Beruflich Dokumente
Kultur Dokumente
2702 <-in
inlet temp-> 70.0 F dry bulb Valid temperature deltaH = -50.30 btu/lb 58.41 0.242 25.2767
inlet RH-> 50.0 % range: H in = 25.30 btu/lb 58.42 0.242 25.2831
outlet temp-> 104.0 F dry bulb -80 to +211.94 H out = 75.60 btu/lb 58.43 0.242 25.2896
outlet RH-> 94.0 % generated tables-> 58.44 0.242 25.2960
CFM in-> 2,000.0 dry air density in = 0.0740 lb/ft^3 58.45 0.243 25.3025
altitude (ft.)-> 0 dry air density out = 0.0655 lb/ft^3 58.46 0.243 25.3090
Btu/hr = -446,409 total vapor density in = 0.0006 lb/ft^3 58.47 0.243 25.3154
Btu/hr = -73,463 sensible vapor density out = 0.0030 lb/ft^3 58.48 0.243 25.3219
*Btu/hr = -372,945 latent moist air density in = 0.0745 lb/ft^3 58.49 0.243 25.3283
Tons of heating 37.20 moist air density out = 0.0685 lb/ft^3 58.50 0.243 25.3348
SHR = ~ *t *sat p *H in wb
CFM out = 2,256.7 humidity ratio in = 0.0078 lb(m)/lb(da) 51.0 0.185 20.8232 <-in
moisture added lb/min = 5.61 humidity ratio out = 0.0457 lb(m)/lb(da) 52.0 0.192 21.3883
moisture added lb/hr = 336.84 53.0 0.199 21.9641
pressure = 14.696 psia 54.0 0.206 22.5508
dewpoint in = 50.52 F sat. vapor pressure in = 0.3633 psia 55.0 0.214 23.1487
dewpoint out = 101.91 F sat. vapor pressure out = 1.0709 psia 56.0 0.222 23.7582
wet bulb in = 58.44 F vapor pressure in = 0.1816 psia 57.0 0.230 24.3796
wet bulb out = 102.22 F vapor pressure out = 1.0066 psia 58.0 0.239 25.0133 <-in
dry air pressure in = 14.5139 psia 59.0 0.247 25.6595
negative capacity indicates heating dry air pressure out = 13.6889 psia 60.0 0.256 26.3188
*assumes water temp = leaving air temp 61.0 0.266 26.9914
processes: heating/ cooling/ humidifying/ dehumidifying vapor massflow in = 1.1514 lb/min
vapor massflow out = 6.7654 lb/min -69 0.000 -17.3243
Psychrometric formulae extracted from- dry air massflow in = 147.9175 lb/min -59 0.001 -14.8265
2001 ASHRAE HANDBOOK: FUNDAMENTALS dry air massflow out = 147.9175 lb/min -49 0.002 -12.3133
Ch.6, "Psychrometrics" -39 0.003 -9.7746
Enter input to yellow cells only -29 0.005 -7.1952
If you must enter wet bulb or dew point instead of RH, -19 0.009 -4.5526
then simply adjust RH as necessary to obtain the -9 0.014 -1.8138
desired wet bulb or dew point temperature. 1 0.023 1.0674
11 0.036 4.1553
21 0.056 7.5374
31 0.085 11.3311
41 0.127 15.6917
51 0.185 20.8232
61 0.266 26.9914
71 0.376 34.5430
out-> 102.20 1.015 75.5590 58.0 0.239 25.0132 <-in out-> 102.0 1.009 75.2014
102.21 1.015 75.5770 58.1 0.240 25.0773 102.1 1.012 75.3800
102.22 1.016 75.5949 58.2 0.240 25.1415 102.2 1.015 75.5590
102.23 1.016 75.6128 58.3 0.241 25.2058 102.3 1.018 75.7385
102.24 1.016 75.6308 58.4 0.242 25.2702 102.4 1.021 75.9185
102.25 1.017 75.6487 58.5 0.243 25.3348 102.5 1.024 76.0989
102.26 1.017 75.6667 58.6 0.244 25.3995 102.6 1.027 76.2797
102.27 1.017 75.6846 58.7 0.245 25.4643 102.7 1.030 76.4610
102.28 1.018 75.7026 58.8 0.246 25.5293 102.8 1.033 76.6428
102.29 1.018 75.7206 58.9 0.246 25.5943 102.9 1.036 76.8250
102.30 1.018 75.7385 59.0 0.247 25.6595 103.0 1.040 77.0077
table *t *sat p *H out *t *sat p *H in wb table wb temp wb sat p *H out
out-> 94.0 0.791 62.2448
95.0 0.816 63.7302 `t `sat p td table `t `sat p
96.0 0.842 65.2517 50.48 0.181 101.86 1.005
97.0 0.868 66.8103 50.49 0.181 101.87 1.005
98.0 0.895 68.4073 50.50 0.181 <-in out-> 101.88 1.005
99.0 0.922 70.0437 50.51 0.182 101.89 1.006
100.0 0.950 71.7207 50.52 0.182 101.90 1.006
out-> 101.0 0.979 73.4395 50.53 0.182 101.91 1.006
102.0 1.009 75.2014 50.54 0.182 101.92 1.007
103.0 1.040 77.0077 50.55 0.182 101.93 1.007
104.0 1.071 78.8597 50.56 0.182 101.94 1.007
50.57 0.182 101.95 1.008
-36 0.003 -11.5868 50.58 0.182 101.96 1.008
-26 0.006 -8.6117
-16 0.010 -5.5646 49.6 0.175 101.9 1.005
-6 0.017 -2.4092 49.7 0.176 102.0 1.008
4 0.027 0.9059 49.8 0.177 102.1 1.011
14 0.042 4.4511 49.9 0.177 102.2 1.014
24 0.064 8.3224 50.0 0.178 102.3 1.017
34 0.096 12.6474 50.1 0.179 102.4 1.020
44 0.142 17.5949 50.2 0.179 102.5 1.023
54 0.206 23.3858 50.3 0.180 102.6 1.026
64 0.295 30.3079 50.4 0.181 102.7 1.029
74 0.416 38.7367 50.5 0.181 102.8 1.032
84 0.578 49.1646 50.6 0.182 102.9 1.035
94 0.791 62.2448
104 1.071 78.8597 40 0.120 91 0.718
41 0.124 92 0.741
42 0.129 93 0.764
43 0.135 94 0.788
44 0.140 95 0.813
45 0.145 96 0.838
46 0.151 97 0.864
47 0.157 98 0.891
48 0.163 99 0.918
49 0.169 <-in out-> 100 0.946
50 0.175 101 0.975
51 0.182 102 1.005
52 0.189 103 1.035
53 0.196 104 1.066
Gas Meter Clocking Calculator
ENTER ="dial" cubic ft (0.5,1,2,5,etc.)
here-> 2
ENTER seconds for 1 revolution
here-> 102
Gas heating value must be obtained from the local gas utility.
CFM Calculator Enter input to CFM Calculator
Gas Heat yellow cells only. Electric Heat
Output -> 71,380.0 Btu/hr Amps -> 93.5
Inlet temp -> 70.0 F Volts -> 246.5
Inlet RH -> 30.0 % (optional) Capacity = 78,638.9
Outlet temp -> 125.0 F Inlet temp -> 74.0
Elevation -> 1,000.0 Inlet RH -> 30.0
deltaT = 55.0 F Outlet temp -> 130.0
CFM = 1,247 return air 1,202 Elevation -> 1,000.0
CFM = 1,376 supply air 1,326 deltaT = 56.0
^*standard^ CFM = 1,359
formula CFM = 1,501
*see note at right
Right and left calculators operate independently.
Calculators include precise psychrometric calculations for maximum accuracy.
Make sure the desired elevation is entered, since the cfm result can vary
considerably depending upon this value.
F
return air 1,300
supply air 1,437
^*standard^
formula -> cfm = (btu/hr) /(deltaT*1.08)
*For reference purposes only.
Supply/Return Grill *Enter (ft/min) Supply/Return Grill *Enter (ft/min)
350 350
300 325 300
250 275 250
Length" 24 Height" 24 <-Size Ak-> 4
CFM = 1,200 (core area/ free area) CFM = 1,200 Ak = "effective area"
*If you see a cell with ######, then widen the column until a number appears.
325
275 See:
ft^2 http://www.hartandcooley.com/grd/all_grd.htm
"effective area" for Ak values
velocity pressure
ft^2
"effective area"
(in. w.c.)
pressure
0.056
"inches
CFM and Capacity Calculators
Written and designed by Richard Perry, Dec. 2009
mailto:hvacrmedic@yahoo.com
Comments welcome.
http://spreadsheets.google.com/ccc?key=0AtjMgexpe-TUdDU0d3FmakEtd3FyblpMYlBzMzNUYVE&hl=en
HVAC Engineering Book
**Conversion of enthalpy to IP units included the energy to heat dry air by the temperature difference from Celsius to Fahrenheit scale start point (32/1.8)
SI units IP units
Ingreso de
Datos
792.4 m 2600.0 ft
22.2 o
C 72.0 o
F
15.6 o
C 60.0 o
F
92.16 kPa 27.281 In. Hg
691.03 mm hg
-5674.359
6.3925247
-0.0096778
6.2216E-07 Convertidor Grados
2.0748E-09 F C
-9.484E-13 53.042 11.69
4.163501 50 10.00
-5800.2206
1.3914993 CONVERSION DE METROS A PIES
-0.0486402 METROS PIES
4.1765E-05 1000 3280.84
-1.4452E-08
6.545967
6.5400000
14.5260000
0.7389000
0.0948600
0.4569000
-19.636987
1.3914993
-14.4
3.64375603
-0.3724257
0
37.2350073
-20.090436
1.3914993
-14.0
3.48113024
-0.3477732
0
37.0855694
7.894
7.477
2,681 Pa
1,767 Pa
0.019 kg/kg
0.012 kg/kg
65.1 kJ/kg
0.143 78 0.483
0.149 79 0.499
0.154 80 0.515
0.160 81 0.532
0.166 82 0.550
0.173 83 0.568
0.179 84 0.587
0.186 85 0.606
0.193 86 0.625
0.200 <-in out-> 87 0.646
0.208 88 0.666
0.215 89 0.688
0.223 90 0.709
0.232 91 0.732