Busduct and
Aluminium
Products
Division
01
MATERIAL FOR busduct attenuation of dynamic impacts during MATERIAL busduct components
conductor as well as providing easy chosen, enclosures are directly welded Busduct enclosures are connected to a
access to connection terminals and in- to GCB casings. A flexible connection main transformer body using two flan-
stalled devices; this is especially useful involves a circuit breaker flange being ged half shells bolted together which are
for carrying out maintenance and im- affixed by a rubber compensator which fixed to busduct enclosures by rubber
provements. Interface boxes and exis is connected to a busduct enclosure compensators thus allowing thermal
ting sections of conductors are designed and conductively bridged by aluminium and mechanical dilatation. The rubber
to facilitate the replacement of bus joints. The connection is designed in ac- compensators are bridged by alumi
hings or even of the entire machine if ne cordance with the specific type of the nium links in one or three phases in
cessary. On customer request, infrared circuit breaker utilized. Conductors are order to maintain the conductivity of
thermometers can be added to the con- connected to GCB terminals using flexi the enclosures. Earthing is carried out UNIT TRANSFORMER CONNECTION
nection terminals of larger generators. ble silver-plated copper joints. in accordance with a grounding diagram.
Branch busduct enclosures are connec-
GENERATOR NEUTRAL POINT GENERATOR CIRCUIT BREAKER CONNECTION TO INSTRUMENT ted to unit transformers using two flan-
CONNECTION STEEL PLATFORM CUBICLES ged half shells bolted together or are
fixed using rubber compensators that
Generator neutral point boxes are spe- EGE also supplies the calculation, design Connection to instrument cubicles is fa- allow for thermal and mechanical dila-
cifically designed for the type of gene and manufacture of a steel platform un- cilitated using two flanged half shells bol- tation. The entire system is designed
rator used. They are equipped with ope der a generator circuit breaker made ted together which are fixed to busduct for easy erection on site and for the
nings for easy erection and maintenance according to the type of the circuit brea enclosures by rubber compensators, simplification of the future maintenance
on site. Inter-phase star connection is ker in use, site conditions, the civil ar- permitting thermal and mechanical di- of flexible silver-plated copper joints con
done using flat copper bars fixed with rangement, and the customers specific latation. The entire system is designed necting silver-plated aluminium termi-
insulators to neutral point box casings, requirements. The standard surface for easy erection on site and to simplify nals at connection points on both sides.
or using a special E-shaped aluminium treatment method is hot dip galvanisa- future maintenance. The rubber com- Rubber compensators are bridged by
tube fixed by insulators to a neutral tion. The steel support platform under pensators are bridged by aluminium aluminium links in one or three phases
point box. Neutral point boxes are fixed a generator circuit breaker can be ship links in order to preserve the conductivi- in order to maintain the conductivity of
to generator casings by a flanged bolt ped together with the delivery of gene ty of enclosures. Earthing occurs at only enclosures. Earthing is carried out in
CONNECTIONS connection. rator busducts. one place. accordance with a grounding diagram.
10
11
CONNECTION POINTS
assembly