Beruflich Dokumente
Kultur Dokumente
Engineering Services
FAN 351
The greatest advantage of the fan-coil system is its flexibility for adaptation to many
building requirements. The fan-coil conditioner system is primarily applied to air
condition perimeter spaces. Proper conditions within the perimeter space are
obtained by use of terminal units called room fan-coil air conditioners. The basic
elements of these units are a finned-tube coil and a fan section (Figure 1).
Fan-coil systems are generally classified into two major groups; single pipe systems
(2-pipe) and multipipe systems (3 or 4-pipe). A single pipe system contains a single
supply of water to each fan-coil unit and a single return. Cold or hot water is
supplied depending on the season. A multipipe system contains a double supply of
water, one hot and one cold to each fan-coil unit. A 3-pipe system has a common
return, while a 4-pipe system has a separate return for hot and for cold water
supplies.
9/83 1
Engineering Report: H215
The chilled water and hot water piped to each fan-coil conditioner is supplied from
central heating and cooling equipment. The type of water piping required will
depend on whether both chilled and hot water are simultaneously available at each
fan-coil conditioner, or are available separately by manual or automatic change-
over.
Room fan-coil conditioners are similar to unit ventilators except that fan-coil units
generally have a smaller capacity and they admit either no outside air or a small,
fixed quantity of outdoor air. (Some units are provided with a damper to admit from
0 to 100 percent outside air. This damper can be controlled automatically.) The units
are generally available in nominal sizes of 200, 300, 400, and 600 CFM. Several
manufacturers also offer 800 and 1200 CFM models.
Although fan-coil units are usually sold with covers, most manufacturers provide
basic units for furred-in, recessed and concealed installation and for use with covers
made by sheet metal fabricators.
The temperature of the space served by vertical fan coil unit may be controlled by a
standard heating cooling deadband thermostat mounted in one of the end
compartments of the unit. Horizontal units are usually installed in or near the ceiling.
A wall mounted thermostat is recommended for such installations. This
recommendation also applies to most concealed and recessed vertical units. Control
pressure from the thermostat operates throttling valves, or three-way mixing valves
to control the flow of water through the coil. When automatic damper control is
provided, the usual manual control assembly is omitted and a damper actuator is
applied. Valves for fan coil units should have flared connections. Factory piping
packages and direct shipment of valves to fan-coil unit manufactures are available.
Features
2. Confined Room Air Circulation: Since most units recirculate only room air (some
use outside air), circulation of the air between rooms is minimized.
9/83 2
Engineering Report: H215
Two-Pipe Systems
The two-pipe system is the oldest and lowest first cost method. During cold weather,
hot water is circulated to all fan-coil units. During hot weather, chilled water is
circulated to all fan-coil units.
Chiller Controls
As TT-4 senses the outside air temperature, it reversely readjusts the setpoint of
TCR-3. TT-6 senses the hot water supply temperature, depending on the offset
9/83 3
Engineering Report: H215
Figure 2
9/83 4
Engineering Report: H215
incurred, produces an output signal through TCR-3 adjusting the position of valves
TV-1 and TV-2 in sequence. TCR-3 should be reset to provide hot water at a
temperature which is always 10 to 15 degrees higher than normally required. This
permits each unit thermostat to provide individual space control under all conditions.
Heating Switchover
When PSM-1 is in the "Heating" position, zone valves TV-3, TV-4, TV-5 and TV-6
are in their normal positions. Hot water flows though TV-3 and TV-5 to the zone,
then back to the main hot water circuit through TV-4. Valve TV-6 is closed and
thermostat TC-1 is inoperative.
Cooling Switchover
When PSM-1 is placed in the "Cooling" position, TV-4 is closed and TV-3 opens to
return water. The zone pump temporarily recirculates all the water to avoid dumping
hot water into the chilled water circuit. When the return water cools to 90F, TC-1
opens TV-5 to chilled water and opens TV-6 to chilled water return, thus completing
the switchover from heating to cooling. The chiller should not be started until the
switchover is complete and flows have been established through the chiller.
Unit Controls
Unit thermostat TC-2 operates the water supply to the unit coil. As stated earlier,
TC-2 may be a wall mounted thermostat or a thermostat mounted within the unit.
The valve may be a throttling valve or a three-way mixing valve, as shown in figures
8 and 9.
If the unit valve is a throttling valve, the volume of water circulated by the zone
pump is variable. If this volume is reduced appreciably, an objectionable increase in
pressure drop across the valve will result unless a pump with a flat pressure-volume
characteristic is used, and a system bypass is used to maintain a relatively constant
flow through the system.
If the unit valve is a three-way mixing valve, the volume of water circulated by the
zone pump is constant since a varying portion of the water flows through the unit
coil while the reset bypasses the coil.
Thermostat TC-2 is direct acting during heating operation and reverse acting during
cooling operation. Switchover is accomplished by changing supply air pressure to
TC-2 by means of switch PSM-1 and three-way air valve ASV-1.
9/83 5
Engineering Report: H215
Chiller Controls
Each zone water heater is controlled by a receiver controller TCR-3 operating steam
valve TV-1. As TT-4 senses outside air temperature, it reversely readjusts the
setpoint of TCR-3. TT-6 senses the hot water supply temperature, depending on the
offset incurred, produces an output signal through TCR-3 adjusting the position of
TV-1. TCR-3 should be reset 10 to 15 degrees higher than normally required. This
permits each unit thermostat to provide individual space control under all conditions.
A second steam valve operated in sequence is not required unless the zone heater
is quite large.
Heating Switchover
When PSM-1 is in the "Heating" position, zone valves TV-2, TV-3 and TV-4 are in
their normal positions and TCR-3 controls TV-1. Water flows from the zone heater
through TV-2 to the units in that zone and then back to the zone heater.
9/83 6
Engineering Report: H215
Cooling Switchover
When PSM-1 is placed in the "Cooling" position, steam valve TV-1 is closed to shut
off the steam supply to the water heater by 3-way air valve ASV-2. The zone pump
temporarily recirculates all the water. When the return water cools down to 90F,
thermostat TC-1 closes TV-2 and opens TV-3 and TV-4, thus permitting circulation
of chilled water to the zone.
Figure 3
9/83 7
Engineering Report: H215
Comparison
The control arrangement shown in Figure 2 uses common sources of chilled and hot
water for all zones. The control arrangement in Figure 3 has a common source of
chilled water for all zones, but has a separate water heater for each zone. Three-
way air valve ASV-2 of Figure 3 may be deleted if there is no steam supply to the
water heater when the system is on cooling operation.
Three-Pipe Systems
The three-pipe system is more versatile than the two-pipe system because this
system can supply both hot and chilled water to the fan coil units throughout the
year. The need for central changeover is eliminated. Each fan coil unit functions
independently of every other unit in the building because its control valve selects
either hot or chilled water depending on the space needs. A common return is used
for both hot and chilled water supplies. Figure 10 shows the terminal unit piping
arrangement. Energy loss is not as large as one might think with a common return
because little or no mixing occurs during Summer and Winter seasons. Mixing will
occur during periods of reduced heating or cooling loads, but with both hot and cold
water temperatures reversely readjusted to outside air temperature, the energy loss
is minimized. Despite these factors three pipe systems are usually quite inefficient
and are seldom installed today. However, energy conservation potential does exist
for present systems.
The central heating and cooling controls outlined in figure 2 is the same
configuration that would be used in a three-pipe system, except no season
changeover controls are needed. A heating/cooling deadband thermostat is required
for each unit.
This system features central cooling with zone heating. It's the same as the two-pipe
system with zone heaters (Figure 3) except that no season changeover controls are
needed. A receiver-controller is needed for each zone heater with the output placed
directly on the zone steam valve TV-1, rather than through air switching valve ASV-
2, as shown in Figure 3. A heating/cooling deadband thermostat is needed to
control each fan coil unit.
9/83 8
Engineering Report: H215
9/83 9
Engineering Report: H215
Though the individual control and piping vary for application purposes, the four-pipe
fan-coil system consists of basically the same equipment as the two-pipe system.
A four-pipe fan-coil system is designed to provide hot and cold water at each of its
fan-coil units the year round. In effect, each unit is a separate zone and functions
independently. The unit's control valve selects either hot or cold water, depending
on the requirement at the time of selection. A four-pipe system completely isolates
the cold and hot water systems so that the piping for each system can be designed
independently, allowing for diversity of application. Four-pipe systems can be
separated into two basic types; those using room units with single coils and those
using room units with split coils.
System Features
9/83 10
Engineering Report: H215
9/83 11
Engineering Report: H215
Multi-Unit Control
In many cases building areas are divided into relatively small rooms or offices, each
served by a single unit. Each of these units is controlled by a separate thermostat
and valve. For larger areas, however two or more units may be required. In such
cases a single wall mounted thermostat can serve as many as eight or ten units,
provided the thermostat is located to respond to representative conditions. If valve
top thermostats are employed in such areas, it is recommended that no more than
four units be controlled from a single thermostat located in a representative unit. If
there are more than four units, they should be divided into groups of four or less
with a separate valve top thermostat serving each group.
Valves
Although it is recommended that each unit have its own control valve, it is possible
to control a group of units with a single control valve arranged to serve the units
under control of a single wall mounted thermostat.
One serious disadvantage of this method is that later subdivision of the space
requires extensive piping changes. It also requires very accurate sizing of orifices or
adjustment of balancing cocks to assure even heat distribution to the units.
The following piping arrangements are examples of typical applications for terminal
unit piping. It is important that the contractor and unit manufacturer involved
understand each of the arrangements. Figures 8-13 and their explanations clearly
identify the basic piping arrangements and valve applications for the two-, three-
and four-pipe systems.
9/83 12
Engineering Report: H215
Figure 8
The piping arrangement shown in Figure 9 is also used in a two-pipe system but
utilizes a three-way valve. This arrangement can also be used for either a cooling or
a heating application. When used in a heating application, the valve is usually piped
normally open to the coil; when used in a cooling application, the valve is usually
piped normally closed to the coil; assuming in both applications that a direct acting
thermostat is used. The valve can be controlled by either a valve top thermostat or a
room thermostat.
Figure 9
9/83 13
Engineering Report: H215
Figure 10
The piping arrangement shown in Figure 11 is used in a four-pipe double coil
application. It utilizes two (2) three-way sequencing valves. The heating coil, piped
normally open to the coil, operates over a 4-8 psi spring range; the cooling coil,
piped normally closed to the coil, operates over a 9-13 psi spring range. The heating
valve can be controlled by either a valve top thermostat or a room thermostat. The
cooling valve is positioned by a valve actuator.
Figure 11
9/83 14
Engineering Report: H215
The piping arrangement shown in Figure 12 is also used in a four-pipe double coil
application. It utilizes one normally open throttling valve and one normally closed
throttling valve. The heating coil is controlled by the normally open valve with a 3-6
psi spring range. The cooling coil is controlled by the normally closed valve with a 9-
13 psi spring range. The heating valve is controlled by a valve top thermostat or a
room thermostat. The cooling valve is positioned by a valve actuator.
Figure 12
Figure 13
9/83 15