Catalogue 2006
EUROMOLD
COMPANY PRESENTATION

EUROMOLD International standards


Euromold is the leading All our products meet the
European specialised designer, International standards like
manufacturer and distributor of CENELEC HD 629.1, CENELEC
prefabricated cable accessories EN 50180, IEC 137, IEEE 386
for medium voltage energy & 404 or country specifica-
distribution. Euromold provides tions. Official certificates, CESI,
a complete range of acces- KEMA, ATEX prove the con-
sories for underground cables: formity of our products. Long
pre-moulded EPDM or silicone duration tests of existing or
rubber connectors, terminations new products are continuously
and joints for cables and epoxy performed in our test fields.
bushings for transformers and
switch gear, as well as a large
range of cold-shrinkable Laboratory accreditation
terminations and joints from 12 Since June 2000, Euromolds
to 42 kV. independent ELAB laboratory
Euromold is also the manufac- obtained the BELTEST accredi-
turer of electrical components tation no.192-T-ISO 17025
for the high voltage accessories conform with the European
of the Nexans group. standards for laboratories ISO
17025 for electrical testing of
ISO 9001 Certificate medium voltage cable acces-
Since 1992, Euromolds sories according to the Inter-
commitment to quality is national standards IEC 61442
demonstrated by its ISO 9001 and HD 629.
certification.

While every care is taken to ensure that the information contained


in this publication is correct, no legal responsibility can be accepted
for any inaccuracy. EUROMOLD NV reserves the right to alter or
modify the characteristics of its products described in this catalogue
04/2006

as standards and technology evolve.


SEPARABLE CONNECTORS
AND BUSHINGS
INTERFACE B

Table of contents Interface B


400LR - elbow connector Dimensions according to
400TE - tee connector European CENELEC EN
400T1 - equipment bushing 501810 and 50181 (in mm).
400AR-1 - equipment bushing
400AR-2 - equipment bushing
Accessories
Possible arrangements
Fixings for equipment bushings
Dia. 56 0,2
Dia. 46 0,2
Dia. for
0
pin 14 - 0,04

40
min.

90 0,2

11 min.

Dia. 70 0,2
04/2006


Connecting possibilities

BUSHINGS / CONNECTION CONNECTORS /


ACCESSORIES ACCESSORIES

Equipment
interface dead-ending
of equipment
(K)(M)400DR
Dead-end receptacle

(K)(M)400AR-2
Equipment bushing

one cable to (K)(M)400LR/G


equipment Elbow connector

(K)(M)400T1
Equipment bushing

(K)(M)400AR-1
Equipment bushing

(K)(M)400TE/G
Tee connector

two cables to
cable equipment
isolation
(K)(M)400SOP
Stand-off plug tap-off
630/250A
(K)400RTPA
Reducing tap plug

cable
in-line
earthing
400GP junction
Earthing plug
(K)(M)400CP-SC
Connecting plug


400LR
INTERFACE B
ELBOW CONNECTOR

Application Technical characteristics Up to 36 kV - 400 A


Separable elbow connector The thick conductive EPDM
(plug-in type) designed jacket provides a total safe to
to connect polymeric touch screen which ensures
insulated cable to equipment safety for personnel.
(transformers, switch gear, Each separable connector is 6/10 (12) kV
motors...). tested for AC withstand and 6.35/11 (12) kV
partial discharge prior to 8.7/15 (17.5) kV
leaving the factory. 12/20 (24) kV
12.7/22 (24) kV
18/30 (36) kV

Design 210 mm
Separable connector
comprising:
1. Conductive EPDM insert.
2. Conductive EPDM jacket.
3. Insulating EPDM layer
moulded between the insert
and the jacket.
4. Type B - 400 A interface
4
as described by CENELEC
EN 50180 and 50181. 5
5. Conductor connector.
6. Cable reducer. 1
7. Earthing lead. 2
365 mm
The screen break design 3
enables cable outer sheath
testing without removing or
dismantling the connector.

Specifications and 7
standards
The separable connector 400LR
meets the requirements of
6
CENELEC HD 629.1.

Separable Voltage Current


Conductor sizes (mm2)
connector Um Ir
type (kV) (A) min. max.
400LR/G 12 400 50 240
K400LR/G 24 400 25 240
04/2006

M400LR/G 36 400 35 185


Kit contents
The complete (K)(M)400LR/G The kit also comprises lubricant, wipers,
elbow connector kit comprises installation instructions and crimp chart.
the following components:

+ + + + = (K)(M)400LR/G-W-X
connector kit

Connector housing Pin contact Conductor Bail Cable reducer


(K)(M)400BLR/G + hex. key contact restraint 411CA-W
400LRF 400LRC-X 400BA

Ordering instructions
Select the part number Ordering Dia. over core insulation (mm)
which gives the best centring part number min. max.
to the cable core insulation 400LR/G-11-X 12.0 17.5
diameter and substitute X 400LR/G-15-X 16.0 22.0
using table X, according to the 400LR/G-19-X 20.0 26.5
conductor size and type. 400LR/G-22-X 23.5 31.0
Add a 'K' for use up to 24 kV 400LR/G-25-X 26.5 32.5
and add an 'M' for use up to 400LR/G-27-X 28.5 37.5
36 kV.
Table X

Conductor Aluminium Copper


sizes
(mm) DIN hexagonal Deep indent DIN hexagonal
25 - - 25(K)M-11-2
Example: 35 35(K)M-12-2 35KM-12-1 35(K)M-11-2
The copper wire screened cable 50 50(K)M-12-2 50(K)M-12-1 50(K)M-11-2
70 70(K)M-12-2 70(K)M-12-1 70(K)M-11-2
is 12 kV, 150 mm2 stranded
95 95(K)M-12-2 95(K)M-12-1 95(K)M-11-2
copper with a diameter over
120 120(K)M-12-2 120(K)M-12-1 120(K)M-11-2
core insulation of 23.5 mm.
150 150(K)M-12-2 150(K)M-12-1 150(K)M-11-2
Order a 400LR/G-19-150(K)M- 185 185(K)M-12-2 185(K)M-12-1 185(K)M-11-2
11-2 elbow connector kit. 240 240(K)M-12-2 240(K)M-12-1 240(K)M-11-2

For use with For use with Alupe or For use with fabric tape For use with For outdoor Components can be
copper tape C 33-226 cables. (graphite) screened cables. other cable types. applications. ordered individually.
screened cables. Please contact our Order additional Please contact our Order: +MWS.
Order: Kit MT. representative. semi-conductive tape representative.
(type TSC).


400TE
INTERFACE B
TEE CONNECTOR

Application Technical characteristics Up to 36 kV - 400 A


Separable tee connector (plug- The thick conductive EPDM
in type) designed to connect jacket provides a total safe to
polymeric insulated cable to touch screen which ensures
equipment (transformers, switch safety for personnel.
gear, motors...). Each separable connector is 6/10 (12) kV
tested for AC withstand and 6.35/11 (12) kV
partial discharge prior to 8.7/15 (17.5) kV
leaving the factory. 12/20 (24) kV
12.7/22 (24) kV
18/30 (36) kV

Design 255 mm
Separable connector 220 mm
comprising:
1. Conductive EPDM insert.
2. Conductive EPDM jacket.
3. Insulating EPDM layer
moulded between the insert
and the jacket.
4. Type B - 400 A interface
as described by CENELEC 4 9
EN 50180 and 50181.
5. Conductor connector.
5
10 6 8
6. Basic insulating plug
(with VD point). 1
7. Cable reducer.
8. Conductive rubber cap. 2
390 mm
9. Clamping pin contact.
10. Bail restraint. 3
11. Earthing lead.
The screen break design
enables cable outer sheath
testing without removing or
dismantling the connector.
11
Specifications and
standards
The separable connector 400TE 7
meets the requirements of
CENELEC HD 629.1.

Separable Voltage Current


Conductor sizes (mm2)
connector Um Ir
type (kV) (A) min. max.
400TE/G 12 400 70 240
K400TE/G 24 400 25 240
04/2006

M400TE/G 36 400 35 185


Kit contents
The complete (K)(M)400TE/G The kit also comprises lubricant, wipers,
elbow connector kit comprises installation instructions and crimp chart.
the following components:

+ + + + + = (K)(M)400TE/G-W-X
connector kit

Connector housing Clamping Conductor Basic Bail Cable reducer


(K)(M)400BT/G pin contact contact insulating restraint 411CA-W
400TEF 400TEC-X plug + 400T-BA
rubber cap
(K)(M)400BIPA

Ordering instructions
Select the part number Ordering Dia. over core insulation (mm)
which gives the best centring part number min. max.
to the cable core insulation 400TE/G-11-X 12.0 17.5
diameter and substitute X 400TE/G-15-X 16.0 22.0
using table X, according to the 400TE/G-19-X 20.0 26.5
conductor size and type. 400TE/G-22-X 23.5 31.0
Add a 'K' for use up to 24 kV 400TE/G-25-X 26.5 32.5
and add an 'M' for use up to 400TE/G-27-X 28.5 37.5

36 kV.
Table X

Conductor Aluminium Copper


sizes
(mm) DIN hexagonal Deep indent DIN hexagonal

Example: 25 - - 25(K)M-11-2
The copper wire screened cable 35 35(K)M-12-2 35KM-12-1 35(K)M-11-2
is 24 kV, 240 mm2 stranded 50 50(K)M-12-2 50(K)M-12-1 50(K)M-11-2
70 70(K)M-12-2 70(K)M-12-1 70(K)M-11-2
aluminium with a diameter over
95 95(K)M-12-2 95(K)M-12-1 95(K)M-11-2
core insulation of 32.1 mm.
120 120(K)M-12-2 120(K)M-12-1 120(K)M-11-2
Order 3 x K400TE/G-27-
150 150(K)M-12-2 150(K)M-12-1 150(K)M-11-2
240(K)M-12-2 tee connector kit. 185 185(K)M-12-2 185(K)M-12-1 185(K)M-11-2
240 240(K)M-12-2 240(K)M-12-1 240(K)M-11-2

For use with For use with Alupe or For use with fabric tape For use with For outdoor Components can be
copper tape C 33-226 cables. (graphite) screened cables. other cable types. applications. ordered individually.
screened cables. Please contact our Order additional Please contact our Order: +MWS.
Order: Kit MT. representative. semi-conductive tape representative.
(type TSC).


400T1 /400AR-1 /400AR-2
INTERFACE B
EQUIPMENT BUSHINGS

Application Technical characteristics Up to 36 kV - 400 A


For use in equipment insulated Each bushing is tested for
with oil fluid, typically for AC withstand and partial
transformers, switch gear, discharge prior to leaving the
capacitors... factory.
6/10 (12) kV
6.35/11 (12) kV
8.7/15 (17.5) kV
12/20 (24) kV
12.7/22 (24) kV
18/30 (36) kV

Design
The equipment bushings are
moulded epoxy insulated parts in
accordance with CENELEC EN
50180.

Specifications and
standards C
The plug-in type equipment
10
bushings meet the requirements
A
of IEC 137. The (K)(M)400T1
also meets CENELEC EN
50180 .
B
Minimum oil level:
Ordering instructions -12 kV: 40 mm
-24 kV: 50 mm
To order the equipment -36 kV: 70 mm
bushing, specify the type.
The bushing are supplied
with an earth lead (/J) or an E
earth plate (/GS). This earth
connection must be specified D
when ordering. Dia. 70
Dia. F
E.g. K400AR-1/J. In mm
Dia. G

Equipment Voltage Current Dimensions (mm)


bushing Ur Ir
type (kV) (A) A B C D E Dia. F Dia. G
400T1 12 400 310 144 30 M12 22 88 128
K400T1 24 400 310 144 30 M12 22 88 128
M400T1 36 400 310 144 30 M12 22 88 128
400AR-1 12 400 380 213 30 M12 22 74 128
K400AR-1 24 400 380 213 30 M12 22 74 128
M400AR-1 36 400 380 213 30 M12 22 74 128
400AR-2 12 400 329 138 36 M16 40 100 150
K400AR-2 24 400 329 138 36 M16 40 100 150
04/2006

M400AR-2 36 400 329 138 36 M16 40 100 150


FIXINGS FOR
EQUIPMENT BUSHINGS
INTERFACE B

400AR-2/GS bushing 400AR-1/J and 400T1/J


NF C 52-053 bushings
French standards. DIN 42 538
German standards.

bushing interface

fixing studs

fixing flange
B DIN 42 538
NF C 52-053
E DIN 42 538
claw clamp
clamp

equipment

sealing gasket

equipment
connection

tabs for the


bail restraint

earth jumper

earth plate

NF C 52-053 DIN 42538


(French standards) (German standards)

M10 or M12 M10

30 25
50 to 70 55

4 fixing 6 fixing Dia. 90


studs Dia. 105
04/2006

studs
Dia. 140
Dia. 171
In mm

10
ACCESSORIES
INTERFACE B

Application Technical characteristics Up to 24 kV


For use with connectors and All these products, except the
bushings with an interface B earthing plug, are tested for
as described by CENELEC EN AC withstand and partial
50180 and 50181. discharge prior to leaving the
factory. 6/10 (12) kV
6.35/11 (12) kV
8.7/15 (17.5) kV
12/20 (24) kV
12.7/22 (24) kV
18/30 (36) kV

400DR Ordering instructions


Dead-end receptacle Order
Fits over a bushing with a type 400DR for 12 kV,
B interface to provide 'dead- K400DR for 24 kV or
end' facility. M400DR for 36 kV
Is used with a 400BA restraint applications.
bail. Can be supplied with integral
earth lead: add -/G.

400SOP Ordering instructions


Stand-off plug Order
Is designed to support and 400SOP for 12 kV,
'dead-end' connectors with a K400SOP for 24 kV or
type B interface when removed M400SOP for 36 kV
from equipment. applications.

400GP Ordering instructions


Earthing plug Order
Is designed to support and 400GP for 12 kV, 24 or 36 kV
earth connectors with a type B applications.
interface when removed from
equipment.
04/2006

11
400BIPA Ordering instructions
Basic insulating plug Order
Acts as a tightening nut for the 400BIPA for 12 kV,
400TE tee connector kit. K400BIPA for 24 kV or
The plug contains a voltage M400BIPA for 36 kV
detection point. applications.
The conductive rubber
protection cap is included.

400CP-SC Ordering instructions


Connecting plug Order
For connecting a 400TE and 400CP-SC for 12 kV,
one or more 430TB, 400TB K400CP-SC for 24 kV or
or 440TB connectors, thus M400CP-SC for 36 kV
creating a multiple cable applications.
connection to equipment.

400RTPA Ordering instructions


Reducing tap plug Order
Provides a type A interface to a 400RTPA for 12 kV or
400TE connector. K400RTPA for 24 kV
A 'C' spanner, 600SW, is used applications.
to tighten the reducing tap plug Order 600SW for the 'C'
on to its mating part. spanner.

Kit MT Ordering instructions


Earthing kit for copper Order
tape screened cables Kit MT for 12 kV, 24 kV
Contains a tinned copper braid or 36 kV applications.
(25 mm - L=500 mm), a
tinned copper wire for cleating
and water sealing mastic.

12
POSSIBLE ARRANGEMENTS
INTERFACE B

400TE/G 400TE/G-P2
Single cable arrangement. Dual cable arrangement.
Order 400TE/G for 12 kV, Order 400TE/G-P2 for 12 kV,
K400TE/G for 24 kV or K400TE/G-P2 for 24 kV or
M400TE/G for 36 kV M400TE/G-P2 for 36 kV
applications. applications.

250 500

400TCS
clamping
screw

basic connecting basic


insulating plug insulating
plug plug

110 110 245

400TE/G-P4 475
Single cable arrangement with
tap-off.
Order 400TE/G-P4 for 12 kV
or K400TE/G-P4 for 24 kV
applications. reducing type A
tap plug separable
connector

110 233
04/2006

In mm

13
Connector on stand-off Connector on earthing
plug plug
Order 400SOP for 12 kV, Order 400GP for 12 kV, 24 kV
K400SOP for 24 kV or and 36 kV applications.
M400SOP for 36 kV
applications.

stand-off basic basic


plug insulating insulating
plug plug

earthing
plug

Cable and equipment


testing.

600

400TR insulating
test rod shroud

110

In mm

14
Additional catalogue information on power cable accessories
is available by contacting us at the address below:

Distributed by:
EUROMOLD N.V. 04/2006

EUROMOLD N.V. headquarters Zuid III, Industrielaan 12, B-9320 Erembodegem


Tel.: +32 (0)53 85 02 11 Fax: +32 (0)53 83 10 13 www.nexans.com info.euromold@nexans.com

Catalogue also available on CD-ROM