Sie sind auf Seite 1von 8

Air System Sizing Summary for Building 1 8th to 15th

ProjectName:Building 09/08/2017
Preparedby:ArieListon 05:29PM

Air System Information


AirSystemName Building 1 8th to 15th Numberofzones 8
EquipmentClass CW AHU FloorArea 3840.0 m
AirSystemType VAV Location Manila, Philippines

Sizing Calculation Information


CalculationMonths Jan to Dec ZoneL/sSizing Peak zone sensible load
SizingData Calculated SpaceL/sSizing Individual peak space loads

Central Cooling Coil Sizing Data


Totalcoilload 179.0 kW Loadoccursat Aug 1800
Sensiblecoilload 117.5 kW OADB/WB 33.2 / 26.8 C
CoilL/satAug1800 6425 L/s EnteringDB/WB 28.0 / 20.3 C
MaxblockL/satNov1500 6425 L/s LeavingDB/WB 12.8 / 12.2 C
SumofpeakzoneL/s 6451 L/s CoilADP 11.1 C
Sensibleheatratio 0.656 BypassFactor 0.100
m/kW 21.5 ResultingRH 46 %
W/m 46.6 Designsupplytemp. 12.8 C
Waterflow@5.6Krise 7.71 L/s ZoneT-statCheck 0 of 8 OK
Maxzonetemperaturedeviation 0.4 K

Central Heating Coil Sizing Data


No central heating coil loads occurred during this calculation.

Supply Fan Sizing Data


ActualmaxL/satNov1500 6425 L/s FanmotorBHP 0.00 BHP
StandardL/s 6409 L/s FanmotorkW 0.00 kW
ActualmaxL/(s-m) 1.67 L/(s-m) Fanstatic 0 Pa

Outdoor Ventilation Air Data


DesignairflowL/s 1622 L/s L/s/person 8.63 L/s/person
L/(s-m) 0.42 L/(s-m)

HourlyAnalysisProgramv4.90 Page1of8
Zone Sizing Summary for Building 1 8th to 15th
ProjectName:Building 09/08/2017
Preparedby:ArieListon 05:29PM

Air System Information


AirSystemName Building 1 8th to 15th Numberofzones 8
EquipmentClass CW AHU FloorArea 3840.0 m
AirSystemType VAV Location Manila, Philippines

Sizing Calculation Information


CalculationMonths Jan to Dec ZoneL/sSizing Peak zone sensible load
SizingData Calculated SpaceL/sSizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m) L/(s-m)
Zone1 15.6 1166 306 Oct1500 0.1 720.0 1.62
Zone2 15.6 1166 306 Oct1500 0.1 720.0 1.62
Zone3 13.7 1025 238 Nov1500 0.1 560.0 1.83
Zone4 13.7 1025 238 Nov1500 0.1 560.0 1.83
Zone5 8.5 633 168 Nov1500 0.1 400.0 1.58
Zone6 8.5 633 168 Nov1500 0.1 400.0 1.58
Zone7 5.4 401 100 Nov1500 0.0 240.0 1.67
Zone8 5.4 401 100 Nov1500 0.0 240.0 1.67

Zone Terminal Sizing Data


NoZoneTerminalSizingDatarequiredforthissystem.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m) L/(s-m)
Zone 1
SU801 2 1.5 Jun0800 110 0.0 40.0 2.76
DU801 3 1.6 Jun0800 121 0.0 60.0 2.02
DU804 1 1.7 Jun0800 124 0.0 60.0 2.07
FDU801 1 2.3 Dec1500 173 0.0 80.0 2.16
FDU802 3 2.2 Dec1500 167 0.0 80.0 2.09
FDU805 1 2.3 Dec1500 169 0.0 80.0 2.11
Zone 2
SU801 2 1.5 Jun0800 110 0.0 40.0 2.76
DU801 3 1.6 Jun0800 121 0.0 60.0 2.02
DU804 1 1.7 Jun0800 124 0.0 60.0 2.07
FDU801 1 2.3 Dec1500 173 0.0 80.0 2.16
FDU802 3 2.2 Dec1500 167 0.0 80.0 2.09
FDU806 1 2.3 Dec1500 168 0.0 80.0 2.10
Zone 3
SU801 2 1.5 Jun0800 110 0.0 40.0 2.76
FDU1001 1 1.8 Jun0800 132 0.0 80.0 1.65
FDU1002 1 1.8 Jun0800 135 0.0 80.0 1.69
DU1001 1 2.2 Dec1500 164 0.0 60.0 2.74
DU1002 3 2.1 Dec1500 159 0.0 60.0 2.65
FDU1003 1 2.3 Dec1500 168 0.0 80.0 2.10
Zone 4
SU801 2 1.5 Jun0800 110 0.0 40.0 2.76
FDU1001 1 1.8 Jun0800 132 0.0 80.0 1.65
FDU1002 1 1.8 Jun0800 135 0.0 80.0 1.69
DU1001 1 2.2 Dec1500 164 0.0 60.0 2.74
DU1002 3 2.1 Dec1500 159 0.0 60.0 2.65
FDU1003 1 2.3 Dec1500 168 0.0 80.0 2.10

HourlyAnalysisProgramv4.90 Page2of8
Zone Sizing Summary for Building 1 8th to 15th
ProjectName:Building 09/08/2017
Preparedby:ArieListon 05:29PM

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m) L/(s-m)
Zone 5
VSU1201 1 1.8 Jun0800 132 0.0 80.0 1.65
VSU1202 1 1.8 Jun0800 135 0.0 80.0 1.69
VSU1203 1 2.3 Dec1500 173 0.0 80.0 2.16
EU1201 1 2.3 Dec1500 174 0.0 100.0 1.74
DU1201 1 2.1 Dec1500 160 0.0 60.0 2.66
Zone 6
VSU1201 1 1.8 Jun0800 132 0.0 80.0 1.65
VSU1202 1 1.8 Jun0800 135 0.0 80.0 1.69
VSU1203 1 2.3 Dec1500 173 0.0 80.0 2.16
EU1201 1 2.3 Dec1500 174 0.0 100.0 1.74
DU1201 1 2.1 Dec1500 160 0.0 60.0 2.66
Zone 7
VSU1201 1 1.8 Jun0800 132 0.0 80.0 1.65
DU1401 1 2.2 Dec1500 164 0.0 60.0 2.74
EU1401 1 2.3 Dec1500 175 0.0 100.0 1.75
Zone 8
VSU1201 1 1.8 Jun0800 132 0.0 80.0 1.65
DU1401 1 2.2 Dec1500 164 0.0 60.0 2.74
EU1401 1 2.3 Dec1500 175 0.0 100.0 1.75

HourlyAnalysisProgramv4.90 Page3of8
Ventilation Sizing Summary for Building 1 8th to 15th
ProjectName:Building 09/08/2017
Preparedby:ArieListon 05:29PM

1. Summary
VentilationSizingMethod Sum of Space OA Airflows
DesignVentilationAirflowRate 1622 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m) Occupants (L/s) (L/s/person) (L/(s-m)) (L/s) (% of supply) (L/s)
Zone 1
SU801 2 40.0 2.0 110.5 2.50 0.30 0.0 0.0 17.0
DU801 3 60.0 3.0 121.3 2.50 0.30 0.0 0.0 25.5
DU804 1 60.0 3.0 124.5 2.50 0.30 0.0 0.0 25.5
FDU801 1 80.0 4.0 172.7 2.50 0.30 0.0 0.0 34.0
FDU802 3 80.0 4.0 167.3 2.50 0.30 0.0 0.0 34.0
FDU805 1 80.0 4.0 168.6 2.50 0.30 0.0 0.0 34.0
Zone 2
SU801 2 40.0 2.0 110.5 2.50 0.30 0.0 0.0 17.0
DU801 3 60.0 3.0 121.3 2.50 0.30 0.0 0.0 25.5
DU804 1 60.0 3.0 124.5 2.50 0.30 0.0 0.0 25.5
FDU801 1 80.0 4.0 172.7 2.50 0.30 0.0 0.0 34.0
FDU802 3 80.0 4.0 167.3 2.50 0.30 0.0 0.0 34.0
FDU806 1 80.0 4.0 168.4 2.50 0.30 0.0 0.0 34.0
Zone 3
SU801 2 40.0 2.0 110.5 2.50 0.30 0.0 0.0 17.0
FDU1001 1 80.0 4.0 132.2 2.50 0.30 0.0 0.0 34.0
FDU1002 1 80.0 4.0 135.4 2.50 0.30 0.0 0.0 34.0
DU1001 1 60.0 3.0 164.1 2.50 0.30 0.0 0.0 25.5
DU1002 3 60.0 3.0 158.7 2.50 0.30 0.0 0.0 25.5
FDU1003 1 80.0 4.0 168.4 2.50 0.30 0.0 0.0 34.0
Zone 4
SU801 2 40.0 2.0 110.5 2.50 0.30 0.0 0.0 17.0
FDU1001 1 80.0 4.0 132.2 2.50 0.30 0.0 0.0 34.0
FDU1002 1 80.0 4.0 135.4 2.50 0.30 0.0 0.0 34.0
DU1001 1 60.0 3.0 164.1 2.50 0.30 0.0 0.0 25.5
DU1002 3 60.0 3.0 158.7 2.50 0.30 0.0 0.0 25.5
FDU1003 1 80.0 4.0 168.4 2.50 0.30 0.0 0.0 34.0
Zone 5
VSU1201 1 80.0 4.0 132.2 2.50 0.30 0.0 0.0 34.0
VSU1202 1 80.0 4.0 135.4 2.50 0.30 0.0 0.0 34.0
VSU1203 1 80.0 4.0 172.7 2.50 0.30 0.0 0.0 34.0
EU1201 1 100.0 4.0 173.9 2.50 0.30 0.0 0.0 40.0
DU1201 1 60.0 3.0 159.8 2.50 0.30 0.0 0.0 25.5
Zone 6
VSU1201 1 80.0 4.0 132.2 2.50 0.30 0.0 0.0 34.0
VSU1202 1 80.0 4.0 135.4 2.50 0.30 0.0 0.0 34.0

HourlyAnalysisProgramv4.90 Page4of8
Ventilation Sizing Summary for Building 1 8th to 15th
ProjectName:Building 09/08/2017
Preparedby:ArieListon 05:29PM

VSU1203 1 80.0 4.0 172.7 2.50 0.30 0.0 0.0 34.0


EU1201 1 100.0 4.0 173.9 2.50 0.30 0.0 0.0 40.0
DU1201 1 60.0 3.0 159.8 2.50 0.30 0.0 0.0 25.5
Zone 7
VSU1201 1 80.0 4.0 132.2 2.50 0.30 0.0 0.0 34.0
DU1401 1 60.0 3.0 164.1 2.50 0.30 0.0 0.0 25.5
EU1401 1 100.0 4.0 174.9 2.50 0.30 0.0 0.0 40.0
Zone 8
VSU1201 1 80.0 4.0 132.2 2.50 0.30 0.0 0.0 34.0
DU1401 1 60.0 3.0 164.1 2.50 0.30 0.0 0.0 25.5
EU1401 1 100.0 4.0 174.9 2.50 0.30 0.0 0.0 40.0
Totals (incl. Space Multipliers) 8189.4 1622.0

HourlyAnalysisProgramv4.90 Page5of8
Air System Design Load Summary for Building 1 8th to 15th
ProjectName:Building 09/08/2017
Preparedby:ArieListon 05:29PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1800 HEATING DATA AT DES HTG
COOLING OA DB / WB 33.2 C / 26.8 C HEATING OA DB / WB 20.6 C / 14.2 C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window&SkylightSolarLoads 313m 32199 - 313m - -
WallTransmission 947m 3106 - 947m 182 -
RoofTransmission 0m 0 - 0m 0 -
WindowTransmission 313m 8648 - 313m 562 -
SkylightTransmission 0m 0 - 0m 0 -
DoorLoads 0m 0 - 0m 0 -
FloorTransmission 0m 0 - 0m 0 -
Partitions 0m 0 - 0m 0 -
Ceiling 0m 0 - 0m 0 -
OverheadLighting 26880W 17248 - 0 0 -
TaskLighting 0W 0 - 0 0 -
ElectricEquipment 0W 0 - 0 0 -
People 188 9653 11295 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
SafetyFactor 0%/0% 0 0 0% 0 0
>> Total Zone Loads - 70854 11295 - 744 0
ZoneConditioning - 95085 11295 - -12437 0
PlenumWallLoad 20% 1122 - 0 0 -
PlenumRoofLoad 70% 0 - 0 0 -
PlenumLightingLoad 30% 8064 - 0 0 -
ReturnFanLoad 6425L/s 0 - 1622L/s 0 -
VentilationLoad 1622L/s 13577 50251 409L/s -696 0
SupplyFanLoad 6425L/s 0 - 1622L/s 0 -
SpaceFanCoilFans - 0 - - 0 -
DuctHeatGain/Loss 0% 0 - 0% 0 -
>> Total System Loads - 117848 61546 - -13133 0
CentralCoolingCoil - 117467 61546 - -13133 0
CentralHeatingCoil - 0 - - 0 -
>> Total Conditioning - 117467 61546 - -13133 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

HourlyAnalysisProgramv4.90 Page6of8
System Psychrometrics for Building 1 8th to 15th
ProjectName:Building 09/08/2017
Preparedby:ArieListon 05:29PM

August DESIGN COOLING DAY, 1800

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (C) (kg/kg) (L/s) (ppm) (W) (W)
VentilationAir Inlet 33.2 0.01973 1622 400 13577 50251
Vent-ReturnMixing Outlet 28.0 0.01185 6425 862 - -
CentralCoolingCoil Outlet 12.8 0.00859 6425 862 117467 61546
CentralHeatingCoil Outlet 12.8 0.00859 6425 862 0 -
SupplyFan Outlet 12.8 0.00859 6425 862 0 -
ColdSupplyDuct Outlet 12.8 0.00859 6425 862 - -
ZoneAir - 25.0 0.00919 6425 1018 95085 11295
ReturnPlenum Outlet 26.2 0.00919 6425 1018 9186 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.204 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2940.3 W/(L/s)
Site Altitude = 20.7 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (C) (L/s) (ppm) (W) (W)
Zone1 13515 Cooling 17397 25.2 1162 1028 0 0
Zone2 13500 Cooling 17389 25.2 1161 1028 0 0
Zone3 10989 Cooling 15014 24.9 1021 1008 0 0
Zone4 10989 Cooling 15014 24.9 1021 1008 0 0
Zone5 6821 Cooling 9301 25.0 630 1023 0 0
Zone6 6821 Cooling 9301 25.0 630 1023 0 0
Zone7 4109 Cooling 5834 24.9 400 1009 0 0
Zone8 4109 Cooling 5834 24.9 400 1009 0 0

HourlyAnalysisProgramv4.90 Page7of8
System Psychrometrics for Building 1 8th to 15th
ProjectName:Building 09/08/2017
Preparedby:ArieListon 05:29PM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (C) (kg/kg) (L/s) (ppm) (W) (W)
VentilationAir Inlet 20.6 0.00752 409 400 696 0
Vent-ReturnMixing Outlet 19.5 0.00752 1622 429 - -
CentralCoolingCoil Outlet 12.8 0.00752 1622 429 13133 0
CentralHeatingCoil Outlet 12.8 0.00752 1622 429 0 -
SupplyFan Outlet 12.8 0.00752 1622 429 0 -
ColdSupplyDuct Outlet 12.8 0.00752 1622 429 - -
ZoneAir - 19.1 0.00752 1622 439 12437 0
ReturnPlenum Outlet 19.1 0.00752 1622 439 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.204 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2940.3 W/(L/s)
Site Altitude = 20.7 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (C) (L/s) (ppm) (W) (W)
Zone1 -141 Deadband 2343 19.1 306 439 0 0
Zone2 -140 Deadband 2343 19.1 306 439 0 0
Zone3 -117 Deadband 1825 19.1 238 439 0 0
Zone4 -117 Deadband 1825 19.1 238 439 0 0
Zone5 -71 Deadband 1285 19.1 168 439 0 0
Zone6 -71 Deadband 1285 19.1 168 439 0 0
Zone7 -44 Deadband 765 19.2 100 439 0 0
Zone8 -44 Deadband 765 19.2 100 439 0 0

HourlyAnalysisProgramv4.90 Page8of8