Sie sind auf Seite 1von 8

Scientia Iranica A (2013) 20 (2), 278285

Sharif University of Technology


Scientia Iranica
Transactions A: Civil Engineering
www.sciencedirect.com

Research note

Fuzzy genetic algorithm approach for optimization of surge tanks


M.R. Chamani a, , S. Pourshahabi a , F. Sheikholeslam b
a
Department of Civil Engineering, Isfahan University of Technology, Isfahan, P.O. Box: 84156-83111, Iran
b
Department of Electrical Engineering, Isfahan University of Technology, Isfahan, Iran

Received 15 November 2011; revised 25 September 2012; accepted 12 November 2012

KEYWORDS Abstract The fundamental goal of a pipeline utility is to serve its customers with a low cost water supply
Optimization; of acceptable quality. The number, type, size, and location of transient protective devices play a direct role
Genetic algorithm (GA); in the pipeline system reliability and expenditure. The purpose of this study is to optimize the design
Fuzzy inference system of these devices to prevent water column separation after source pump power failure. The minimum
(FIS); pressures along the pipeline are assumed to be higher than 10 m to avoid water column separation. A
Transient flow; rational, systematic, and efficient optimization algorithm is constructed by combining the Fuzzy Inference
Protective devices. System (FIS) and the Genetic Algorithm (GA). The FIS representing expert knowledge is incorporated into
the GA approach to improve its fitness evaluation process. Three cases are presented to demonstrate the
effectiveness and efficiency of the proposed hybrid approach.
2013 Sharif University of Technology. Production and hosting by Elsevier B.V.
Open access under CC BY license.

1. Introduction commonly known as water hammer. The governing equations


of water hammer include two independent partial differential
One objective of a pipeline system is to provide customers equations, the conservation of mass and momentum equations.
with a low cost water supply of acceptable quality. Despite The most general and well-known technique for solving these
the many studies conducted on the optimization of pipeline equations is the method of characteristics. Controlled valve
systems under steady state conditions, there is still much to movement, pump inertia control, pressure relief valves, air
be learned about their operation under transient conditions. valves, surge tanks (open-end or one-way surge tanks), and
Negative and positive transient pressure surges travel along air chambers are some of the transient protection devices and
the pipeline, which may cause damage to the system. It methods [3].
is, therefore, necessary to study unsteady flows or transient Vtkovsk et al. [4] applied a forward transient technique
conditions in pipeline systems. Low pressure transient waves and the Genetic Algorithm (GA) optimization technique for
have considerable potential to draw contaminants through leak detection and calibration of pipe internal roughness in
leaks into a pipeline system. A motivation for considering the water distribution systems. Stephenson [5] presented design
transient waves arises from water quality considerations [1,2]. nomographs to simplify the process of sizing air vessels for
water hammer protection of pumping pipelines. Jung and
Transient pressure waves occur in pipelines due to changes
Karney [1] optimized the location, size, and number of transient
in fluid velocity typically caused by pump power failure or
control devices in water distribution networks using GA and
valve movement. When velocities in a pipe system change so
Particle Swarm Optimization (PSO). They examined a gravity
rapidly that the elastic properties of the pipe and liquid must
network with different protection strategies in each case.
be considered in an analysis, there is a hydraulic phenomenon
Transient pressure waves were caused by valve closures.
Izquierdo et al. [6] used a neural network to optimize the

Corresponding author. Tel.: +98 311 3913831; fax: +98 311 3912700. design of air vessels based on system parameters to achieve
E-mail address: mchamani@cc.iut.ac.ir (M.R. Chamani). permissible heads during a hydraulic transient.
Peer review under responsibility of Sharif University of Technology. The purpose of the present work is to optimize the design of
transient control devices to prevent water column separation
after pump power failure. The optimization algorithm is
combined with a transient simulation program to achieve the
optimal solution. The large search space of the problem is
1026-3098 2013 Sharif University of Technology. Production and hosting by Elsevier B.V. Open access under CC BY license.
http://dx.doi.org/10.1016/j.scient.2013.04.002
M.R. Chamani et al. / Scientia Iranica, Transactions A: Civil Engineering 20 (2013) 278285 279

maintained using a genetic algorithm. The GA deals with a large Mamdani method is intuitive and has widespread acceptance,
number of discrete or continuous variables, does not require while the Sugeno method is computationally efficient and
a derivable objective function, explores a wide search space works well with optimization and adaptive techniques. The
simultaneously, provides a population of optimum solutions, Sugeno method also has guaranteed continuity of the output
and works with numerically generated data, experimental data, surface [17]. To demonstrate the effectiveness of the proposed
or analytical functions in extremely complex problems [7]. In hybrid approach, three cases are presented.
this paper, GA is improved using fuzzy inference systems. A
fuzzy decision making is incorporated in the GA approach to 2. Optimization algorithm
improve its fitness evaluation process and its capability for
handling constraints. The fitness evaluation in this paper does The optimization algorithm is combined with a transient
not incorporate cost directly. Each chromosome is evaluated simulation program to achieve an optimal solution. In ordinary
using a fuzzy decision defined after transient analysis. genetic algorithms, the fitness function that evaluates each
The basic idea underlying fuzzy logic was suggested by chromosome derives from a mathematical formula describing
Zadeh [8]. In general, fuzzy logic is concerned with formal the objective function. Definition of a fitness function is an
principles of approximate reasoning, while classical two-valued important and difficult task. The fitness evaluation in this paper
logic (true or false) is concerned with formal principles of does not incorporate cost directly. In the present work, a fuzzy
reasoning. Fuzzy logic uses the continuum of logical values decision making is incorporated in the GA approach to improve
between 0 (completely false) and 1 (completely true). Two its fitness evaluation process and its capability of handling
of the main concepts that play an important role in many constraints. The objective of the proposed method is to optimize
applications of fuzzy logic are the concepts of linguistic variable one-way surge tanks with a least cost design subject to the
and fuzzy if-then rules [9]. For example, height is a linguistic following constraints:
variable when its values are defined to be low, medium or
high. Each linguistic value is represented as a fuzzy set that is 1. Minimum pressures along the pipeline should be higher
characterized by a membership function, usually taking values than 10 m to avoid water column separation.
between 0 and 1. In general, a fuzzy rule can be represented as: 2. Final liquid height in the tanks should be sufficient to
prevent vortices at the surge tank outlet.
If x1 is A1 and x2 is A2 and . . . xn is An then
As will be explained in the next section (Section 3),
y1 is B1 and y2 is B2 and . . . ym is Bm, maintaining the desirable final liquid height in the surge
where x1 , x2 , . . . , xn , y1 , y2 , . . . , ym are linguistic variables, and tanks leads to the least cost design of these devices. The final
A1 , A2 , . . . , An , B1 , B2 , . . . , Bm are their respective linguistic liquid height constraint is regarded as the objective of the
values. The goal of using fuzzy systems is to put human optimization subject to the minimum head constraint. In this
knowledge into engineering systems in a systematic, efficient, method, each feasible chromosome (solution) that satisfies
and analyzable order. Fuzzy systems are knowledge-based or the pressure constraint after transient analysis is evaluated
rule-based systems and work very well for many engineering in the range of [0, 1] using a fuzzy inference system, with
problems [10]. respect to the final liquid height in the surge tanks, as shown
Goulter and Bouchart [11] used fuzzy sets combined in Figure 1. The fitness value for infeasible chromosomes or
with linear programming for network cost minimization. chromosomes that violate the minimum pressure constraint is
Vamvakeridou-Lyroudia [12] used fuzzy sets for pressure and set to zero without FIS interference. Normalizing the fitness
velocity constraint violation in a dynamic programming algo- value in the range [0, 1], it will be possible to find the
rithm, for optimal design of water supply networks. Xu and global optimum solution. Using the fuzzy inference system,
Goulter [13] presented a fuzzy linear program optimization determination of the fitness value for each chromosome and
method in which the capital costs of the network were min- satisfying the constraints, are accomplished in an easy and
imized while maintaining the nodal heads at demand nodes transparent manner. A generalized method is obtained for
within a satisfactory region, as defined by the customers evaluation of the fitness value that does not change with
at those nodes. Revelli and Ridolfi [14] simulated uncertain dimensional characteristics, time, or location.
parameters, like the roughness coefficient of pipes and the Mamdani and Sugeno are two types of fuzzy inference
demands of the network, using fuzzy theory. Vamvakeridou- system that are tested and compared in this paper. In these
Lyroudia et al. [15] used a fuzzy multi-objective optimization fuzzy systems, minimum is used as the AND operator, and
model (minimizing cost and maximizing a benefit-quality func- maximum is used as the OR operator. The weighted average
tion) to the Anytown water distribution network. They used and the centroid methods are used as the defuzzification
genetic algorithms, combined with fuzzy reasoning, for benefit- methods in Sugeno and Mamdani FIS methods, respectively.
quality evaluation. They showed that their model manages to The input variables and the rules of these two fuzzy systems are
find a better solution than any other previous approach in terms the same. In Mamdani-type inference, the output membership
of cost, despite the multiple criteria applied for the benefit functions are fuzzy sets, but Sugeno output membership
function being more extensive and stricter. Amirabdollahian functions are constant. The binary genetic algorithm has been
et al. [16] applied a fuzzy genetic algorithm to obtain the least- written in MATLAB, version 7.6.0.324 (R2008a). Tournament
cost design of looped water distribution networks. They used selection and elitism (retaining the best solution at each
a fuzzy decision system to eliminate the traditional use of the generation) are used. The probability of uniform crossover is
penalty function in the genetic algorithm. They concluded that 0.8 and the mutation probability is 0.05. The algorithm stops
their proposed method yielded solutions with reduced costs. when the fitness value reaches one or when the number of
Mamdani and Sugeno are two types of fuzzy inference generations is sufficient to converge. The appropriate number
system that are tested and compared in this paper. In Mamdani- of generations will be noted in each case. The optimization
type inference, the output membership functions are fuzzy sets, algorithm is flexible enough to deal with a variety of pipelines,
but Sugeno output membership functions are constant. The changing the system characteristics and membership functions.
280 M.R. Chamani et al. / Scientia Iranica, Transactions A: Civil Engineering 20 (2013) 278285

Figure 2: Schematic view of a one-way surge tank.

found by the potential flow theory should be increased by


about 10% or so, depending on other conditions [19]. With an
appropriate margin of safety and considering bathtub vortex
criteria, the minimum (final) liquid height in the surge tank
above the pipeline level is chosen about 1.0 m for conditions
in the present study.
The initial water volume in the surge tank comprises three
parts, as shown in Figure 2. The first part is consumed to
overcome water column separation, the second part must
remain in the tank to prevent vortices, and the third part is
related to the clearance of the intake (vertical distance from
Figure 1: The flowchart of fuzzy genetic algorithm. intake level to the bottom of the tank).
For the pipeline used in this study, 100 different scenarios of
3. Optimization of one-way surge tanks one-way surge tanks, with and without an air chamber, were
tested using the transient simulation model, via a trial and
The one-way surge tank is used to prevent unallowable low error process that satisfied the minimum pressure constraint.
pressures. When the pressure at the tank inlet drops below the Number, size, and location of the surge tanks, as well as the
liquid level in the tank, the check valve will open to allow the initial air volume in the air chamber, were assumed to vary
flow from the tank into the pipeline. The check valve at the in each scenario. The volume of water consumed by one-way
inlet prevents any return flow into the tank. It is an appropriate surge tanks to avoid water column separation was computed
control device in pumping lines because the hydraulic grade for each scenario. The results obtained from this investigation
line is usually too far from the pipeline center [3,18]. showed that the number, size, and location of the surge tanks
To obtain the optimal ratio of height to diameter in had no significant effects on the volume of water consumed to
surge tanks, the designer should take into account economics, overcome water column separation. In other words, the amount
hydraulics, safety, aesthetic constraints, and so on. Without of water consumed in the surge tanks to effectively handle the
structural constraints taken into account, the best height-to- water column separation is approximately constant. Changes
diameter ratio will be 1, using the mathematical optimization. in surge tank design only affect the water remaining in the
The same ratio will be obtained when hydrostatic behavior tanks or the minimum head in the system. This conclusion is
considerations are taken into account. demonstrated through the illustrative cases that will follow.
One of the difficulties encountered in hydraulic structures From the above observations, it may be concluded that
is vortex formation at intakes. When the submergence depth the optimal design of the surge tank will be accomplished
(vertical distance between water surface and intake center) when the first part of the water volume in each surge
is not sufficient, air enters the pipe by means of a free- tank (part 1) is completely consumed to overcome water
surface vortex and decreases intake efficiency. The critical column separation, and the water remaining above the pipeline
submergence (Sc ) is the submergence required to avoid air- level (part 2) is only sufficient to prevent bathtub vortices.
entraining vortices at intake, and can be obtained with a Therefore, maintaining the desirable final liquid height in the
potential flow solution [1921]. The difference between results surge tanks leads to the least cost design of these devices.
obtained from this theory and experimental data is within Undoubtedly, the number of one-way surge tanks must also
10%. Possible causes for this difference may be viscosity, be considered in the optimization process because of the
surface tension, gravity, and circulation effects present in installation, maintenance, and operation problems associated
real fluid-flow. Furthermore, as intake diameter increases, the with these hydraulic devices.
assumption of point sink may deviate from reality. Due to The above heuristics are presented in a number of fuzzy IF-
these reasons, the critical submergence for a real fluid flow THEN rules. In other words, expert knowledge is transformed
M.R. Chamani et al. / Scientia Iranica, Transactions A: Civil Engineering 20 (2013) 278285 281

for checking and verifying the transient analysis program. This


study consists of three cases. The aim of the first case is to
optimize one-way surge tanks in a system including an air
chamber. In the second case, optimization of one-way surge
tanks in the system without an air chamber is considered for
preventing column separation. The third case is presented to
investigate the possibility of maintaining the positive pressures
Figure 3: Membership functions for input variables. along the pipeline system.

into a fuzzy system. When transient analysis is completed, 5. Results and discussions
the final liquid height in each surge tank may be insufficient
(less than 1.0 m and unable to prevent bathtub vortices), 5.1. Case 1
sufficient (about 1.0 m), or excessive (more than 1.0 m). Each
input comprises three membership functions (low, good, and As already stated, column separation occurs at about 5.197 s
high), if it is insufficient, sufficient, or excessive, respectively, after complete pump power failure. In this case, optimization of
as presented in Figure 3. The horizontal axis represents the three one-way surge tanks in a system including an air chamber
final water surface height and the vertical axis represents is considered to maintain allowable pressures. The air chamber
membership values for low, good and high. The upper is located at the pump station and the initial air volume is set at
and lower bounds depend on the size of the surge tanks and 2.8 m3 (100 ft3 ). Since a one-way surge tank can be placed on
are determined by the optimization algorithm. If the liquid each node, a total number of 42 series pipes, starting with pipe
height in the tank reaches zero and the pressure at the tank number one at the upstream, are considered instead of the three
connection drops to below zero, the liquid height in the surge existing pipes (three segments in the shortest pipe, 23 and 16
tank will be presented by a negative value, as shown in the segments in the two other pipes). Four different sizes (1, 1.25,
low membership function in Figure 3. This means that the 1.5, and 1.75 m) are considered for the diameter of each surge
size of the one-way surge tank must be increased. The inputs tank. The ratio of initial liquid height to diameter in each surge
are considered to be the minimum, maximum, and mean values tank is assumed to be 1.0 from which the height of each tank can
among the final liquid height in the surge tanks. The output is be calculated after its diameter is determined. The diameter of
the fitness value in the range of [0, 1], as shown in Figure 4. The the connection pipe to the pipeline and the discharge coefficient
fuzzy system is constructed based on 10 rules. The infeasible in the surge tanks are assumed to be 0.3 m and 0.8, respectively.
rules are omitted. The location and size (diameter) of three one-way surge
tanks are the design variables. Therefore, there are 4,093,440
4. Description of pipeline system (41 40 39 4 4 4) possible combinations in the
complete enumeration for this case. The population size is
The pipeline used for this study is that studied by 100 and the algorithm stops when the fitness value reaches
Watters [18]. A transient analysis program is used to determine one or when there are 50 generations. The fuzzy system
the pressure head and velocity along the pipeline system after used is a three-input-one-output system with 10 rules. The
pump power failure. The code of this program is presented in three inputs are the minimum, maximum, and mean values
FORTRAN [3], which is converted to metric units. It is based among the final liquid height in the tanks, and the output is
on the method of characteristics. The system includes a pump the fitness value. The result of the optimization shows that
station at the upstream and a reservoir at the downstream, as only two one-way surge tanks will be sufficient to overcome
shown in Figure 5. The pump station has four similar (source) column separation. The initial liquid height in one of the three
pumps in parallel to deliver 694 lit/s from an elevation of surge tanks does not decrease during transient simulation and
120.4 m to an elevation of 256 m. Pipeline specifications are two other tanks are sufficient to prevent column separation.
presented in Table 1. Each pump has five stages and the rotary Therefore, this tank is omitted and the simulation program
moment of inertia for each pump and motor unit is 20 kg m2 . runs again with two remaining tanks. Mamdani and Sugeno
The minimum pressures along the pipeline are assumed to results are presented in Table 2. It is shown that both Mamdani
be higher than 10 m to avoid water column separation, and Sugeno methods yield the same results, but the Sugeno
based on absolute atmospheric pressure, fluid temperature, system shows a slower convergence in this case. The numbers
and vapor pressure. The real time of transient simulation after of generations to convergence in Mamdani and Sugeno types
power failure is set at 100 s. The results of the analysis show are 5 and 13, respectively, as shown in Figure 6. Although
that column separation occurs at about 5.197 s after complete both methods achieve the same solutions, a slight difference is
pump power failure. A software package HYTRAN [22] is used observed between the two maximum fitness values in the two

(a) Mamdani type. (b) Sugeno type.

Figure 4: Membership functions for output variable.


282 M.R. Chamani et al. / Scientia Iranica, Transactions A: Civil Engineering 20 (2013) 278285

Table 1: The pipeline data.

Pipe no. Upstream Downstream Length (m) Diameter (m) Material Friction factor Wave
elevation (m) elevation (m) speed (m/s)

1 126.5 126.5 610 0.762 Steel 0.013 1094


2 126.5 213.4 4828 0.762 Steel 0.013 1094
3 213.4 246.9 3219 0.762 Concretea 0.019 1063
a
Reinforced concrete.

Table 2: Results of case 1.

FIS method Optimization results of one-way surge tanks Transient analysis results Maximum Number of
fitness value generations
No. Optimal Diameter (m) Initial Final Minimum Maximum Consumed
locationa liquid liquid head (m) air water
height (m) height (m) volume (m3 ) (m3 )

1b 16 1.00 1.00 1.00


Mamdani 2 29 1.50 1.50 1.02 9.62 7.74 1.14 0.85 5
3 36 1.25 1.25 1.02

1b 10 1.00 1.00 1.00


Sugeno 2 29 1.50 1.50 1.02 9.62 7.74 1.14 0.98 13
3 36 1.25 1.25 1.02
a
The number refers to the pipe number where a one-way surge tank is located at downstream end of the pipe.
b
This surge tank is omitted because the initial liquid height does not change in this tank.

Figure 5: The schematic layout of the pipeline.

Figure 7: Volume of consumed water by one-way surge tanks.

station (at node 30 or at the downstream end of the 29th pipe)


is larger and consumes more water. The reason for this may
be that this tank should act sooner than the other to eliminate
negative pressures. Figure 7 shows the total volume of water
consumed by one-way surge tanks to avoid column separation
for each generation number. As demonstrated in Figure 7, the
difference between maximum and minimum values is less than
0.07 m3 of water before convergence, which is negligible in
comparison with the dimensions of the surge tanks.
After each power failure event, liquid is drawn into the
pipeline from the air chamber, permitting the flow in the
pipeline to decelerate more slowly and keeping the pressure
relatively high. As the amount of liquid in the air chamber
Figure 6: Convergence of fuzzy genetic algorithm in case 1. decreases, the air volume expands, decreasing the pressure at
the pump discharge. The air chamber must be sufficiently large
sets of results, as presented in Table 2. The explanation for this to supply the needs of the pipeline without being empty and
is that the output membership functions are fuzzy sets in the permitting air to enter the pipeline. The maximum air volume
Mamdani system but constant in the Sugeno system. during the transient analysis establishes the minimum total
Fulfillment of the minimum pressure constraint and final volume of the air chamber. With an initial air volume of 2.8 m3 ,
liquid height in the tanks indicates the effectiveness of the the maximum air volume in the air chamber will be 7.74 m3
fuzzy-genetic method. The surge tank closer to the pump (Table 2). When the air chamber is used alone, the initial air
M.R. Chamani et al. / Scientia Iranica, Transactions A: Civil Engineering 20 (2013) 278285 283

Figure 8: Propagation of a negative wave resulting from pump power failure.


Figure 9: Convergence of fuzzy genetic algorithm in case 2.
volume must be at least 5.9 m3 to prevent water column
separation, and the maximum air volume will be 13.06 m3 .
The reduction of the final air volume when the surge tanks are
installed will be 40.7%. It is, therefore, possible to decrease the
air chamber size to a considerable extent by using one-way
surge tanks.
Figure 8 shows the propagation of a negative wave resulting
from pump power failure without any transient control devices
every fifth time step. Column separation occurs at about 5.197 s
and the minimum pressure will be lower than 10 m.
Included in this plot are the results from runs (Case 1) and an air
chamber alone, which represent the lower bound on pressure
heads along the pipeline (envelope curves). The extreme values
of minimum head along the pipeline after these scenarios are
higher than 10 m. Figure 8 illustrates how these scenarios
affect the pressure profile during a transient incident. In Case
1, the minimum head is 9.62 m (Table 2) at node 35 after
8.167 s. The optimum locations are at the downstream end of Figure 10: Convergence of fuzzy genetic algorithm in case 3.
pipe 29 (node 30) and at the downstream end of pipe 36 (node
37). In another alternative scenario (i.e., air chamber alone with 5.3. Case 3
an initial air volume of 5.9 m3 ), the minimum head is 9.87 m
at node 31 after 10.208 s. In order to get positive pressures along the pipeline system
In Table 3, simulation runs are again presented to see if in this case, two one-way surge tanks and four possible values
there are any alternatives to having just one larger tank half for the initial air volume (4, 5, 6, and 7 m3 ) in the air chamber
way between. All conditions (the initial air volume in the air
are assumed. The location and diameter of two one-way surge
chamber and the other characteristics of air chamber and surge
tanks and the initial air volume in the air chamber are the
tank) are the same as those in Case 1.
design variables. The rules of the fuzzy system, the options for
the location and diameter of surge tanks, and the population
5.2. Case 2 size are considered to be the same as in Case 2. Mamdani
and Sugeno results are summarized in Table 5. The number
In this case, optimization of five one-way surge tanks in the
of generations to convergence is presented in Figure 10. Both
system without an air chamber is used for preventing column
Mamdani and Sugeno methods show the same results for this
separation. The diameter of the connection pipe to the pipeline,
case. The minimum pressures along the pipeline are positive.
and the discharge coefficient in the surge tanks, are assumed
to be 0.3 m and 0.8, respectively. The ratio of initial liquid
height to diameter in each surge tank is assumed to be 1.0. 6. Conclusions
The location and diameter of the five one-way surge tanks
are the design variables. The options for the location of surge This paper applies Genetic Algorithms (GA) combined with
tanks are considered to be the same as in the previous case. Fuzzy Inference Systems (FIS) for optimization of the location
Four different sizes (2, 2.5, 3, and 3.5 m) are assumed for the and size of surge tanks in a water system consisting of a
diameter of each surge tank. There are 92,086,026,240 (41 series of pipes. The fitness evaluation in this paper does not
40 39 38 37 45 ) possible combinations in the complete incorporate cost directly. Minimizing the size of the surge
enumeration for this case. With a population size of 100 tanks results in minimized costs. Maintaining the desirable final
chromosomes, and after 100 generations, the maximum fitness liquid height in the surge tanks leads to a least cost design
value will be approximately 0.6. Therefore, 10,000 evaluations (the least volume of material used in the walls, bottom, and
will be performed in each run (0.000011% of the total possible roof) for these devices. The results obtained from the present
combinations). As demonstrated in Table 4, the Mamdani work indicate that determination of the fitness value for each
and Sugeno methods yield the same results. Figure 9 shows chromosome and satisfaction of the constraints can be simply
maximum fitness values for 100 generations. The minimum accomplished using the fuzzy inference system. A generalized
pressures along the pipeline are kept at an acceptable level. method is developed for evaluating the fitness value that does
284 M.R. Chamani et al. / Scientia Iranica, Transactions A: Civil Engineering 20 (2013) 278285

Table 3: One large one-way surge tank.

Alternative no. No. of surge tanks Locationa Tank diameter (m) Initial liquid height (m) Minimum head (m)

1 1 32 3 10 Column separation occurs


2 1 33 3 10 Column separation occurs
a
Location is the pipe number where a one-way surge tank is located at downstream end of the pipe.

Table 4: Results of Case 2.

FIS method Optimization results of one-way surge tanks Transient analysis results Maximum Number of
fitness value generations
No. Optimal Diameter (m) Initial liquid Final liquid Minimum Consumed
locationa height (m) height (m) head (m) water (m3 )

1 16 2.00 2.00 1.83


2 21 2.00 2.00 1.75
Mamdani 3 25 2.00 2.00 1.45 9.61 5.26 0.54 42
4 30 3.00 3.00 2.73
5 36 2.00 2.00 1.90
1 16 2.00 2.00 1.83
2 21 2.00 2.00 1.75
Sugeno 3 25 2.00 2.00 1.45 9.61 5.26 0.57 43
4 30 3.00 3.00 2.73
5 36 2.00 2.00 1.90
a
The number refers to the pipe number where a one-way surge tank is located at downstream end of the pipe.

Table 5: Results of case 3.

FIS method Optimization results Transient analysis results Maximum Number of


fitness value generations
Initial air Surge Optimal Tank di- Initial liquid Minimum Maximum air
volume (m3 ) tanks no. locationa ameter (m) height (m) head (m) volume (m3 )

1 30 2.00 2.00
Mamdani 7.00 0.03 14.94 0.50 13
2 36 2.50 2.50
1 30 2.00 2.00
Sugeno 7.00 0.03 14.94 0.50 13
2 36 2.50 2.50
a
The number refers to the pipe number where a one-way surge tank is located at downstream end of the pipe.

not change with dimensional characteristics, time (implying [5] Stephenson, D. Simple guide for design of air vessels for water hammer
inflation and discount rates in costs), and location. The stopping protection of pumping lines, J. Hydraul. Eng., 128(8), pp. 792797 (2002).
[6] Izquierdo, J., Lpez, P.A., Lpez, G., Martnez, F.J. and Prez, R. Encapsu-
criteria of the optimization algorithm become rational, and local lation of air vessel design in a neural network, Appl. Math. Model., 30,
optimum solutions are avoided by normalizing the fitness value pp. 395405 (2006).
in the range [0, 1]. The number, size, and location of the surge [7] Haupt, R.L. and Haupt, S.E., Practical Genetic Algorithms, 2nd Edn., John
Wiley & Sons Inc., Hoboken, New Jersey (2004).
tanks have no significant effects on the volume of consumed
[8] Zadeh, L.A. Fuzzy sets, Inf. Control, 8(3), pp. 338353 (1965).
water to overcome water column separation. In other words, [9] Zadeh, L.A. Fuzzy logic, IEEE Comput., 21(4), pp. 8393 (1988).
the amount of water consumed by one-way surge tanks to [10] Wang, L.X., A Course in Fuzzy Systems and Control, Prentice-Hall, Inc., New
effectively handle water column separation is approximately Jersey (1997).
[11] Goulter, I.C. and Bouchart, F. Fuzzy programming in water distribution
constant and does not change with changes in surge tank network design, In Proc. of 1st Int. Conf. on Comput. Methods and Water
geometry or location. Mamdani and Sugeno methods yield Res., Rabat, pp. 3344, Springer, Morocco, Berlin (1988).
similar results for the demonstrated cases. Fulfillment of the [12] Vamvakeridou-Lyroudia, L.S. Fuzzy reasoning in water supply network
optimization, In Proc. of the 4th Int. Conf. on Application of Artif. Intell. to Civ.
minimum pressure constraint and critical submergence shows
and Struct. Engrg., pp. 255262, Civil-Comp Press, Cambridge, Edinburgh,
the effectiveness of the fuzzy-genetic method proposed. UK (1995).
[13] Xu, C. and Goulter, I.C. Optimal design of water distribution networks
using fuzzy optimization, Civ. Engrg. Environ. Syst., 16, pp. 243266
References (1999).
[14] Revelli, R. and Ridolfi, L. Fuzzy approach for analysis of pipe networks, J.
[1] Jung, B.S. and Karney, B.W. Hydraulic optimization of transient protection Hydraul. Eng., 128(1), pp. 93101 (2002).
devices using GA and PSO approaches, J. Water Resour. Plann. Manage., [15] Vamvakeridou-Lyroudia, L.S., Walters, G.A. and Savic, D.A. Fuzzy multi-
132(1), pp. 4452 (2006). objective optimization of water distribution networks, J. Water Resour.
[2] Jung, B.S., Karney, B.W., Boulos, P.F. and Wood, D.J. The need for Plann. Manage., 131(6), pp. 467476 (2005).
comprehensive transient analysis of distribution systems, J. Am. Water [16] Amirabdollahian, M., Chamani, M.R. and Asghari, K. Optimal design of
Works Assn., 99(1), pp. 112123 (2007). water networks using fuzzy genetic algorithm, Proc. ICEWater Manag.,
[3] Larock, B.E., Jeppson, R.W. and Watters, G.Z., Hydraulics of Pipeline Systems, 164(7), pp. 335346 (2011).
CRC Press, New York (2000). [17] Fuzzy Logic Toolbox Users Guide, The MathWorks, Inc. (2008).
[4] Vtkovsk, J.P., Simpson, A.R. and Lambert, M.F. Leak detection and [18] Watters, G.Z., Analysis and Control of Unsteady Flow in Pipelines, 2nd Edn.,
calibration of water distribution systems using transients and genetic Butterworth Publishers, Boston, Massachusett (1984).
algorithms, Water Dist. Syst. Conf., Div. of Water Resour. Plan. ASCE, Tempe, [19] Yldrm, N. and Kocaba, F. Critical submergence for intakes in open
Arizona, pp. 5764 (June 79, 1999). channel flow, J. Hydraul. Eng., 121(12), pp. 900905 (1995).
M.R. Chamani et al. / Scientia Iranica, Transactions A: Civil Engineering 20 (2013) 278285 285

[20] Yldrm, N. and Kocaba, F. Critical submergence for intakes in still-water Shokoufeh Pourshahabi received a B.S. degree in Civil Engineering, in
reservoir, J. Hydraul. Eng., 124(1), pp. 103104 (1998). 2002, from Shahid Bahonar University of Kerman, Iran, and an M.S. degree
[21] Yldrm, N., Kocaba, F. and Glcan, S.C. Flow-boundary effects on in Civil Engineering (Water Resources Engineering), in 2008, from Isfahan
critical submergence of intake pipe, J. Hydraul. Eng., 126(4), pp. 288297 University of Technology, Isfahan, Iran. Since 2009, she has been lecturer in the
(2000). Department of Civil Engineering at the Institute of Higher Education of Eqbal
[22] Lawgun, N. Water hammer software: hytran solutions, Auckland, New Lahoori, Mashhad, Iran. Her research interests include: hydraulic transients,
Zealand. Available in: http://www.hytran.net. evolutionary algorithms, fuzzy inference systems, artificial neural networks,
and extreme values.

Mohammad Reza Chamani received a B.S. degree in Civil Engineering, in Farid Sheikholesalm received a B.S. degree in Electronics from Sharif
1985, from Amirkabir University of Technology, Tehran, Iran, and M.S. and University of Technology, Tehran, Iran in 1990, and M.S. and Ph.D. degrees
Ph.D. degrees in Water Resources Engineering from the University of Alberta, in Communications and in Electrical Engineering from Isfahan University
Edmonton, Canada, in 1993 and 1997, respectively. He joined the Department of Technology, Iran, in 1994 and 1998, respectively. Since 1999, he has
of Civil Engineering at Isfahan University of Technology, Iran, in 1998, and his been with the Department of Electrical and Computer Engineering at Isfahan
current position is Associate Professor. His research interests include, but are University of Technology, Iran, where he is currently Associate Professor
not limited to hydraulic structures, pipe flow, and river engineering. He is also of Electrical Engineering. His research interests include: control algorithms,
author of several books and papers. stability analysis, nonlinear systems, intelligent control and robotics.

Das könnte Ihnen auch gefallen