SR469 - Motor Settings Auto-Config Report

OVERVIEW

Device Summary Generated at : Apr 30 2015 20:28:16


File Name C:\Documents and Settings\All
Users\Documentos\GE Power Man
agement\469PC\gabriel.469
Order Code 469
Firmware Version 5.2x

Input Parameters

Motor Name Plate Information


Full Load Amps 219 A

Locked Rotor Amps as % of FLA 570 %

Motor Nameplate Voltage 4000 V

Service Factor 1.0

HOT Safe Stall Time 15 sec

COLD Safe Stall Time 22 sec

Motor Temperature
Insulation Class F

Insulation Class Temperature Rise 105 C

Motor Class Other

Motor Class Temperature Rise 85 C

Motor Cooling Time Constants (Running) 15 min

Motor Cooling Time Constants (Stopped) 30 min

Number of Stator RTDs 6

Stator RTD Type 100 Ohm Platinum

Number of Bearing RTDs 2

Bearing RTD Type 100 Ohm Platinum

Bearing RTD Alarm Temperature 85 C

Bearing RTD Trip Temperature 90 C

Number of Ambient RTD 1

Ambient RTD Type 100 Ohm Platinum

Ambient RTD Alarm Temperature 20 C

Ambient RTD Trip Temperature 40 C

Version 5.23Page 1
SR469 - Motor Settings Auto-Config Report

Input Parameters(Continued)

System Information
System Frequency 60 Hz

Phase Rotation ABC

Switching Device Breaker

Breaker/ Starter Status 52B

You have selected the operating device as Breaker .Short Circuit Protection will be

enabled,however it is important to verify that the breaker is rated to interrupt the

maximum available fault curent Using Short circuit protection with a breaker

not rated to interrupt the fault current can result in personal injury and

equipment damage

Current Sensing
Phase CT Primary 300 A

Ground CT Connection Residual

Ground CT Secondary 5

Ground CT Primary 300 A

Differential CT Connection Residual

Differential CT Primary 300 A

Differential CT Secondary 5A

Voltage Sensing
Voltage Transformer Connection Type Open Delta

VT Ratio 33.33

VT's connected on Line Side

Voltage Element - Frequency DISABLED

Motor Starting
Acceleration Time at minimum voltage 21 Sec

Acceleration Time at Rated Voltage 4 Sec

Number of starts per hour 2

Time between motor start commands 30 Min

Motor Restart Time 15 Sec

Version 5.23Page 2
SR469 - Motor Settings Auto-Config Report

Calculated Settings

The following motor and system parameters will be programmed to the settings file

System Setup
Motor Full Load Amps 219 A

Motor Nameplate Voltage 4000 V

Nominal System Frequency 60 Hz

System Phase Sequence ABC

Phase CT Primary 300 A

Ground CT Primary 300 A

Ground CT Type 5 A Secondary

Phase Differential CT Primary 300 A

Phase Differential CT Type 5 A Secondary

VoltageTransformer Connection Type Open Delta

Voltage Transformer Ratio 33.33 :1

Digital Inputs
Starter Status Switch Start Aux b

469 Thermal Model


Curve Style Standard

Overload Pickup Level 1.15 FLA

Unbalance k Factor 7

Cool Time Constant Running 15 min

Cool Time Constant Stopped 30 min

Hot/Cold Safe Stall Ratio 0.68

RTD Blasing On/Yes

RTD Blas Minimum 40 C

RTD Blas Center Point 125 C

RTD Blas Maximum 155 C

Thermal Capacity Alarm Latched

Thermal Capacity Alarm Relays Alarm

Thermal Capacity Alarm Level 75 % used

Thermal Capacity Alarm Events On/Yes

Overload Trip Relays Trip

Standard Overload Curve Number 5

The above Thermal Model Protection Setpoints will be used to protect your motor.

The overload curve has been calculated based on hot and cold safe stall times provided.

The curve selection assumes a uniform motor curve supplied by motor manufacturer.

The curve recommended by the Motor Settings Auto-Config should be compared to

curve supplied by the manufacturer to ensure motor protection.

Version 5.23Page 3
SR469 - Motor Settings Auto-Config Report

Calculated Settings (Continued)

Short Circuit Trip


Short Circuit Trip Latched

Overreach Filter On/Yes

Short Circuit Trip Relays Trip

Short Circuit Trip Pickup 7.1 CT

Intentional Short Circuit Trip Delay 0 ms

Short Circuit Trip Backup Off/No

Warning : Short circuit protection should only be used if the operating device is rated to break the

maximum possible fault current. Please confirm that the breaker is rated appropriately

before putting 469 into service with Short Circuit Protection enabled.

Overload Alarm
Overload Alarm Unlatched

Overload Alarm Relays Alarm

Overload Alarm Events On/Yes

Overload Alarm Delay 1 s

Mechanical Jam
Mechanical Jam Trip Latched

Mechanical Jam Trip Relays Trip

Mechanical Jam Pickup 3.00 xFLA

Mechanical Jam Delay 2 s

Current Unbalance
Current Unbalance Alarm Unlatched

Current Unbalance Alarm Relay Alarm

Current Unbalance Alarm Pickup 15 %

Current Unbalance Alarm Delay 6 s

Current Unbalance Alarm Events On/Yes

Current Unbalance Trip Latched

Current Unbalance Trip Relays Trip

Current Unbalance Trip Pickup 20 %

Current Unbalance Trip Delay 2 s

Ground Fault
Ground Fault Alarm Unlatched

Ground Fault Alarm Relays Alarm

Version 5.23Page 4
SR469 - Motor Settings Auto-Config Report

Calculated Settings (Continued)

Ground Fault
Ground Fault Alarm Pickup 0.2 CT

Intentional GF Alarm Delay 200 ms

Ground Fault Alarm Events On/Yes

Ground Fault Trip Latched

Ground Fault Trip Relays Trip

Ground Fault Trip Pickup 0.25 CT

Intentional GF Trip Delay 200 ms

Differential
Phase Differential Trip Latched

Phase Differential Trip Relays Trip

Differential Trip Pickup While Starting 0.25 CT

Differential Trip Delay While Starting 200 ms

Differential Trip Pickup While Running 0.1 CT

Differential Trip Delay While Running 0 ms

Acceleration Timer
Accleration Timer Trip Latched

Acceleration Timer Trip Relays Trip

Acceleration Timer from Start 25.20 s

Start Inhibit
Start Inhibit Block On/Yes

Jogging Block
Jogging Block On/Yes

Maximum Starts/Hour Permissible 2

Time Between Starts 30 min

Restart Block
Restart Block On/Yes

Restart Block Time 15 s

RTD Types
Stator RTD Type 100 Ohm Platinum

Bearing RTD Type 100 Ohm Platinum

Ambient RTD Type 100 Ohm Platinum

RTD Alarms
Open RTD Sensor Alarm Latched

Version 5.23Page 5
SR469 - Motor Settings Auto-Config Report

Calculated Settings (Continued)

RTD Alarms
Open RTD Sensor Alarm Relays Alarm

Open RTD Sensor Alarm Events On/Yes

RTD Short/Low Temp Alarm Latched

RTD Short/Low Temp. Alarm Relays Alarm

RTD Short/Low Temp. Alarm Events On/Yes

Stator RTDs

RTD #1 RTD #2
Application Stator Application Stator
Name Stator1 Name Stator2
Alarm Unlatched Alarm Unlatched
Alarm Relays Alarm Alarm Relays Alarm
Alarm Temperature 125 C Alarm Temperature 125 C
Alarm Events On/Yes Alarm Events On/Yes
Trip Latched Trip Latched
Trip Relays Trip Trip Relays Trip
Trip Temperature 155 C Trip Temperature 155 C

RTD #3 RTD #4
Application Stator Application Stator
Name Stator3 Name Stator4
Alarm Unlatched Alarm Unlatched
Alarm Relays Alarm Alarm Relays Alarm
Alarm Temperature 125 C Alarm Temperature 125 C
Alarm Events On/Yes Alarm Events On/Yes
Trip Latched Trip Latched
Trip Relays Trip Trip Relays Trip
Trip Temperature 155 C Trip Temperature 155 C

RTD #5 RTD #6
Application Stator Application Stator
Name Stator5 Name Stator6
Alarm Unlatched Alarm Unlatched
Alarm Relays Alarm Alarm Relays Alarm
Alarm Temperature 125 C Alarm Temperature 125 C
Alarm Events On/Yes Alarm Events On/Yes
Trip Latched Trip Latched
Trip Relays Trip Trip Relays Trip
Trip Temperature 155 C Trip Temperature 155 C

Version 5.23Page 6
SR469 - Motor Settings Auto-Config Report

Calculated Settings (Continued)

Bearing RTDs

RTD #7 RTD #8
Application Bearing Application Bearing
Name Bearing1 Name Bearing2
Alarm Unlatched Alarm Unlatched
Alarm Relays Alarm Alarm Relays Alarm
Alarm Temperature 85C Alarm Temperature 85C
Alarm Events On/Yes Alarm Events On/Yes
Trip Latched Trip Latched
Trip Relays Trip Trip Relays Trip
Trip Temperature 90C Trip Temperature 90C

Ambient RTD

RTD #12
Application Ambient
Name Ambient
Alarm Unlatched
Alarm Relays Alarm
Alarm Temperature 20C
Alarm Events On/Yes
Trip Latched
Trip Relays Trip
Trip Temperature 40C

Version 5.23Page 7
SR469 - Motor Settings Auto-Config Report

Calculated Settings (Continued)

Under Voltage
Undervoltage Active Only If Bus Energized Off/No

Undervoltage Alarm Unlatched

Undervoltage Alarm Relays Alarm

Undervoltage Alarm Pickup 0.9 Rated

Starting Undervoltage Alarm Pickup 0.85 Rated

Undervoltage Alarm Delay 10 s

Undervoltage Alarm Events On/Yes

Undervoltage Trip Latched

Undervoltage Trip Relays Trip

Undervoltage Trip Pickup 0.85 Rated

Starting Undervoltage Trip Pickup 0.8 Rated

Undervoltage Trip Delay 3 s

Over Voltage
Overvoltage Alarm Unlatched

Overvoltage Alarm Relays Alarm

Overvoltage Alarm Pickup 1.05 Rated

Overvoltage Alarm Delay 10 s

Overvoltage Alarm Events On/Yes

Overvoltage Trip Unlatched

Overvoltage Trip Relays Trip

Overvoltage Trip Pickup 1.1 Rated

Overvoltage Trip Delay 3 s

Phase Reversal
Voltage Phase Reversal Trip Latched

Voltage Phase Reversal Trip Relays Trip