ALFORSAN HOTEL

Quality Check Sheet for Form No. : AFISR/MEP/ E/022


CHECK SHEET FOR INSTALLATION OF 11KV MV Rev. No. : 00

SWITCHGEAR PANEL Date : 31-DEC-2013 :

IR No. :
Rev. No.:
Date :
DANW ETTS ENGINEER Date
AY
1 Check the name plates & labelling are correct as per material submittals.

2 Check the location and mounting are correct.

Check the orientation of MV Switchgear as per Approved SLD & GA


3 Diagram as per Manufacturers recommendations.

4 No dents or damage on the MV Switchgear Panel.

5 Check MV Switchgear Panels are protected from civil works.

6 Check the clearance around the panel as per ADDC/ RSB regulations.

Check the proper fixing of Panel Board Components


7 (VCB,Busbar,CTs,VTs,PTs,Control Panel & etc)

Check the Cleanliness and Readiness of the room prior to Installation of


8 the 11KV MV Switchgear Panel.

Ensure All bus bar bolts are tight in the specified torque limit of the
9 manufacturer.

Ensure the BMS System Containment prior to installation of 11KV MV


10 Switchgear Panel.

11 Ensure all SIN & NCN are close out and approved by consultant

12 Check all bus bar sizes in according with the approved drawing

Check dust settlement on the bus bar links and supports should be cleaned
13 by blower

14 Check the meters, indication lamps,handle,lock & keys etc.

15 Check the painting closing & open position of doors of HV panel.

Comments if any:

Checked by System Specialist


Checked by ETTS Reviewed by FIBREX Witnessed By WSA ENGINEER
DANWAY

Signature: Signature: Signature: Signature:

Name: Name: Name: Name:


Date: Date: Date: Date