11/29/2016 SunRack1000andSunRack900Cabinets

SPARCEnterpriseSunRack1000/900/IIEquipmentRack
MountingGuide

1
CHAPTER

SunRack1000andSunRack900Cabinets
TheSunRack1000andtheSunRack900cabinetscanencloseSunSPARCEnterpriseM3000/M4000/M5000servers,
storageproducts,andqualifiedthirdpartyequipment.

Thisdocumentcontainsthefollowingsections:

TechnicalInformation

MountingSpecifications

StabilizingtheCabinet

1.1TechnicalInformation
TheSunRack1000comesasa42rackunit(U)ora38Uenclosure.TheSunRack900comesasa38Uor36Uenclosure.
Entrylevelandmidrangeserverscanbemountedorpreinstalledintheseequipmentcabinets.

NoteTheSunRack1000/900cabinetshaveroundRETMArailholes.

FIGURE11illustratesSunRack1000/900withonemodularpowersupply(MPS)andTwoMPSs.

FIGURE11 SunRack900WithModularPowerSupplies

https://docs.oracle.com/cd/E1985501/8195367/Syst_cab_info.html#0_pgfId5529 1/12
11/29/2016 SunRack1000andSunRack900Cabinets

FigureLegend
1 SunRack900WithOneModularPowerSupply
2 SunRack900WithTwoModularSupplies

1.1.1PhysicalSpecifications
UsethefollowingtabletodeterminespacerequirementsfortheSunRack1000andtheSunRack900.

TABLE11 SunRack1000Dimensions

Characteristic 42U 38U

Height 2019mm/79.5in. 1880mm/74in.

Width 597mm/23.5in. 597mm/23.5in.

Depth 1000mm/39.8in. 1000mm/39.8in.

Weight 193kg/426lb 168kg/370lb

TablelistingSunRack1000dimensions.

https://docs.oracle.com/cd/E1985501/8195367/Syst_cab_info.html#0_pgfId5529 2/12
11/29/2016 SunRack1000andSunRack900Cabinets

TABLE12 SunRack900Dimensions

Characteristic 38U 36U

Height 1880mm/74in. 1880mm/74in.

Width 597mm/23.5in. 597mm/23.5in.

Depth 900mm/35.4in. 900mm/35.4in.

Weight 168kg/370lb 172kg/380lb

TablelistingSunRack900dimensions.

FIGURE12illustratestheSunRack100042Ushippingcratedimensions.

FIGURE12 SunRack100042/38RackUnitShippingDimensions

https://docs.oracle.com/cd/E1985501/8195367/Syst_cab_info.html#0_pgfId5529 3/12
11/29/2016 SunRack1000andSunRack900Cabinets

FigureLegend
1 Height,2184mm/86in.
2 Width,1080mm/42.5in.
3 Depth,1506mm/59.3in.

FIGURE13illustratesthetopandfrontdimensionsofaSunrack.

FIGURE13 SunRack900WithCabinetExtenderTopandFrontDimensions

FigureLegend
1 Length,doorsopen,2194mm/86.4in.
2 Length,doorsclosed,1000mm/35.4in.
3 Height,1880mm/74in.
4 Width,597mm/23.5in.

FIGURE14andFIGURE15illustratethefootprintofaSunRack1000andSunRack900.

FIGURE14 SunRack1000BottomView

https://docs.oracle.com/cd/E1985501/8195367/Syst_cab_info.html#0_pgfId5529 4/12
11/29/2016 SunRack1000andSunRack900Cabinets

FigureLegend
1 Cabinetwidth,599mm/23.6in. 7 Depth,holetocastercenter,90mm/3.5in.
2 Widthbetweenpadcenters,516mm/20.3in. 8 Depthbetweencasterx,620mm/24.4in.
3 Widthbetweenholes,386mm/15.2in. 9 Depth,castertohole,90mm/3.5in.
4 Width,sidetopadcenter,42mm/1.7in. 10 Depthbetweenpads,800mm/31.5in.
5 Width,sidetohole,107mm/4.2in. 11 Depth,padtorear,50mm/2in.
6 Depth,fronttohole,200mm/7.9in. 12 Frontofcabinet

FIGURE15 SunRack900BottomView

https://docs.oracle.com/cd/E1985501/8195367/Syst_cab_info.html#0_pgfId5529 5/12
11/29/2016 SunRack1000andSunRack900Cabinets

FigureLegend
1 Cabinetwidth,599mm/23.6in. 7 Depth,holetocastercenter,100mm/3.9in.
2 Widthbetweenpadcenters,516mm/20.3in. 8 Depthbetweencasterx,620mm/24.4in.
3 Widthbetweenholes,386mm/15.2in. 9 Depth,castertohole,90mm/3.5in.
4 Width,sidetopadcenter,42mm/1.7in. 10 Depthbetweenpads,800mm/31.5in.
5 Width,sidetohole,107mm/4.2in. 11 Depth,padtorear,50mm/2in.
6 Depth,fronttohole,90mm/3.5in. 12 Frontofcabinet

1.1.2ElectricalSpecifications
TABLE13andTABLE14displaysystemelectricalspecificationsandreceptaclemodelnumbers.

TABLE13 SunCabinet(ModularPowerSystem)ElectricalSpecificationsAmericas,Japan,Taiwan

Parameter Value

https://docs.oracle.com/cd/E1985501/8195367/Syst_cab_info.html#0_pgfId5529 6/12
11/29/2016 SunRack1000andSunRack900Cabinets

Inputcurrent Voltagerange 208VACthreephase

Current,maximum 45Aat208VACperphase

Currentfrequencyrange 5060Hz

VoltAmpere 16200VA
rating

Connectortype NorthAmerican,Japan, 260AIEC3094Pinfor208VACthreephase,preinstalledwiththe


Taiwan cabinet

Receptacletype NorthAmerican,Japan, 260AIEC3094Pinfor208VACthreephase,HubbellC460P9Wor


Taiwan equivalent

TABLE14 SunCabinet(ModularPowerSystem)ElectricalSpecificationOtherCountries

Parameter Value

Inputcurrent Voltagerange 230/400VACthreephase

Current,maximum 32Aperphase

Currentfrequency 5060Hz
range

VoltAmpere 22080VA
rating


Other 232AIEC3095Pinfor230/400VACthreephase,preinstalledwiththe
Connectortype cabinet.

Receptacletype Other 232AIEC3095Pinfor230/400VACthreephase,HubbellC532R6Sor


equivalent

1.1.3VibrationLimitations
TABLE15liststheallowablevibrationforM3000/M4000/M5000serversinaSunRack1000/900.

https://docs.oracle.com/cd/E1985501/8195367/Syst_cab_info.html#0_pgfId5529 7/12
11/29/2016 SunRack1000andSunRack900Cabinets

TABLE15 AllowableVibrationfortheM3000/M4000/M5000Servers

Operating NonOperating

Vertical:0.15g Vertical:3.0mmpkpk/0.5g,

Horizontal:0.10g 5to500Hz,sweptsine

5to500Hz,sweptsine Horizontal:3.0mmpkpk/0.25g,

5to500Hz,sweptsine

TablelistingtheallowablevibrationforM3000/M4000/M5000serverinaSunRack1000/900.

1.1.4SpaceandThermalSpecifications
Formaintenanceaccess,entrylevelandmidrangeserversinracksrequireaminimumoffourfeettothefront,threefeetto
therear,andthreefeetfromthetop.rackscanbeplacednexttoeachothersincetherearenosideclearancerequirements
duringoperation.

Bothentrylevelandmidrangeserversmustmaintaintheminimumthermaldistancebetweentherearoftheserverinan
rack(914mm/36in.)andanyobstructionsorwalls.

1.1.5ServiceArea
TheSunSPARCEnterpriseM3000/M4000/M5000serversareaccessedfromthetopsurfaces.Astepladdermaybe
requiredformaintenancedependingupontheheighttheseserversaremountedinthecabinet.Ensureanadequateservice
areaformaintenancework.

FIGURE16 FrontandRearMaintenanceAccessandThermalSpecifications

https://docs.oracle.com/cd/E1985501/8195367/Syst_cab_info.html#0_pgfId5529 8/12
11/29/2016 SunRack1000andSunRack900Cabinets

FigureLegend
1 914mm(36inches)accessatrear
2 Reardoor
3 1219mm(48inches)accessatfront
4 Frontdoor
5 914mm(36inches)accessfromthetop

1.1.6AccessRoute
Ifyourexistingloadingdockmeetsheightorramprequirementsforastandardfreightcarriertruck,youcanuseapallet
jacktounloadtheserver.Ifnot,youmustprovideastandardforkliftorothermeanstounloadtheserver,orrequestthe
serverbeshippedinatruckwithaliftgate.

Allserversnotshippedinanrackshouldbeliftedonlybypropercomputerliftingequipmenttopreventpersonalinjuryor
damagetoserverequipment.

Eachserverthatisnotpreinstalledinanrackisshippedinaseparatecrate.Apalletjackisrequiredtomoveeachshipping
cratetotheserverlocation.

Leaveeachserverinitsshippingcrateuntilitreachesitsfinaldestination.Ifthecratedoesnotfitthroughtheplanned
accessroute,partiallydisassembleit.

Theentireaccessroutetoyourcomputerroomshouldbefreeofraisedpatternsthatcancausevibration,andtheroute
mustmeettherequirementslistedinTABLE16.

TABLE16 AccessRouteRequirements

https://docs.oracle.com/cd/E1985501/8195367/Syst_cab_info.html#0_pgfId5529 9/12
11/29/2016 SunRack1000andSunRack900Cabinets

WithShippingPallet WithoutShippingPallet

Minimumdoorheight 2184mm/86in. 2019mm/79.5in.

WithShippingPallet WithoutShippingPallet
Minimumelevatordepth 1506mm/59.3in. 1506mm/59.3in.

Maximumincline 10 10

Minimumelevator,palletjack,andfloorloadingcapacity 544kg(1200lb)
(maximumweightperserver)

Tablelistingaccessrouterequirements.

1.1.7ServerGuidelines
AsyouplanyourspaceneedsfortheSunracks,keeptheseconditionsinmind:

Eachrackcontainingmidrangeserversrequiresitsownpowercords,connectedtoseparatepoweroutlets.See
ElectricalSpecifications,fordetailsonelectricalrequirements.

Circuitbreakersaresuppliedbythecustomerasrequiredbylocal,state,ornationalelectricalcodes.

Theserversrequireelectricalcircuitsthataregroundedtoearth.

1.2MountingSpecifications
TheSunRack1000/900canencloseuptotwentyone2UM3000servers,six6UM4000serversandthree10UM5000
servers.IfyouaremountingserversinaSunRack900,anoptionalcabinetextenderisavailabletoextendthedepthofthe
rackfromthereartoenablethedoortoclose.

1.2.1InstallingtheCabinetExtender(Optional)
1.Removethereardooroftherackandsetitaside.

2.Placethecabinetextenderontothedoorhingepinsattherearoftherackandsecureinplace.
(FIGURE17)

3.Mountthereardooronthecabinetextender.

https://docs.oracle.com/cd/E1985501/8195367/Syst_cab_info.html#0_pgfId5529 10/12
11/29/2016 SunRack1000andSunRack900Cabinets

FIGURE17 InstallingtheCabinetExtender

1.3StabilizingtheCabinet
TheSuncabinetcanbepermanentlymountedtothefloorusingthesamebracketsthatsecuredthecabinettotheshipping
pallet.Thecabinetsideofthemountingbracketsareslottedtoallowforverticalpositioning.

FIGURE18illustratesamountingbracketonaSunRack1000andtheholespacingrequiredtosecurethecabinet
permanentlytothefloor.

FIGURE18 SunRack1000MountingBracketsandHoleSpacingforFloorMounting

https://docs.oracle.com/cd/E1985501/8195367/Syst_cab_info.html#0_pgfId5529 11/12
11/29/2016 SunRack1000andSunRack900Cabinets

FIGURE19 HoleSpacingforFloorMounting

FigureLegend
1 Width,1000mm/39.5in.
2 Depth,388mm/15.2in.



SPARCEnterpriseSunRack1000/900/IIEquipment
819536715
RackMountingGuide

Copyright2009,2011,Oracleand/oritsaffiliates.Allrightsreserved.FUJITSULIMITEDprovided
technicalinputandreviewonportionsofthismaterial.

https://docs.oracle.com/cd/E1985501/8195367/Syst_cab_info.html#0_pgfId5529 12/12