IEC 61508
Data Declaration
DOCUMENT NO. MTL08FMEA4521/2
This document is issued as a summary of the key factors affecting the application of the equipment
as a sub-system being part of a Safety System intended to conform with the requirements of
IEC61508 - Functional Safety of Electrical/Electronic/Programmable Electronic Safety Systems.
The hardware has been subjected to a Failure Modes and Effects Analysis (FMEA) to determine the
specific failure modes and failure rates with the relevant results presented herein.
Product Description
The MTL4521 and MTL5521 are loop powered modules which enable a device located in the
hazardous area to be controlled from the safe area. The output current available to the hazardous
area is limited to comply with the requirements of IIC gas atmospheres.
The definitions for product failure of the MTL4521 and MTL5521 were determined as:-
FMEA/DD4521/07/08 Page 1 of 2
FMEA
IEC 61508
Example of use in a safety function
In this example, the application context is assumed to be:
According to the definitions of IEC61508 the failure rates for these categories are then (FITs)
Model sd su dd du
MTL4521 or MTL5521 0 436 0 0
In this example, the safe failure fraction is 100% (because the device is loop-powered it is impossible
for it to energise the output unless the input is energised). So the devices meet the hardware
architecture constraints to be used as single devices in Safety Instrumented Functions up to SIL3.
Notes
FITs means failures per 109 hours or failures per thousand million hours.
Source data for this analysis is taken from IEC TR 62380:2004 Reliability Data Handbook.
Failure mode distributions are taken principally from IEC 62061: Safety of Machinery.
Unless the application context is to de-energise on demand, proof testing must be carried
out according to the application requirements, but it is recommended that this be carried out
at least once every three years. For de-energise on demand applications, proof testing is
unnecessary.
Consideration should be made of the normal lifetime for a device of this type which would
be in the region of ten years.
There are no internal diagnostic elements of this product.
For all other product parameters related to its application (voltage range, environment, etc.)
please refer to the published MTL data sheet for this product, available at www.mtl-
inst.com.
FMEA/DD4521/07/08 Page 2 of 2