Withincreasingpricehikeforcopper(inIran)anditsvulnerabilitytotheft,thereis
someconcerntotelecommunications,utilitycompanyandbuildingcontractorstofind
analternativematerialtocopperasagroundingnetwork.Theaimofthisarticleisthe
comparisonofCopperwithSteelforGroundingPurposes.Therelevantkeytechnical
characteristicsofSteelincomparisonwithcopperare:
Steelabsorbsapproximately1.36timesasmuchheatasanequalvolumeofcopper
beforefusing(whenconsideringthespecificweight,specificheatandthemelting
temperature).
Steelcanwithstandhighertemperaturebeforemelting(1510Centigradecompared
to1083Centigradeforcopper).
Itrequiresabout5.6(ratioofresistivity=RhoCu/RhoFe)timesasmuchsteelto
achievethesameresistanceascopper.
Steelisapproximatelytwiceasmechanicallystrongascomparedtocopperforthe
samecrosssectionalarea.
BasedonthepricesofsteelandcopperinIran,substantial(estimatedat
approximately40%50%)savingscanbeachievedinsomesteelgroundingdesign
https://www.linkedin.com/pulse/sescdegscoppervssteelgroundingsystemsfarzinkhaleghi 1/5
6/1/2017 SESCDEGSCopperVs.SteelinGroundingSystems|FarzinKhaleghi|Pulse|LinkedIn
afterincorporatingtheeffectofcorrosionandcathodicprotection.Thesavings 3 14
Buscargente,empleos,empresasydems Avanzada
Inicio Perfil Mired
wouldbemuchhigherinothercountries,wherecopperisveryexpensive.
Aprendizaje Empleos Intereses Servicioscomerciales PruebaunacuentaPremiumgratis
electricalcharacteristicsofcopper,i.e.groundingsystemsweremadeofsteel
conductorsthathavehigherpermeabilityandlowerconductivitythancopper.
steelconductorsarewellknownforitsvulnerabilityforcorrosion,comparedto
copper.
Abovefigureshowsthatthereare4separatetrenchesconstructedinasampleproject
whichhavebeenbuiltandbeenmonitoredfor6months.Fortrench2andtrench4,
therearedifferentfromtherestsasthesetrenchesareaddedwithEAF,whichiscarbon
basedpowdertypefillerwhichismarketedworldwide.
ThemeasureddataUsingFallofPotentialmethodareshowninnextTableandFigure.
Thedifferenceofgroundingimpedancevalueforcoppertapeandstrandedgalvanized
ironis10.45%forsystemswithoutEAF.Meanwhile,thedifferencefortrencheswith
additionofEAFis11.13%.
So,onecanconcludethatthey(Steel&Copper)havealmostthesameimpedance.But,
thisisnotallthestory!Let'slookatthissubjectwithadifferentpointofview:
Groundingsystemsweremadeofsteelconductorsthathavehigherpermeabilityand
lowerconductivitythancopperandthisraisessomeuniqueissues.Inaconventional
groundinganalysisapproach,agroundingsystemisgenerallyassumedasan
equipotentialstructure.Thiswouldbeinaccurateforagroundinggridmadeofsteel,
especiallyifthesubstationsizeislargeandthesoilresistivityislow.Infact,theground
impedanceofthegroundingsystemhasasignificantinductivecomponent,whichisnot
takenintoaccountbyclassicalgroundinganalysismethods.Inordertogetaccurate
results,theanalysisofthegroundingperformancewascarriedoutusingthe
MultiGroundZsoftwarepackage,whichtakesintoaccountvoltagedropsalong
conductorsinagroundingsystem,therefore,eliminatingtheassumptionthata
groundinggridisanequipotential.
Consideringthegridimbeddedinauniformsoil,thegroundimpedance,GPR,GPD,
touchandstepvoltagesarecomputedfora200mby200mgrid.BelowFigurepresents
thecomputedresultsforbothcopperandsteelgrids.
https://www.linkedin.com/pulse/sescdegscoppervssteelgroundingsystemsfarzinkhaleghi 2/5
6/1/2017 SESCDEGSCopperVs.SteelinGroundingSystems|FarzinKhaleghi|Pulse|LinkedIn
3 14
Buscargente,empleos,empresasydems Avanzada
Inicio Perfil Mired Aprendizaje Empleos Intereses Servicioscomerciales PruebaunacuentaPremiumgratis
Letuslookattheresultsshowninabovefigures.Forasoilresistivityof5ohmm,the
groundimpedanceis0.0132ohmforthecoppergridand0.0234ohmforthesteelgrid,
adifferenceof77.5%.
Whileforasoilresistivityof1000ohmm,thegroundimpedancesare1.129ohmand
1.130ohmforcopperandsteelgrids,respectively.Thedifferenceof0.12%is
negligible.
Thegroundpotentialrise(GPR)is261.5Vforacoppergrid,56%ofthesteelgrid
(466.04V)whenthesoilresistivityis5ohmm.Whenthesoilresistivityincreasesto
1000ohmm.Thegroundpotentialrisesofthecopperandsteelconductorsarealmost
thesame,i.e.,45130Vvs.45020V.
Inasoilof5ohmmand1000ohmmsoilresistivity,thecomputedmaximumtouch
voltagesare54.2Vand11041Vforagridconsistingofcopperconductorsand93.7V
and10580Vforagridconsistingofsteelconductors,resultingin72.9%(5ohmm)
and4.10%(1000ohmm)differences,respectively.Similarly,thestepvoltageshave
differencesof96.7%and1.6%forthetwosoilmodels,respectively.
CONCLUSIONS
Foruniformsoilswithhighresistivity,
groundingsystemsconsistingofsteel
conductorshaveperformancethatissimilar
tothoseconsistingofcopperconductors.For
uniformsoilswithlowresistivity,grounding
systemsconsistingofsteelconductorshavea
muchsmallereffectivesizethanthose
consistingofcopperconductors.Therefore,a
coppergridwillprovideabetterperformance
thanasteelgrid.
Foratwolayersoil,whenthebottomlayer
resistivityishigh,thegroundingsystems
consistingofsteelconductorsbehavemuch
likecoppergrids.Whenthebottomlayer
resistivityislow,theeffectivesizeofa
https://www.linkedin.com/pulse/sescdegscoppervssteelgroundingsystemsfarzinkhaleghi 3/5
6/1/2017 SESCDEGSCopperVs.SteelinGroundingSystems|FarzinKhaleghi|Pulse|LinkedIn
groundingsystemconsistingofsteel
Buscargente,empleos,empresasydems
Avanzada
3
14
thiscase,agroundinggridmadeofcopper
conductorswillhaveamuchbetter
performancethanagridconsistingofsteel
conductors.
Whenthesizeofagroundinggridissmall,the
performanceofacoppergroundinggridisnot
significantlyimprovedcomparedtothatofa
steelgrid.
Duetothecomplexityofrealsoilstructures,theperformanceofindividual
groundingsystemsmustbeevaluatedcorrectlyusingadequatesoftwaretoolsto
avoidcostlyoverdesignsordangerousunderdesigns.
Ref:
"PowerGroundingSafety:CopperGroundingSystemsvs.SteelGrounding
Systems"byYexuLi,JinxiMa,andFaridPaulDawalibi
"ComparisonStudyofUsageasGroundingElectrodebetweenGalvanizedIron
andCopperwithandwithoutEarthAdditiveFiller"byF.Mahtar,A.Ramli,
W.R.WanAbdullah,M.N.Isa
"SteelGroundingDesignGuideandApplicationNotes"byP.K.Sen,Ph.D.,P.E.,
KeithMalmedal,P.E.,JohnP.Nelson,FellowIEEE,P.E.
Denunciar esto
Farzin Khaleghi
Member of TC 81 Committee - Lightning protection at Iranian National Standards Orginiz Seguir
22 artculos
1 comentario Recomendado
https://www.linkedin.com/pulse/sescdegscoppervssteelgroundingsystemsfarzinkhaleghi 4/5
6/1/2017 SESCDEGSCopperVs.SteelinGroundingSystems|FarzinKhaleghi|Pulse|LinkedIn
SES CDEGS - Feasibility of Electrical CDEGS So ware - What can i do with CDEGS So ware - Risk Managment
Separation of Proximate Grounding "Finite Volume" in real projects using based on IEC 62305-2 Using SES-Shield
Systems as a Function of Soil Structure CDEGS! Farzin Khaleghi en LinkedIn
Farzin Khaleghi en LinkedIn Farzin Khaleghi en LinkedIn
Descubre ms historias
Centrodeayuda Acercade Carrerasprofesionales Publicidad TalentSolutions SalesSolutions SmallBusiness Mvil Idioma Abnateaunacuentasuperior
LinkedInCorporation2017 Condicionesdeuso Polticadeprivacidad Opcionesdeanuncio Directricescomunitarias Polticadecookies Polticadecopyright Enviarcomentarios
https://www.linkedin.com/pulse/sescdegscoppervssteelgroundingsystemsfarzinkhaleghi 5/5