13214 797 - -
Central Cooling Coil Outlet 13.3 0.00891 13214 797 149051 14072
Supply Fan Outlet 13.6 0.00891 13214 797 5506 -
Cold Supply Duct Outlet 14.0 0.00891 12554 797 - -
Zone Air - 22.4 0.00893 12554 808 127461 990
Zone Direct Exhaust Outlet 22.4 0.00893 350 808 - -
Return Plenum Outlet 22.4 0.00893 12204 808 0 -
Duct Leakage Air Outlet 13.6 0.00891 661 797 - -
Return Duct Outlet 22.0 0.00893 12864 807 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2944.1 W/(L/s)
Site Altitude = 9.8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (C) (L/s) (ppm) (W) (W)
Zone 1 127587 Cooling 127461 22.4 12554 808 0 0

Hourly Analysis Program v4.90 Page 7 of 9


System Psychrometrics for EPCC
Project Name: EPCC 07-20-2017
Prepared by: AAC 09:41AM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 10.6 0.00393 350 400 -1776 0
Vent - Return Mixing Outlet 14.7 0.00393 13214 759 - -
Central Cooling Coil Outlet 14.7 0.00393 13214 759 0 0
Supply Fan Outlet 15.0 0.00393 13214 759 5506 -
Cold Supply Duct Outlet 15.0 0.00393 12554 759 - -
Zone Air - 14.8 0.00393 12554 769 -2534 0
Zone Direct Exhaust Outlet 14.8 0.00393 350 769 - -
Return Plenum Outlet 14.8 0.00393 12204 769 0 -
Duct Leakage Air Outlet 15.0 0.00393 661 759 - -
Return Duct Outlet 14.8 0.00393 12864 769 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2944.1 W/(L/s)
Site Altitude = 9.8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (C) (L/s) (ppm) (W) (W)
Zone 1 -16152 Deadband -2534 14.8 12554 769 0 0

Hourly Analysis Program v4.90 Page 8 of 9


Psychrometric Analysis for EPCC
Project Name: EPCC 07-20-2017
Prepared by: AAC 09:41AM

Location: Doha, Qatar


Altitude: 9.8 m.
Data for: June DESIGN COOLING DAY, 1500

1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet 0.024
4. Supply Fan Outlet
5. Duct Heat 1
6. Room Air
7. Return Duct Outlet 0.022
0.020

Specific Humidity ( kg/kg )


0.018
0.016
0.014
0.012
34 5 72 0.010
6 0.008
0.006
0.004
0.002
0.000
0 5 10 15 20 25 30 35 40 45
Temperature ( C )