Components of AHU | 21

Condensation Pan: Droplet Eliminator:


Applied as a standard feature in all cooling Droplet eliminators are applied as a stand-
sections. It is manufactured from stainless ard feature in all cooling exchangers. Drop
steel. Being double inclined, it allows very eliminators manufactured from polypro-
fast drainage of the condensated water. pylene which is resistant to temperatures
Undersides of condensation pans are of up to 130 C. Their casing is manufac-
insulated with mineral wool. The standard tured from stainless steel as a standard
drain pipe diameter is 1. It does not allow feature. Standard rail mechanism allows
accumulation of water and ensures quick easy removal and servicing.
drainage.

COOLING COIL

FL50 x 100

FL60 x 100

FL60 x 110

FL60 x 120
FL20 x 20

FL20 x 30

FL30 x 30

FL30 x 40

FL30 x 50

FL30 x 60

FL40 x 40

FL40 x 50

FL40 x 60

FL40 x 70

FL50 x 50

FL50 x 60

FL50 x 70

FL50 x 80

FL50 x 90

FL60 x 60

FL60 x 70

FL60 x 80

FL60 x 90

FL70 x 70

FL70 x 80

FL70 x 90
Size

B 612 612 918 918 918 918 1224 1224 1224 1224 1530 1530 1530 1530 1530 1530 1836 1836 1836 1836 1836 1836 1836 2142 2142 2142
B 772 772 1078 1078 1078 1078 1384 1384 1384 1384 1690 1690 1690 1690 1690 1690 1996 1996 1996 1996 1996 1996 1996 2302 2302 2302
H 612 918 918 1224 1530 1836 1224 1530 1836 2142 1530 1836 2142 2508 2814 3120 1836 2142 2508 2814 3120 3426 3732 2142 2508 2814
H 722 1028 1028 1334 1640 1946 1334 1640 1946 2252 1640 1946 2252 2618 2924 3230 1946 2252 2618 2924 3230 3536 3842 2252 2618 2924
L 765 765 765 765 765 765 765 765 765 765 765 765 765 765 765 765 765 765 765 765 765 765 765 765 765 765

COOLING COIL

FL100 x 100

FL100 x 110
FL70 x 100

FL70 x 110

FL80 x 100

FL80 x 110

FL80 x 120

FL80 x 130

FL90 x 100

FL90 x 110

FL90 x 120

FL90 x 130
FL80 x 80

FL80 x 90

FL90 x 90
Size

B 2142 2142 2508 2508 2508 2508 2508 2508 2814 2814 2814 2814 2814 3120 3120
B 2302 2302 2668 2668 2668 2668 2668 2668 2974 2974 2974 2974 2974 3280 3280
H 3120 3426 2508 2814 3120 3426 3732 4038 2814 3120 3426 3732 4038 3120 3426
H 3230 3536 2618 2924 3230 3536 3842 4148 2924 3230 3536 3842 4148 3230 3536
L 765 765 765 765 765 765 765 765 765 765 765 765 765 765 765

5.2.7. The Drainage System


The majority of cooling coils have been For this reason, traps must be used for
placed to allow supply air to pass through pans to avoid water accumulation in air
them onto the units. As a result, they are handling units.
subjected to negative (-) static pressure.
If measures to balance pressure on the Example:
condensation drainage line have not been Negative Static Pressure = 65 mmWG
taken, air that is suddenly and quickly Height H = 85 mmSS
sucked back from drainage tubes will For safety = 20 mmSS
cause the condensate to accumulate in Hmin = Static Pressure + 20 mm
the drain pan.

The water which collects as the unit


continues to operate will be accumulated
with the air current and cause the water
filling the drain pan to seep into air intake
ducts and/or water flooding damage in
the building.