As per Chapter 6 of TS As per appd.

Remarks
Documents
dt.06/01/15
Suitable filter circuits shall be provided in in all Less than or
chargers to limit the ripple content (peak to peak) in equal to 3% RMS
output voltage to 1% irrespective of dc load level, (without any
when they are not connected to battery. battery
connected).
Necessary temperature sensors shall be provided in Not specified.
the mid location of battery banks and shall be wired
to the respective charger for feedback control. The
manufacturer shall demonstrate this feature during
testing of each charger.
Uniform and stepless adjustments of voltage setting Not specified.
(in manual and auto mode) shall be provided on the
front of the charger panel covering the entire float
charger output range specified.
For limiting the output voltage of the charger a Not specified.
potentiometer shall be provided to set the upper
limit of this(boost charging) voltage anywhere in
the output range specified in the boost charging
mode.
The charger output voltage variation shall be within +/-1(% omitted) Text correction
+/_1% of the set value for AC input voltage of set value for required.
variation of +/_10%,frequency variation of +/-5% , +/_10% of input
a combined voltage and frequency variation of voltage variation
+/_10% and a DC load variation from zero to full and +/-5%
load. variations for 0-
100% load
variations
Stepless adjustments of the load limiter setting shall Not specified.
be possible from 80% to 100% of rated output
current of charger.
All battery chargers shall have 2 MCCBs in the Only one MCCB
input side to receive cables from two sources. provided in the
input circuit.
Mechanical interlock shall be provided such that Not specified.
only one will be closed at a time.
MCCB shall be of P2 duty and suitable for As per revised
continuous duty. standards for
LV switchgear
IEC 60947
Part2,MCCBs
do not have
any P1 duty or
P2
duty(defined
in IEC 157-
1).Now, they
are applicable
only to MV
and HV
breakers.
Alternatively,
MCCBs have
Ultimate
Breaking
Capacity(Icu)
and Service
Breaking
Capacity(Ics)
in the new
standard.
MCCBs shall have aux. contacts for annunciation. Not specified.
One AC voltmeter and one AC ammeter with Only input
selector switches shall be provided in all chargers. voltmeter is
specified.
A potential contact for float/boost mode shall be Not specified.
provided for external interlocks.
Cl.6.18.3.10 The charger shall be fabricated from Structure and Deviation in
2.0mm cold rolled sheet steel and shall be of folded front door are thickness/type
type construction. made of 3mm and of
2mm CRCA sheet construction.
respectively.
However, rear
door and side
covers are made
of 1.6mm CRCA
sheet. Not
specified reg.
folded type
construction.
The chargers shall have hinged double leaf doors Only single door
provided on front and backside for adequate access provided in front
to the chargers internals. and rear.
The control wiring shall be carried out with PVC 0.5 sq.mm
insulated,1.5 sq.mm stranded copper wire stranded copper
wires used for
control card
wiring.
After primer application, two coats of finishing Paint shade
synthetic enamel paint of RAL7035 shall be approved is IS
applied, unless required otherwise by the 631 of IS:5 for
Employer.The inside of the chargers shall be glossy inside, outside
white. and
structure.Type of
paint is
epoxy(powder
coating).

Also, toggle switches have been approved for lighting control instead of rotary switches
and float/boost selection is through toggle switches in the front of the panel instead of
lockable selector switches.
HVDC Engg. May please confirm whether these toggle switches are permitted.