NFPA20Update 2013Edition
GoalsandObjectives
Bytheendofthispresentation,the
participantwillbeableto:
NFPA20Update 2013Edition 1. RepeattherevisioncycleforNFPA20
2. Discusshowtousetheprovisionsofthe2013
KennethE.Isman,P.E.F.S.F.P.E.
Kenneth E Isman P E F S F P E editionevenifapreviouseditionisbeing
di i if i di i i b i
VicePresidentofEngineering enforced
3. Designafirepumpsystemforaverytall
building
4. Discussthedifferencesbetweenlimitedservice
controllersandregularfirepumpcontrollers
Whydoesthismatter? Whydoesthismatter?
Weallneedtokeepuptodate Newtechnologyoralternatearrangements
Limitourliability ForExample:NFPA20 2007
Mostchangesareclarificationofoldtext 1.5Equivalency.Nothinginthisstandardisintended
topreventtheuseofsystems,methods,or
Manufacturers will change their product lines
Manufacturerswillchangetheirproductlines devices of equivalent or superior quality strength
devicesofequivalentorsuperiorquality,strength,
tomeetthenewrules fireresistance,effectiveness,durability,andsafety
Newtechnologyoralternatearrangements overthoseprescribedbythisstandard.
(Equivalency) Systemsmeetingthe2013editionofNFPA20
areequivalentorsuperiortothosemeeting
the2007edition
1
5/1/2013
NFPA202013 WaterMistPumps
FirePumpInstallationIssues Anumberofchangesthroughoutthe
document
Clarifiedtherulesformultiplesmallvolume
positivedisplacementpumpsusedasasingle
pumpingunitforawatermistsystem
Singlecontroller
HelpsNFPA20workwithNFPA750andlisted
watermistsystems
WithinSightof Plans(4.2.3.1)
ThereareanumberoflocationsinNFPA20 Plansneedtobedrawntoscale
whereitspecifiesthattwodifferentpartsof Listof14itemsthatneedtobeincludedon
thepumpinstallationneedtobewithin plans
sightofeachother
Thistermwasdefinedaseachoftheitems
beingvisibleandnotmorethan50ftdistant
fromtheotheritem
9 10
PumpsinSeries CommitteesConcernsaboutPumpsinSeries
Proposalstoputallpumpsinseriesinthe Verticalstagingofpumpsishardtodo
samepumproom correctly
Ultimately,theseproposalsfailed,butbeon Ifthehighpumpstartsbeforethelowpump,the
thelookoutforthisinfutureeditions highpumpcouldbedamaged
Intercontrolwiringbetweencontrollerscouldbe
I l ii b ll ld b
damaged
Communicationbetweenpeopleinseparate
pumproomsisdifficult
Testingofpumpsisdifficult
11
2
5/1/2013
VerticalStagingofPumps PumpsinSeries
FirePump
Controller To High Zone To High Zone
Standpipe Risers Standpipe Risers
High Zone Pump
(Where will water To Low Zone
FirePump
Controller
go for testing?) S d i
Standpipe
Risers High
FirePump
Test equipment is
Controller
FirePump
Controller Zone easier to arrange
To Low Zone Pump
Standpipe Risers
16
SuctionPipeWaterVelocity AgeofWaterSupplyTests
Standardhassaidforyearsthatthemaximum Anewsection4.6.1.2wasaddedtorequire
velocityis15ft/secinsuctionpipe thatwatersupplytestsusedtodeterminethe
Standardhasalsoprovidedminimumpipesizes(in adequacyofwatersuppliesbedonewithin12
Tables)anddefinedmaximumflows monthsofthesubmissionoftheworking
Whenyouputtogetherthedefinedmaximumflows
h h h d f d fl plans.
l
andminimumpipesizes,youendupwithvelocities
of15.1ft/secand15.3ft/secinsomecases
Committeeclarifiedthatisokaybydeleting15
ft/secruleandaddinganotetotheTableonwhy
thesepipesizeswereselected
18
3
5/1/2013
TestHeaders AccuracyofMeters
Thevalveonthepipetothetestheaderneeds Forflowmeterlinesthatareloopedbackto
tobeinstalledevenifthetestheaderisnotin pumpsuctionorwatertanks
anareasubjecttofreezing(4.20.3.3.1) Ameanswillneedtobeincludeddownstream
Thevalveneedstobesupervisedclosed ofthemetertotesttheflowsothatthe
(4.16.2) accuracyofthemetercanbechecked
Testheadercanbeindoorsaslongasitisnot Couldbeadifferenttestheaderfromtheone
inthepumproomandwatercanbe usedtotestthepump
dischargedduringtesting(4.20.1.4) Ortherecouldbeapipeconnectingthe
dischargefromthemetertothetestheader
19 20
ElbowsandTeesinSuctionfor
MeterArrangement
HorizontalSplitCasePumps
Newthreedimensional(isometric)figures
wereaddedtotheannextoshowcorrectand
incorrectcombinationsofteesandelbows
22
ElbowsandTees ElbowsandTees
23 24
4
5/1/2013
QuestionsfromPart1 HighRiseBuildings
1. Whenweretheissuesdealingwiththe2013 Definition: morethan
editionofNFPA20votedonbythe 75ft(23m)fromthe
membershipoftheNFPA? lowestleveloffire
departmentvehicle
2. Whyshouldyoucarewhatisinthe2013 accesstohighestfloor
h h fl
forhumanoccupancy
editionsincethejurisdictionyouworkinhas
>75ft
probablynotyetlegallyadoptedit?
Section5.7VeryTallBuildings VeryTallBuilding
WaterSupplyTanks(Section5.7.1.5)
Theautomaticandmanualfillvalvecombination
foreachtankortankcompartmentshallhaveits
ownconnectiontooneofthefollowing
A
Astandpiperiserthatissuppliedwithabackupfire
standpipe riser that is supplied with a back up fire
pump
Areliabledomesticrisersizedtomeetthe
requirementsof5.7.1.4(fullflowdemandofsystem)
5
5/1/2013
Section5.8FirePumpBackUp VeryTallBuilding
Forpumpsservingzonesthatarepartiallyor
whollybeyondthepumpingcapabilityofthe
FireDepartment,doeitherofthefollowing:
Provideabackuppump(fullymeetingallsystem
d
demands)
d)
Provideanauxiliarymeansofmeetingallofthe
systemdemands(acceptabletotheAHJ)
ReliablePowertoElectricMotors LimitedServiceController
Theannexnotethatdiscussestheattributes Ratherthaneliminatethem,upgradedthe
ofareliablepowersupplywasmodified circuitbreaker
Removedthediscussionofpoweroutages Onlydifferencebetweenfullservice
duringstorms controllerswillbetheisolationswitch
ItisnottheintentofNFPA20torequire
It is not the intent of NFPA 20 to require
standbypowerforallfirepumps
TheimpairmentproceduresofNFPA25could
beusedwhenpoweroutagesoccurrather
thanforcingeveryonewithanelectricmotor
drivenfirepumptoinstallagenerator
33 34
DikesandFuelTanks CleaningupFuel
Thecommitteeclarifiedachangethatthey Acommentwasacceptedbythecommitteeto
triedtomakelastcycletostatethatdikesare requirealistedactivefuelmaintenance
notrequiredwhendoublewalltanksareused systemtobeinstalledonallfuelstoragetanks
ThiswasoverturnedbytheNFPAmembership
Theissueisstillvalid,thereneedstobeaplan
forhowallownerswillmaintaintheirfuel
35
6
5/1/2013
AcceptanceTestForm QuestionsAfterPart2
Theforminthestandardwasupdatedwithall 3. Atankholding15,000gallonsisbeingused
ofthenewrequirementssinceitwaslast asapartofafireprotectionsystemforthe
updated topfloorsinabuilding600fttall.Howmany
automaticfillvalvesdoesthetankneed?
4. Aftermanufacturersstartimplementingthe
rulesinthe2013editionofNFPA13,whatis
themaindifferencegoingtobebetweena
limitedservicecontrollerandaregular(full
service)controller?
37
39