application.............................................................1 Calibration...........................................................23
Calibration Overview...........................................23
OPERATION OVERVIEW............................................2 Important Calibration Notes................................23
Theory of Operation..............................................2 Calibration Initiation.............................................23
Detectable Gases..................................................2 Detailed Calibration Procedure using
Standard Output....................................................2 Magnetic Switch..................................................23
Optional Relays.....................................................2
Communication.....................................................3 Maintenance........................................................23
Recording Capability.............................................3 Routine Inspection..............................................23
Detection Range...................................................3 Optics Cleaning...................................................24
Protective Caps and Covers................................24
Operation................................................................3
Module Identification.............................................3 Troubleshooting...............................................24
Operating Modes..................................................4
4-20 mA Current Loop Output...............................4 Replacing opecl transmitter/
Fault Indication......................................................5 receiver electronics module.....................25
Transmitter Lamp Operation..................................5 Module Replacement Procedure.........................25
Important
Be sure to read and understand the entire
instruction manual before installing or operating
the gas detection system. This product is intended
to provide early warning of the presence of a
flammable or explosive gas mixture. Proper device
installation, operation, and maintenance is required
to ensure safe and effective operation.
application
The Open Path Eclipse Model OPECL is an open
path infrared gas detection system that provides
continuous monitoring of combustible hydrocarbon gas
concentrations in the range of 0 to 5 LFL-meters, over a
distance of 5 to 120 meters. Standard system outputs
include an electrically isolated/non-isolated 4-20 mA dc
current output, with HART communication and RS-485
MODBUS communication. Alarm and fault relays are
available as an option. A LON based model (with no
analog or relay outputs) is available for use with Eagle
Quantum Premier systems.
10.2 2 95-8556
communication Operation
The standard OPECL system provides an analog 4-20
mA signal output, with HART and RS-485 MODBUS serial Module Identification
communication from the receiver module. EQP Models
While the OPECL transmitter and receiver modules
communicate with the EQP controller over the LON.
appear physically identical, each module is labeled as
transmitter or receiver on the enclosure. The physical
recording capability mounting requirements for both modules are generally
identical. However, there are functional and electrical
Non-volatile memory is provided to save the 10 most
characteristic differences as identified in Table 1.
recent calibrations, alarm/fault events, and minimum/
maximum operating temperature history. A real time
clock is provided to record operating service time and to
time stamp events. This information is accessible using
HART and MODBUS communication, or S3 software for
EQP models.
Detection Range
The standard OPECL system can cover a range of 5 to
120 meters.
10.2 3 95-8556
Table 2Factory Default Settings
The OPECL has four operating modes: warm-up, Fault Mode OPGD-Rx PIR9400, User Defined
normal, alignment and calibrate.
Warm-up
Calibrate
Warm-up mode is entered upon application of 24 Vdc After alignment is completed, zero calibration is
operating power. During warm-up, the 4-20 mA current required. Span calibration of the OPECL is normally
loop output will indicate warm-up, the indicating LED is not required; however, the user has the option to verify
yellow, and the alarm outputs are disabled. The warm- proper calibration or to perform calibration procedures if
up mode lasts nominally two minutes after power-up. necessary. It is recommended that the zero calibration
procedure be performed annually. Refer to the
"Calibration" section in this manual for details.
Normal
After warm-up mode is completed, the device
4-20 mA Current Loop Output
automatically enters the Normal mode, and all analog
and alarm outputs are enabled. OPECL provides a linear current loop output that is
proportional to the detected gas level. Fault and
calibration status are also indicated by this output.
Alignment
The OPECL modules must be properly aligned before The factory default for full-scale 5 LFL-meters output
normal operation is attained. There are two alignment is 20 mA. MODBUS interfaces also have the ability to
procedures: calibrate the 4 mA and 20 mA levels.
1. Basic Alignment requires the OPECL Alignment Kit. EQP models use LON communication, and do not have
a 4-20 mA output.
2. Fine Alignment requires the OPECL Alignment Kit
and a handheld HART Communicator.
10.2 4 95-8556
Fault Indication Transmitter LAMP Operation
Faults and status conditions are indicated using the 420 Dual xenon lamps illuminate the linear detection path
mA analog signal output. Refer to Table 3. Signaling from the transmitter to the receiver. Should excessive
modes include two predefined and one user defined degradation of the light intensity occur, the transmitter
mode. OPGD-Rx mode (default) is available as well as automatically increases the light output of the bulbs.
a user defined mode for third party compatibility. The receiver recognizes this condition by the change
in flash pulse coding and responds by initiating a "Tx
Lamp Fault" warning signal. Total system operation
is maintained, with no loss of sensitivity or detection
performance.
Table 3Detector Status Conditions Indicated by Current Level In this mode of operation, the following occur:
Status 4-20 mA Level (0.1)
1. The indicator LED turns yellow on both the
OPGD-Rx PIR9400 transmitter and the receiver.
(Default)
Normal Gas: 0.35 to 5 LFL-M 2.88 to 20.0 2.88 to 20.0 2. HART and MODBUS communication warn of a Tx
Warmup 1.0 1.0 Lamp Fault condition.
Zero Calibration 1.0 2.2
Calibration Fault 1.0 1.6 3. The 4-20 mA signal drops from a normal 4 mA to 3.0
Beam Block 2.0 1.0 mA in OPGDRx mode (default) or 2.4 mA in PIR9400
Tx Lamp Fault* 3.0 2.4 mode. The analog output value is overridden if the
Calibrate Active at Startup 1.0 0.6 gas level exceeds 0.5 LFL-meters. All gas alarm
EE Error 1.0 1.2 signals will occur as normal.
Ref. ADC Saturated 1.0 0.2
Active ADC Saturated 1.0 0.4 4. The EQP system indicates a trouble condition.
24 VDC Fault 1.0 0.8
Zero Drift 1.0 2.4 Service should be arranged as soon as possible. A new
Flash CRC Error 1.0 1.2 transmitter module should be installed.
RAM Error 1.0 1.2
Over Range 20.4 20.4 note
The Tx Lamp Fault condition indicated by the
*Device is still functional. Gas overrides this indication. 420 mA output can be acknowledged by applying
a magnet to the transmitter module for at least
5 seconds. The coded flash sequence will then
return to normal, which causes the 4-20 mA signal
at the receiver module to also return to normal.
The indicator LED on the receiver will return to
green, however, the indicator LED on the transmitter
will remain yellow to annunciate the lamp fault
condition. This condition will continue until power
to the transmitter unit is cycled or the lamps no
longer operate.
10.2 5 95-8556
Specifications CAUTION
When the OPECL Gas Detector is used in
Input Voltage (Both Modules) conjunction with an appropriate certified Control
24 Vdc nominal. Operating range is 18 to 30 Vdc. Unit and configured for a non-latching high alarm,
Ripple cannot exceed 0.5 volts P-P. the control unit must always latch and require a
deliberate manual action to clear a high gas alarm.
Power Consumption (Per Module) When used as a stand alone device, the high
alarm must always be programmed for latching
Transmitter
operation.
5.0 watts nominal @ 24 Vdc, 6.9 watts @ 30 Vdc.
5.8 watts peak @ 24 Vdc, 7.5 watts peak @ 30 Vdc. FAULT RELAY
Form C Type (NO/NC). Energized during Normal mode,
De-Energized on Fault or loss of power.
Receiver Without Relays
Contact Rating: 5 amperes at 30 VDC.
6.0 watts nominal @ 24 Vdc, 7.6 watts nominal @ 30 Vdc. Non-Latching Operation only not programmable.
10.2 6 95-8556
accuracy HART COMMUNICATION PORT
Refer to the appropriate Appendix for details. An intrinsically safe port is provided on the receiver for
connecting a Rosemount/Emerson HART Communicator.
Note Maximum separation distance between receiver and
Misalignment will cause the manufacturer stated communicator is 610 meters.
Accuracy limits to increase, but remain within the
limits of EN 50241-1, -2, EN 60079-29-4, and IEC Optics Protection
60079-29-4. Stainless steel brow provides a degree of protection
against windblown dirt and rain. Heated optics mitigate
Temperature Range against ice and dew formation.
Operating: 55C to +60C (67F to +140F)
Storage: 55C to +85C (67F to +185F) Wiring
Hazardous Locations: Refer to the appropriate Field wiring screw terminals are UL/CSA rated for up to
Appendix for correct ambient 14 AWG shielded wire, and are DIN/VDE rated for 2.5
temperature range: mm2 wire. Screw terminal required torque range is 3.5
4.4 lb.-in. (0.4-0.5 Nm). Receiver can be wired using 3
Appendix A - FM or 4 wires. Transmitter requires two wires (power only).
Appendix B - CSA
Appendix C - ATEX Certification
Appendix D - IEC
FM
HUMIDITY
SELF-DIAGNOSTIC TEST
Fail-Safe operation ensured by performing all critical
tests once per second.
10.2 7 95-8556
Dimensions Shipping Weight
Transmitter or receiver (replacement):
Module
30 pounds (14 kg)
Length: 11.5 inches (29 cm) Transmitter and receiver with mounting hardware:
Diameter: 3.5 inches (9 cm) nominal 75 pounds (34 kg)
4.5 inches (11 cm) maximum
warranty
Mounting Plate
2 year limited warranty from date of manufacture.
Height: 14.5 inches (37 cm)
Width: 6.5 inches (16 cm)
Designed to attach to a 4 inch nominal diameter pipe.
8.0
Refer to Figure 3A for mounted dimensions and Figure
3B for maximum pan/tilt angles of the mounting plate.
14.5
(36.8)
14.3
(36.3)
7.8
(19.8)
19.0
7.3
(18.5)
7.8
A2634
2251E (19.8)
Figure 3AMounted Dimensions of OPECL in Inches (cm) Figure 3BMaximum Pan/Tilt Angles of Mounting Plate
10.2 8 95-8556
Important Safety Notes Installation
CAUTION
Identification of vapor(s) to be detected
The wiring procedures in this manual are intended
to ensure proper functioning of the system under It is necessary to identify the flammable vapor(s) of
normal conditions. However, because of the interest at the job site in order to determine the proper
many variations in wiring codes and regulations, calibration gas setting for OPECL. In addition, the
total compliance to these ordinances cannot be physical and fire hazard properties of the vapor, such
guaranteed. Be certain that all wiring complies as vapor density and flashpoint should be identified
with the NEC as well as all local ordinances. If and used to assist in selecting the optimum detector
in doubt, consult the authority having jurisdiction mounting locations within the area. The detector must
before wiring the system. Installation must be be installed by qualified personnel only, following local
done by a properly trained person. electrical equipment installation practices.
CAUTION
System Location considerations
This product has been tested and approved
for use in hazardous areas. However, it must The OPECL system is designed for installation in
be properly installed and used only under the hazardous industrial areas. Each module is normally
conditions specified within this manual and installed using a solid vertical steel post or flat surface
the specific approval certificates. Any device mounting adapter to support the weight of the module.
modification, improper installation, or use in a faulty The modules must be strategically located so that the
or incomplete configuration will render warranty hydrocarbon vapor(s) to be detected will intersect
and product certifications invalid. the light beam generated by the transmitter module.
Dispersion characteristics and behavior of the vapor
CAUTION cloud resulting from a gas leak can be difficult to
The system contains no user serviceable internal estimate due to the significant number of variables that
components. Service or repair should never be exist at different applications. Identification of expected
attempted by the user. Device repair should be gas leakage source(s), leak scenario identification,
performed only by the manufacturer or trained and onsite leak simulation are the steps generally
service personnel. recommended to provide the most accurate means of
identifying optimum system installation locations.
Liabilities
The manufacturers warranty for this product is In all cases, the beam path and surrounding area should
void, and all liability for proper function of the be kept free of obstructions that could block the infrared
system is irrevocably transferred to the owner or beam or hinder the free movement of air within the
operator in the event that the device is serviced or area. A clear beam path of 20 CM diameter or greater
repaired by personnel not employed or authorized is required. The system is immune to the effects of
by Detector Electronics Corporation, or if the exposure to both direct and reflected sunlight.
system is used in a manner not conforming to its
intended use. Avoid installation in areas with obstructions such as
steam vents and plumes, smoke stacks and chimneys,
Caution walkways and personnel areas, splash and sprayed
Observe precautions for handling electrostatic water, parking, loading, cranes, vehicle-related areas
sensitive devices. such as bus stops, road junctions, and vegetation such
as trees, shrubs, grass etc.
note
The Open Path Eclipse is intended for detection Det-Tronics Field Service Engineering group routinely
of hydrocarbon vapors only. The device will not provides jobsite application surveys and analysis for
detect hydrogen gas. customers, and their services are highly recommended
if guidance on optimum installation locations is required.
note Additional guidance on the positioning of gas detectors
The terminal compartment for OPECL without for optimum coverage is contained in BS6959 and other
relays is designed for either an increased safety national codes. Consult these codes of practice when
e termination or a flameproof d termination of determining where detectors are to be located.
the supply cable. If a flameproof connection is
chosen, then an ATEX certified cable entry device
must be used. The OPECL with relays requires Ex
d cable entry devices only.
10.2 9 95-8556
Consideration of the following system location guidelines Snow and Ice in Ambients Below 20C
is also recommended:
The heated optics on both modules will melt snow or
ice on the windows in ambient temperatures down to
LED Visibility approximately 20C. Below this temperature, snow
or ice blown onto the window will not be melted until
Select a mounting orientation where the Open Path
the ambient temperature rises. If longterm outdoor
Eclipse status indication LED is visible to personnel
operation in very cold climates is intended, extra
within the area.
shielding / covers are recommended to prevent
accumulation of snow and ice on the windows.
Module Separation Distance
The transmitter and receiver modules must be installed Deluge and Flooding
directly facing each other across the area to be
The modules are rated IP66/IP67 and will not be
protected. Physical obstructions in the direct line of
damaged by occasional deluge or flooding. However,
sight between the modules are not permitted. The
during such an event, the unit will completely lose its
overall line of sight distance between the modules must
IR signal and will enter the Beam-Block / Fault state.
not fall outside the specified operating distance range
In addition, when the deluge / flooding subsides, there
(refer to Specifications for details).
is the possibility that contaminants will be left on the
windows. Install the modules away from areas prone to
Multiple System Installations deluge or flooding.
If multiple OPECL systems are to be installed, ensure
that each receiver can view only the intended transmitter. Areas Prone to Subsidence and Settling
Avoid installation of the modules in areas where
System Mounting Elevation problems with subsidence, settling or thawing of
permafrost can occur or cause significant movement.
In all cases, the modules should be installed at the same
If such locations cannot be avoided, the foundations
elevation above grade to ensure that alignment capability
of the mounting structure should be engineered to
and foul weather performance are not compromised.
minimize any angular movements between the receiver
For detection of lighter than air vapors such as methane,
and transmitter.
installation of modules at approximately 2 meters above
grade minimizes typical beam block conditions due to
human activities, while enabling satisfactory detection Areas Prone to Earthquakes
capability. For detection of heavier than air vapors,
In the event of an earthquake, there is a chance that the
installation of detectors below the expected leakage
modules will become misaligned with respect to each
source is generally recommended unless nuisance
other. As long as the modules do not suffer from direct
beam blocks will occur at an unacceptable rate. In
mechanical impact damage during an earthquake,
this case, identification and analysis of application
they should remain undamaged by such events. After
specific conditions should be completed to determine
an earthquake, it is recommended that the system
the optimum installation elevation.
alignment be checked. Anti-vibration mounts are
unlikely to be of any benefit and are not recommended.
Sources of Heavy Contamination
Avoid locations where high levels of contaminants will Misalignment by Accidental Impact
persistently be blown onto the detector windows. Potential
Locations where there is a significant likelihood of
sources of heavy contamination include generator /
equipment, personnel or moving objects accidentally
turbine exhausts, flarestacks, drilling equipment, process
knocking the modules out of alignment should be
vents / chimneys, etc. If sources of heavy contamination
avoided where possible. If such locations cannot be
cannot be avoided, consider fitting extra shielding and/or
avoided, measures including improved mechanical
providing good access for routine cleaning.
protection and warning notices should be considered.
10.2 10 95-8556
Module Mounting Recommendations IMPORTANT
In all cases, consider whether additional bracing
OPECL modules must be affixed to a solid, non-vibrating
or support is needed to ensure the structural
structure capable of supporting a minimum of 100 lbs (46
integrity of the module installation. See Figure
kg), located within the systems rated separation distance.
4. Remember that accurate module alignment is
essential for proper performance of an open path
A building wall, a heavy steel I-beam, or nearly any type
gas detection system, and even a small amount
of masonry typically provides the most rigid mounting
of movement can have a detrimental effect on
surface available. However, avoid the use of wood
alignment. This is especially true for installations
structures or supports if the possibility of warping exists.
with significant module separation distances.
When using a vertical post, the post must be absolutely
stable and without vibration. Square stock pole is
recommended. Mounting height should not exceed 3
meters.
3 METERS
MAXIMUM HEIGHT
IMMOVABLE
STRUCTURE
1 METER
OR BELOW
FROST LINE
A2501
Figure 4Example of Bracing Added to Vertical Mounting Poles for Increased Robustness of OPECL Installation
10.2 11 95-8556
Module mounting options include: a float-type battery charging system is recommended.
A vertical post with a nominal outside diameter of 4.5 If an existing source of 24 Vdc power is being utilized,
(11.43 cm). Acceptable outside diameter range is 4.0 verify that system requirements are met.
to 5.0 inches. See Figure 5.
note
For flat surface mounting, refer to Figure 6. If disconnection of power is required, separate
disconnect capability must be provided.
Mounting Sequence
1. Attach the OPECL module to the pan-tilt mounting Wiring cable requirements
plate and tighten the OPECL mounting bolts to 20 Always use proper cabling type and diameter for input
lb.-ft. minimum. power as well as output signal wiring. 14 to 18 AWG
shielded stranded copper wire is recommended. For
2. Install the lower mounting bracket. EQP models, refer to the EQP system manual (95-8533)
for specific wiring requirements and recommendations.
3. Place the pan-tilt mounting plate on the lower bracket
and install the upper mounting bracket. Tighten the Always install a properly sized master power fuse or
mounting hardware to 20 lb.-ft. minimum. Tighten breaker on the system power circuit.
the alignment bolts/nuts hand tight only.
note
note The use of shielded cable in conduit or shielded
Anti-seize material (provided) must be applied armored cable is required for ATEX conformance.
to the U-bolt threads at the time of installation to In applications where the wiring is installed in
prevent galling. conduit, dedicated conduit is recommended. Avoid
low frequency, high voltage, and non-signaling
24 VDC power SUPPLY requirements conductors to prevent nuisance EMI problems.
OPECL MODULE
OPECL MODULE
B2305 A2306
*APPLY ANTI-SEIZE MATERIAL TO U-BOLT
THREADS TO PREVENT GALLING.
Figure 5OPECL Gas Detector Mounted to Vertical Post Figure 6OPECL Gas Detector Mounted to Flat Surface
10.2 12 95-8556
Power Wiring Size and Maximum Length optional relays
1. To ensure proper operation, OPECL power terminals Optional relay contacts are dry, meaning that the
(terminals 1 and 2 for Rx and Tx) and 4-20 mA installer must provide the voltage to the common
terminals (terminals 6 and 7 for Rx) must receive 18 terminal of the relay output.
Vdc minimum. 24 Vdc is recommended. Terminals
1 and 4, and terminals 2 and 5 on the OPECL Rx are AC voltage should not be switched directly using the
internally connected (see wiring diagrams). OPECL relays. The use of an external relay is required if
AC voltage must be switched by the OPECL relays.
2. Always determine voltage drops that will occur to
ensure that 24 Vdc is delivered to the OPECL. In order to change alarm relay settings from the factory
default settings, it is recommended to utilize a HART
3. Normally, nothing smaller than 18 AWG (1.0 mm2) Field Communicator. Contact the factory for further
is recommended by Det-Tronics for OPECL power assistance.
cabling.
NOTE
Wire size requirements are dependent upon power Refer to Alarm Relays in the Specifications section
supply voltage and wire length. of this manual for important information regarding
alarm relays.
The maximum distance between the OPECL detector
and its power supply is determined by the maximum The relay board must temporarily be removed from
allowable voltage drop for the power wiring loop. If the the OPECL termination compartment to connect the
voltage drop is exceeded, the device will not operate. relay output field wiring cables. After the relay wiring
To determine the maximum power loop voltage drop, is connected, re-install the relay board using the three
subtract the minimum operating voltage for the device captive screws. Refer to Figure 7.
(18 Vdc) from the minimum output voltage of the power
supply. Note: Relays are not available on EQP models.
24 18 = 6 Vdc
Figure 7OPECL Wiring Termination Compartment with Optional
Relay Board Removed
Maximum Voltage Drop = 6
Maximum Current = 0.35 A
Wire Resistance in Ohms/Foot = 0.006523
10.2 13 95-8556
wiring PROCEDURE
24 VDC 1
For systems using conduit, modules must be wired
+24 VDC 2
using a short piece of suitable flexible conduit to allow
optical alignment of the modules. Conductor insulation 3
should be stripped off with a bare conductor length
of 0.2 inch (5 mm) minimum and 0.7 inch (18 mm) 4
maximum). Open Path Eclipse screw terminal torque 5
range is 3.54.4 lb.-in. (0.40.5 Nm).
6
Cable shield, if used, should be properly terminated. If 7
not terminated, clip the shield wire off short and insulate
it within the detector housing to prevent the shield wire NO USER CONNECTION 8
from accidentally contacting the detector housing or
9
any other wire.
10
Figure 8 shows the wiring terminal strip located inside
11
the detectors integral junction box.
12
Figure 9 shows the wiring terminal configuration for
the OPECL transmitter. (The transmitter requires only 13
A2197
operating power.)
Figure 9Transmitter Wiring Terminal Identification
Figure 10 shows the wiring terminal configuration for the
OPECL receiver without relays.
note + 4-20 MA 6
For proper HART communication, it is required 4-20 MA 7
that an analog signal loop resistance of 250 to 500
ohms be present at the receiver analog output RS-485 B 8
terminals. See Figure 17 for benchtop test wiring. RS-485 A 9
For OPECL systems using HART communication,
the maximum wiring distance is 2,000 feet. 10
11
NO USER CONNECTION
12
13
A2196
A2084
10.2 14 95-8556
24 VDC 1 24 VDC
+
+24 VDC 2
CALIBRATE 3 24 VDC 1
CALIBRATE 3
+24 VDC 5
24 VDC 4
*
4 to 20 MA
+ 4-20 MA 6
+24 VDC 5
4-20 MA 7
+ 4-20 MA 6 +
RS-485 B 8 4-20 MA 7
RS-485 A 9 RS-485 B 8
RELAY POWER 10
WIRING TO OPTIONAL FAULT (ORANGE) 11
RELAY BOARD FAULT 11
NO USER CONNECTION LOW ALARM (WHITE) 12 NO USER CONNECTION
LOW ALARM 12
HIGH ALARM (YELLOW) 13
HIGH ALARM 13
B2050
NO
FAULT Figure 12Detector Wired for Non-Isolated 4 to 20 ma Current
RELAY
NC Output (Sinking)
NO
RELAY BOARD TERMINALS HIGH ALARM
(OPTIONAL) RELAY
NC
C
24 VDC
NO +
LOW ALARM
RELAY
NC
24 VDC 1
C
B2054
+24 VDC 2
CALIBRATE 3
Figure 11Wiring Terminal Identification for OPECL Receiver
with Relays 24 VDC 4 4 to 20 MA *
+24 VDC 5
+ 4-20 MA 6 +
4-20 MA 7
RS-485 B 8
RS-485 A 9
RELAY POWER 10
FAULT 11
NO USER CONNECTION
LOW ALARM 12
HIGH ALARM 13
B2051
10.2 15 95-8556
24 VDC 24 VDC
+ +
24 VDC 1 24 VDC 1
CALIBRATE 3 CALIBRATE 3
4 to 20 MA
24 VDC 4 24 VDC
24 VDC 4
+ 4-20 MA 6 + 4-20 MA 6
4-20 MA 7
4 to 20 MA *
4-20 MA 7 *
RS-485 B 8 RS-485 B 8
+
RS-485 A 9 RS-485 A 9
+
RELAY POWER 10 RELAY POWER 10
24 VDC
FAULT 11 FAULT 11
NO USER CONNECTION
NO USER CONNECTION
LOW ALARM 12 LOW ALARM 12
*TOTAL LOOP RESISTANCE = 250 OHMS MINIMUM, 600 OHMS MAXIMUM. *TOTAL LOOP RESISTANCE = 250 OHMS MINIMUM, 600 OHMS MAXIMUM.
Figure 14Detector Wired for Isolated 4 to 20 ma Current Output Figure 15Detector Wired for Isolated 4 to 20 ma Current Output
(Sinking) (Sourcing)
24 VDC 1 24 VDC 1
24 VDC
+24 VDC 2 +24 VDC 2 +
24 VDC 4 24 VDC 4
COM 1 A 7 4-20 MA 7
COM 1 B 8 RS-485 B 8
COM 2 B 11 NO USER
FAULT 11
CONNECTION
COM 2 SHIELD 12 LOW ALARM 12
Figure 16Wiring Terminal Identification Figure 17Wiring the Model OPECL for Benchtop Testing/
for Eagle Quantum Premier OPECL Programming Using HART Protocol
10.2 16 95-8556
startup BASIC ALIGNMENT PROCEDURE
10.2 17 95-8556
U-BOLT NUTS (2)*
HORIZONTAL ADJUSTMENT
BOLTS WITH LOCKING NUTS (2)
U-BOLT NUTS (2)*
6. Install the Telescope Alignment Tool onto 7. Slowly adjust the receiver module up/down as
the receiver module by inserting the captive required using the vertical adjustment bolts until
thumbscrews into the threaded holes on the the telescope cross hairs are centered as close
faceplate. See Figure 19. Ensure that the telescope as possible to dead center on the window of the
is properly attached, that the eyepiece is accessible, transmitter module. Tighten the vertical alignment
and that the thumbscrews are completely tightened. locking nuts so that no movement will occur.
D2303
Figure 19 OPECL with Telescope Alignment Tool Installed (Transmitter Module Shown)
10.2 18 95-8556
STEP 1: CENTER CROSS HAIRS ON TARGET USING
ADJUSTMENT BOLTS ON MOUNTING PLATE
(POSITION A).
8. Slowly adjust the receiver module left/right as 12. Remove the Telescopic Alignment Tool and re-install
required using the horizontal adjustment bolts until the brow.
the telescope cross hairs are centered as close as
possible to dead center on the transmitter module 13. Bypass all external gas alarm devices that are
window. Tighten the horizontal adjustment bolts and connected to the receiver outputs, and then apply
locking nuts so that no movement will occur. 24 Vdc power to the modules.
9. Rotate the telescope alignment tool by 180 and 14. Upon completion of warm-up mode (approximately
verify that the cross hairs are in the same position. 2 minutes or less), the receiver may display either
If the cross hairs are not in the same position, the a green LED (normal mode) or a red LED (alarm
telescope alignment screws must be adjusted as mode). An alarm condition is not abnormal and will
follows: be cleared by performing a zero calibration.
A. Adjust the telescope alignment screws until the
cross hairs are midway between the original 15. For installations with module separation distances
position (center of transmitter window) and the between 5 and 30 meters, install the appropriate
current position (after the scope was rotated aperture as described in the "Aperture Kit for Short
180). See Figure 20. Range Applications" section.
B. Return the scope to its original position (rotate 16. Perform a zero calibration. (Refer to Zero
180) and repeat steps 7 through 9 until correct Calibration in the Calibration section of this
alignment is achieved. manual.) Any faults or alarms that may be present
as a result of the alignment process will be cleared.
note
No further adjustments are required when the 17. When Basic Alignment and Zero Calibration have
cross hairs are centered on the window with the been successfully completed, a green LED should
scope in both 180 positions. be displayed on the Rx module and the analog
signal output level should be 4.0 milliamperes.
10. Repeat the alignment procedure for the transmitter
module (steps 6 to 9).
10.2 19 95-8556
Aperture Kit for Short Range Applications Recommendations for using the HART Field
Communicator
The Short Range Aperture Kit enables successful
application of the OPECL gas detector at distances Ensure that the HART communicator is certified for
of approximately 5 to 30 meters. The kit is available use in classified areas.
in Delrin plastic (included with OPECL receivers) or
optional stainless steel. The HART communication device must include
the OPECL device descriptor (DD) software menu.
Two aperture sizes are provided: The use of HART communication devices without
the proper DDs may establish generic mode HART
The 0.6" diameter (15 mm dia.) aperture is used for system communication, but will not enable proper operation
separation distances of approximately 5 to 15 meters. with OPECL. Refer to the HART Appendix for
The 1.2" diameter (30 mm dia.) aperture is used for system additional information.
separation distances of approximately 15 to 30 meters. A minimum level of understanding with regard to the
operation and navigation of the HART communicator
note is required. Please refer to the appropriate HART
System separation distances greater than 30 communicator instruction manual for basic operating
meters should not require apertures. instructions if required. Additional information on the
use of the HART communicator is provided within the
HART Appendix in this document.
Procedure for System Commissioning Using the
Apertures For proper HART communication to occur, it is
required that a 250-500 ohm resistive load be present
1. Align the OPECL system using the Basic Alignment in the OPECL analog 4-20 mA signal loop output.
procedure. At the completion of this alignment, the
output signal at the Receiver will indicate a fault NOTE
condition as a result of signal saturation (1.0 mA in During alignment adjustment, the HART field
OPGD-Rx mode or 0.2 / 0.4 mA in PIR9400 mode). communicator may occasionally display a
For an EQP system, a saturation fault is indicated on message stating Non-zero status codes found.
the EQP controller display and also on the S3 point Ignore the next 50 occurrences? When this
display screen. occurs, enter Yes, and continue the Fine Alignment
procedure.
2. Attach the aperture to the front of the OPECL
Transmitter module using the captive screws provided.
Fine Alignment Adjustment Using Partial
note Beam Block Tool
The plastic model uses a one-piece aperture The Partial Beam Block Tool allows fine tuning of
without holder. The stainless steel model uses a Model OPECL alignment and should be used when
holder with interchangeable aperture inserts. the application requires maximum signal strength and
low tolerance to potential output drift. Fine tuning the
Use the larger aperture for separation distances OPECL alignment in this manner ensures that it will
from 15 to 30 meters and the smaller aperture for operate with maximum immunity from zero drift and
distances from 5 to 15 meters. For distances around false readings.
15 meters, start with the larger aperture. An output
signal of 2.4 mA or higher indicates proper detector 1. Perform the basic alignment procedure using the
operation (no fault condition). If the signal is still Telescope Alignment Tool.
saturated (1.0 mA in OPGD-Rx mode or 0.2 / 0.4 mA
in PIR9400 mode), the smaller aperture is required. 2. Perform a zero calibration on the OPECL receiver.
(Zero calibration should be repeated after each
NOTE alignment adjustment.)
System separation distances of 5 to 15 meters may
require the use of both apertures. Place the 0.6" 3. Remove the brow from the front of the receiver.
diameter aperture on the transmitter and the 1.2"
diameter aperture on the receiver if a saturated 4. Connect the handheld HART communicator
signal exists. to the OPECL receiver modules onboard HART
communication port.
3. Perform a zero calibration. After performing the zero
calibration, the Receiver module should display a normal
condition (green LED) and a steady 4 mA output.
10.2 20 95-8556
Note BEAM BLOCK TOP
If a HART handheld communicator is not available,
the alignment procedure can be performed in
a limited way by monitoring the 4-20 mA output.
(This method is only partially effective due to the
deadband built into the 4-20 mA output.) If the
partial beam blocks result in output deflection
greater than 4.00 mA +/- 0.1, alignment should be If this block causes Absorption to increase
adjusted to eliminate the deflection. The OPECLs > 5%, move receiver down.
status LED can also be observed. The LED should
remain green with the beam block in any position.
7. From the Status Menu, select the Sensor Information If this block causes Absorption to increase
Menu (selection #3). > 5%, move receiver left.
(Absorption and Ratio are the readings of interest If this block causes Absorption to increase
while performing the alignment procedure.) > 5%, move receiver up.
NOTE
Make alignment adjustments in very small
increments. After an adjustment is made, wait for
at least 10 seconds for the output level to stabilize.
Continue making adjustments, if necessary, until BEAM BLOCK LEFT
the correct level is achieved.
10.2 21 95-8556
C. If adjustments to the receiver were necessary, Gain Level Check (Optional)
perform a zero calibration and then repeat the It is necessary to complete the alignment procedure
sequence of partial beam blocks. Repeat the before checking the gain level. A handheld HART
adjust, zero calibration, and recheck process until communication device (or S3 Software for an EQP
no adjustments to the receiver are necessary, and system) is required to check the gain.
the partial beam block has little or no effect on the
receiver under test.
Procedure
10. With the beam block tool removed, the Ratio reading 1. Connect the handheld HART communicator to the
must be between 0.65 and 0.95. If a reading over receiver modules onboard HART communication
1.0 is indicated, check to make sure that no other port.
transmitters, IR sources, or potential reflections are
within view of the receiver. It is possible for multiple 2. Turn on the HART communicator and check
transmitters to be viewed by a single receiver. for OPECL device recognition. When HART
Although each receiver is electronically synchronized communication is established, the OPGD Rx Root
to its transmitter, zero drift and/or false gas readings menu will be displayed on the communicator display.
are possible if the rogue IR source continues in the
event of a beam block on the primary transmitter. 3. From the Root menu, select the Status Menu
If this situation occurs, a ratio of over 1.0 will be (selection #2).
realized. Det-Tronics recommends eliminating any
condition that causes a receiver to display a ratio of 4. From the Status Menu, select the Sensor Information
over 1.0. Menu (selection #3).
11. When correct alignment is achieved, tighten all 5. The Sensor Information Menu will display the
mounting bolts to 20 lb-ft minimum using care not following screen.
to disturb the alignment. The telescope can be
used during this step to give a visual indication to
1) Active XXX
judge the effects of the tightening process on the 2) Reference XXX
alignment. Check the alignment one final time using 3) Ratio XXX
the beam block tool to verify that the alignment did 4) Gas Gain X Gas Gain number
not change as a result of tightening. If necessary, 5) Absorption XXX
fine tune the alignment.
12. Upon completion, the OPECL receiver should 6. Observe the Gas Gain level indicated on the Sensor
produce a 4 mA output signal and a green LED Information Menu screen.
indication. If not, ensure that the device has been
zero calibrated. 7. Table 4 can be used as a guideline for new
installations to assess Gas Gain level with proper
13. Proper operation can be confirmed by bypassing alignment.
all system alarms, then placing an optical test film
(sold separately) into the light beam and checking Table 4 Expected Gas Gain Settings for OPECL
for the appropriate signal output level on the HART
field communicator process menu screen. Test Distance (m) Gain Setting
Film p/n 007902-002 should produce an output of
5 1-3*
0.5 to 1.1 LFLMeters. Test Film p/n 007902-003
should produce an output of 1.5 to 2.1 LFLMeters. 20 1*
Alarm conditions, if present, should clear when the
40 1-2
test film is removed from the beam.
60 2
14. Confirm proper operation by completely blocking
80 2-3
the light beam with a solid object such as a piece of
cardboard until a beam block fault is generated. 100 3
120 3-4
15. Replace the HART port cover and the brow.
*Use the Aperture Kit to get desired gain settings.
16. Restore all system alarms to normal operation.
10.2 22 95-8556
Calibration Digital Communication Calibration
MODBUS communication may be utilized to initiate
CALIBRATION OVERVIEW OPECL calibration (consult factory).
Although routine calibration of the OPECL is normally
not required, the device supports non-intrusive field zero Detailed Calibration Procedure using
calibration capability. Span calibration is not required. Magnetic Switch
Zero Calibration
Zero Calibration
1. Apply magnet for 2 seconds minimum to initiate
Zero Calibration is a one-step process consisting of clean
calibration. (Hold the calibration magnet against the
air (zero) condition adjustment only, which is performed
side of the receiver at the location shown in Figure 2.)
automatically by the device. This procedure adjusts
the "clean air" signal output only, and is normally used if A. The onboard LED turns to steady red.
the 4 milliampere signal level has drifted. The cause of B. The current output decreases to 1 mA in
drift is typically due to the presence of background gas OPGDRx mode or 2.2 mA in PIR9400 mode.
during calibration. Ensure that the optical path is clear
of hydrocarbons prior to calibration initiation to ensure 2. When zero calibration is complete:
an accurate zero (clean air) condition. A. The onboard LED changes from steady red to
steady green.
important Calibration Notes B. Calibration is complete and current output returns
to 4 mA.
note
Ensure that the detector has been operating for at
When calibrating an EQP model, calibration status is
least two hours before calibrating.
indicated on the EQP Point Display screen.
Note
Always ensure that the OPECL optics are totally
free of all hydrocarbons before initiating calibration. Maintenance
Warning
CALIBRATION INITIATION Do not open cover when an explosive gas
atmosphere may be present.
Calibration may be initiated by any of the following
means:
The onboard magnetic calibration switch note
Refer to the Model OPECL Safety Manual
Digital communication via MODBUS communication (number 95-8665) for specific requirements
(consult factory for details) and recommendations applicable to the proper
Remote calibration line. installation, operation, and maintenance of all
EQP Point Display SILCertified OPECL IR gas detectors.
Routine Inspection
Calibration Using Magnetic Switch
The OPECL detector should be inspected periodically to
The Open Path Eclipse receiver provides an onboard ensure that external obstructions such as plastic bags,
magnetic calibration/reset switch for non-intrusive mud, snow, or other materials do not block the path and
calibration capability. The magnetic switch is actuated thereby impair the performance of the device.
by holding a calibration magnet at the specified location
on the device bulkhead. See Figure 2 for switch
location. An onboard tri-color LED provides status
indication during calibration.
10.2 23 95-8556
Optics Cleaning Troubleshooting
Cleaning of the OPECL optical surfaces is normally
A Fault status is indicated by a yellow LED and also by
required only if an optical fault is indicated.
the 4 to 20 mA output. Refer to Table 5 for assistance
in correcting malfunctions with the Open Path Eclipse
Thoroughly douse both window surfaces using a liberal
Detector.
amount of isopropyl alcohol to clear away contaminant
particles. Repeat the alcohol flush to remove any
remaining contaminants.
WARNING
Bypass/Inhibit: Volatile organic compounds in
cleaning solutions could cause false alarms.
Low 24 volts 24 vdc operating voltage is out of range. Verify proper wiring to the detector and
correct voltage output from the power source. Power supply faults are self-clearing
when the condition is corrected. If the fault does not clear, consult the factory.
Dirty Optics Perform cleaning procedure, then recalibrate as required. (Refer to Maintenance for
details.)
Calibration Fault If the calibration process is allowed to time-out, the fault is set and can only be reset
with a successful calibration.
Negative Signal Output This fault is indicated when the signal output drops below 0.5 LFL-M. Normally
detection capability is not compromised in this condition. The device was probably
zero calibrated with background gas present. If the condition persists, purge with clean
air and repeat the zero calibration.
Calibration line active at start-up The only way to clear this fault is to correct the wiring and reapply power. Be sure that
the calibration line is not shorted and that the calibration switch is open. If the fault
does not clear, consult the factory.
EE Error If power is interrupted while the unit is updating its internal data logs, an EE Error may
occur. Cycling power will correct this fault.
10.2 24 95-8556
replacing OPecl transmitter/ Module Replacement Procedure
receiver electronics module Tools Required:
4 mm hex wrench
Warning Torque wrench capable of accurately measuring 40
Do not open when an explosive gas atmosphere inch-pounds
may be present.
1. Bypass system alarms as needed, then remove 24
Caution
Vdc power from the OPECL detector.
Only Det-Tronics authorized personnel are allowed
to perform this repair.
2. Remove the four stainless steel flange bolts using
a 4 mm hex wrench. See Figure 22. Take care to
CAUTION
properly support the module as the last flange bolt is
Replacement of the OPECL transmitter or receiver
removed.
module requires disassembly of the device
housing. Remove power to the device before
3. Carefully remove the old module by extracting it
disassembly.
straight out from the bulkhead.
CAUTION
caution
The Model OPECL detector contains
Handle the new module carefully to prevent
semiconductor devices that are sensitive to
damage. Since both the lens and circuit board
electrostatic discharge (ESD). Use normal
protrude beyond the edge of the housing, the
precautions for handling ESD sensitive devices.
module should only be set down on its side to
Handle the device by the housing, taking care not
prevent damage to the lens or circuit board.
to touch electronic components or terminals.
4. Ensure that the o-ring on the replacement module
is present, undamaged, and correctly seated in the
groove on the housing. See Figure 23. This o-ring
is required to maintain the watertight integrity of the
OPECL housing.
INCORRECT
A2498
A2499
10.2 25 95-8556
BULKHEAD transmitter, not on the receiver). If the separation
OPECL MODULE distance is between 5 and 30 meters and signal
saturation is indicated after completion of the
Basic Alignment procedure, an aperture will
be required (even if no aperture was originally
installed). Refer to the "Aperture Kit for Short
Range Applications" section in this manual for
complete information regarding apertures.
A2500
ALIGNMENT
PIN (2)
9. Perform a zero calibration of the detector.
TO INSTALL REPLACEMENT MODULE, LINE UP
PINS (2) WITH HOLES IN BULKHEAD AND
INSERT MODULE FULLY INTO BULKHEAD. 10. Upon completion of zero calibration, verify proper
operation by performing an optical test film
Figure 24OPECL Module Removed from Bulkhead
test and also a beam block test as previously
described in this manual.
note
NOTE Replacement receiver modules are furnished from
If the replacement module is a receiver and is the factory with default configuration settings. If
used in an EQP system, it will have LON address the OPECL system has had any configuration
switches that must be set. Set the switches on changes in the field, the new receiver will require
the new module the same as the switches on changes to configuration parameters using a
the module being replaced before installing the HART communicator or a FlexVu UD10 display unit
module into the bulkhead. (use S3 software for EQP models).
5. Line up the two pins on the replacement module with 11. Restore system alarms (remove bypass).
the two holes in the bulkhead and insert the module
straight into the bulkhead. See Figure 24.
DEVICE REPAIR AND RETURN
6. Insert and tighten the four flange bolts in an
opposing consecutive order in two stages first The Open Path Eclipse IR Hydrocarbon Gas Detector
partially tighten all four bolts equally, and then is not designed to be repaired in the field. If a problem
fully tighten each bolt in an opposing order to 40 should develop, first carefully check for proper wiring,
inchpounds (4.5 Nm) of torque. Bolts are M6 per programming and calibration. If it is determined that the
ISO 965 with M5 head, SST with a yield stress of 448 problem is caused by an electronic failure, the device
N/mm2 (65.00 PSI) minimum. must be returned to the factory for repair.
10.2 26 95-8556
ORDERING INFORMATION SPARE PARTS
Part Number Description
When ordering, please refer to the OPECL Model Matrix:
102740-002 Calibration Magnet
alignment equipment
005003-001 Silicone Free Grease
Part Number Description
107427-040 O-Ring, 3.75 i.d., for wiring
009104-001 OPECL Alignment Telescope
compartment cover
Consists of a 32mm sighting device
with 3-9x zoom magnifier that is factory 107427-053 O-Ring, 3.25 i.d., for front flange
assembled with precision holder and (internal)
reflective mirror, and partial beam
007167-001 M6 Flange Bolt
block tool.
009762-002 Partial Beam Block Tool 009186-001 Spare Pan-Tilt Mounting Kit (for one
(included with 009104-001) OPECL module only)
011405-201 Spare electronics/lamp module for
accessories OPECL transmitter, SIL
10.2 27 95-8556
OPECL MODEL MATRIX
MODEL DESCRIPTION
OPECL Open Path Eclipse Infrared Gas Detector
TYPE MATERIAL
S Stainless Steel
TYPE CONDUIT ENTRY THREAD TYPE
2M 2 Port, Metric M25
2N 2 Port, 3/4" NPT
TYPE OUTPUT
00 None (Transmitter only)
14 Eagle Quantum Premier (EQP) (Receiver or Kit)
18 4-20 mA, RS485, HART (Receiver or Kit)
25 4-20 mA, RS485, HART w/Optional Relay Board (Receiver or Kit) Ex d only
TYPE APPROVALS
W FM/CSA/ATEX/CE/IECEx
T SIL/FM/CSA/ATEX/CE/IECEx
B INMETRO (Brazil)
R VNIIFTRI (Russia)
TYPE CLASSIFICATION
1 Division/Zone Ex d e ([ib] receiver only)
2 Division/Zone Ex d ([ib] receiver only)
TYPE CONFIGURATION
S Transmitter/Receiver/Mounting Hardware
T Transmitter Module Only
R Receiver Module Only
10.2 28 95-8556
Appendix A
FM Approval Description
Approval
Open Path Eclipse Infrared Hydrocarbon Gas Detector, Model OPECL Series.
Class I, Div. 1, Groups B, C & D (T5) with intrinsically safe output for HART communication in accordance with
control drawing 007722-001 (see Appendix G).
Class I, Div. 2, Groups A, B, C & D (T4).
NEMA/Type 4X.
Conduit seal not required.
Performance verified in accordance with FM 6325, ANSI/ISA 12.13.04.
Accuracy
5% of full scale gas concentration or 10% of applied gas concentration, whichever is greater.
note
In order to remain within 5% of full scale gas concentration or 10% of applied gas concentration, the
maximum misalignment is 0.05 degrees.
Response Time
T90: <5 seconds (5.0 LFL-meters applied).
Note: Add 2 seconds to response time for EQP compatible models.
NOTES
Approval of the Model OPECL does not include or imply approval of the apparatus to which the detector may
be connected and which processes the electronic signal for eventual end use. In order to maintain an approved
system, the apparatus to which the detector is connected must also be approved.
This Approval does not include or imply Approval of the communications protocol or functions provided by the
software of this instrument or the communications apparatus or software connected to this instrument.
The following items, functions and options describe the CSA approval.
Approval
Open Path Eclipse Infrared Hydrocarbon Gas Detector, Model OPECL Series.
Class I, Div. 1, Groups B, C & D (T5) with intrinsically safe output for HART communication in accordance with
control drawing 007722-001 (see Appendix G).
Class I, Div. 2, Groups A, B, C & D (T4).
Type 4X.
Conduit seal not required.
NOTES
Approval of the Model OPECL does not include or imply approval of the apparatus to which the detector may
be connected and which processes the electronic signal for eventual end use. In order to maintain an approved
system, the apparatus to which the detector is connected must also be approved.
This Approval does not include or imply Approval of the communications protocol or functions provided by the
software of this instrument or the communications apparatus or software connected to this instrument.
The following items, functions and options describe the ATEX approval.
Approval
Open Path Eclipse Infrared Hydrocarbon Gas Detector, Model OPECL Series.
Receiver Transmitter
0539FM
APPROVED
II 2 G
0539FM
II 2 G
APPROVED
WARNING
Always ensure that the detector/junction box hazardous (classified) location ratings are applicable for the
intended use.
For ambient temperatures below 10C, use field wiring suitable for the expected conditions, and for ambient
temperatures above +60C, use field wiring suitable for 20C above the maximum expected conditions.
ATEX Standards:
EN 50241-1/A1: 2004
EN 50241-2: 1999
EN 60079-29-4: 2010
Performance Approved for Methane
EN 60079-0: 2009
EN 60079-1: 2007
EN 60079-7: 2007
EN 60079-11: 2007
EN 60529:1991+A1:2000
EN 50270: 2006
EN 50271: 2010
response time
4-20 mA Model
T50: 1.2 seconds (2.5 LFL-meters applied)
T90: 2.5 seconds (2.5 LFL-meters applied).
EQP Model
T90: 5.3 seconds* (2.5 LFL-meters applied).
* For EQP model only, average of three consecutive trials, with the minimum and maximum response times no
greater than 2 seconds from the average indicated response time.
alignment
Misalignment will cause the manufacturer stated accuracy limits to increase, but remain within the limits of EN
50241-1, -2 and EN 60079-29-4.
The following items, functions and options describe the IECEx approval.
Approval
Open Path Eclipse Infrared Hydrocarbon Gas Detector, Model OPECL Series.
Receiver Transmitter
IECEx ULD 05.0001X IECEx ULD 05.0001X
Ex d [ib] IIC T5 Gb Ex d IIC T5 Gb
T5 (Tamb 55C to +60C) T5 (Tamb 55C to +60C)
--OR-- --OR--
Ex d e [ib] IIC T5 Gb. Ex d e IIC T5 Gb.
T5 (Tamb 50C to +60C) T5 (Tamb 50C to +60C)
IP66/IP67. IP66/IP67.
HART Communication Port:
Uo = 4.0V Co = 20F
Io = 100mA Lo = 500H
Um = 250V
IEC Standards:
IEC 60079-0: 2007
IEC 60079-1: 2007
IEC 60079-7: 2006
IEC 60079-11: 2006
IEC 60529, 2.1 ed.+Corr.1:2003+2:2007
IEC 61000-4-3: 2006
When connecting to a circuit using up to 1% of Co or Lo, then the C or L is limited to the Co and Lo listed above. If
either the C or L is above 1% of Co or Lo, then C or L are each limited to 50% of the Co or Lo listed above.
Um is restricted to 250 V, prospective short circuit current < 1500 A.
The Infrared Hydrocarbon Gas Detectors shall be powered from a SELV isolating transformer and the fuse for Isc
shall be of the type complying with IEC60127.
WARNING
Always ensure that the detector/junction box hazardous (classified) location ratings are applicable for the
intended use.
For ambient temperatures below 10C, use field wiring suitable for the expected conditions, and for ambient
temperatures above +60C, use field wiring suitable for 20C above the maximum expected conditions.
response time
4-20 mA Model
T50: 1.2 seconds (2.5 LFL-meters applied)
T90: 2.5 seconds (2.5 LFL-meters applied).
EQP Model
T90: 5.3 seconds* (2.5 LFL-meters applied).
* For EQP model only, average of three consecutive trials, with the minimum and maximum response times no
greater than 2 seconds from the average indicated response time.
alignment
Misalignment will cause the manufacturer stated accuracy limits to increase, but remain within the limits of
IEC 60079-29-4.
The following items, functions and options describe various other approvals applicable to the Model OPECL.
SIL Approval
IEC 61508
Certified SIL 2 Capable.
Applies to specific models refer to the Safety Reference Manual (form 95-8665) for details.
INMetro (Brazil)
Certificate No. UL-BR 12.0128X
VNIIFTRI (Russia)
GOST R Certificate of Compliance
1Exd[ib]IICT5 X
OR
2Exde[ib]IICT5 X
HART Communication
Digital communication with the Open Path Eclipse is necessary to monitor internal status and to modify the factory
settings. This appendix provides guidance on establishing HART communication, and describes the communi-
cation menu structure when using the Open Path Eclipse with the HART Handheld Communicator.
Note
The HART protocol incorporates a concept called the "Device Description Language" that enables all sup-
pliers of HART instruments to define and document their products in a single consistent format. This format
is readable by handheld communicators, PC's and other process interface devices that support DDL. DDL
enables full interoperability of devices, regardless of manufacturer, allowing full functionality from any HART
device.
In the event that your Communicator does not establish communications with the Open Path Eclipse, you may
need to ensure that the appropriate DDLs for the OPECL are included within your Communicator. To review the
device descriptions programmed into your HART Communicator:
2. From the Offline menu, press New Configurations to access the list of device descriptions programmed into
your HART Communicator. The Manufacturer menu displays a list of each manufacturer with device descrip-
tions currently installed in your Communicators Memory Module. The standard 12 MB Memory Module is
recommended, as it allows for more device descriptions.
3. Select a manufacturer, and the Model menu displays, containing a list of currently installed device models
provided by the selected manufacturer.
4. Review the different manufacturers and models to determine the installed HART-compatible devices in your
Communicator.
If you cannot find the OPECL device on your Communicator, the device revision you are looking for is not pro-
grammed into the Memory Module. In this instance, you are limited to what is available using the generic interface
built into your HART Communicator.
NOTE
If a device is found, the HART Communicator displays the Online menu. If no device is found, the
Communicator displays the Main menu. If no device is found, check the connections, verify the presence of
a minimum of 250 ohms load resistance in series in the loop, and retry by selecting Online. To poll multiple
devices in the loop, refer to the HART Communicator manual.
Coefficient Menu
Sensor Info Menu
1) Coefficient A
1) Active 2) Coefficient B
2) Reference 3) Coefficient C
3) Ratio 4) Coefficient D
4) Gas Gain 5) Coefficient E
5) Absorption
6) Span Factor
7) Sensor Temp
8) Coefficient Menu
OPGD Option Menu
1) PV.Digital Units
Fault Status Menu 2) Blocked Optics Timer
3) Heater Control
1) Current Op Mode 1 4) Distance
2) Current Op Mode 2 5) AZT Level*
2) Fault 1 6) AZT Zero Drift Limit*
3) Fault 2 7) AZT Con Suppress*
4) Status 1 8) Assembly Number
5) Status 2
On EQP models, the HART communicator must be connected to the I.S. communication port.
Online Menu
When HART communication is established with the receiver, the first menu displayed is the OPGD RX Root
menu:
To select any of the 5 menu options shown, highlight the desired option using the up/down arrow key, and then
t Menu press the right arrow key.
Control drawing
An important difference in EQP applications is that LON network cabling will be routed both in and out from the the
EQP OPECL receiver enclosure, so this requirement should be anticipated and planned for during installation.
Note that only the receiver is connected to the LON network. The transmitter is not connected to the LON and
requires wiring for operating power only.
Note: *Use the same type of cable in each wiring segment between
network extenders.
**Maximum wire lengths represent the linear wire distance of
LON communications wiring between network extenders.
The maximum wire lengths given in Table H-1 are based upon
the cables physical and electrical characteristics.
Important
Det-Tronics recommends the use of shielded cable (required by ATEX) to prevent external electromagnetic
interference from affecting field devices.
Important
For best fault isolation performance, the maximum LON wiring length should not exceed 1600 feet (500
meters).
Important
Be sure that selected cable meets all job specifications. The use of other cable types can degrade system
operation. If necessary, consult factory for further suggested cable types.
Multi-Colored LED
Operation of the status indicating LED is identical to all other OPECL versions.
Analog Output
A 4-20 mA analog current output is not available with EQP OPECL.
RS-485 Communication
RS-485 communication is not available with EQP OPECL.
Calibration Routine
The calibration procedure for the EQP OPECL is identical to all other OPECL versions.
NOTE
For complete information regarding installation, configuration or operation of the Eagle Quantum Premier
system, refer to form 95-8533 (Eagle Quantum Premier hardware manual).
Calibration and beam block faults are automatically latched and displayed on the EQP controller. The trouble
relay is activated.
Gas Level 1 2 3
Device Fault 1 2 3
Addresses 1 to 4 are reserved for the EQP controller. Valid addresses for field devices including OPECL gas
detectors are from 5 to 250.
IMPORTANT
If the address is set to zero or an address above 250, the system will ignore the switch setting and the
device.
The LON address is programmed by setting rocker switches on an 8 switch DIP Switch located within the
OPECL housing. The address number is binary encoded with each switch having a specific binary value with
switch 1 being the LSB (Least Significant Bit). (See Figure H-1.) The devices LON address is equal to the added
value of all closed rocker switches. All Open switches are ignored.
Example: for node No. 5, close rocker switches 1 and 3 (binary values 1 + 4); for node No. 25, close rocker
switches 1, 4 and 5 (binary values 1 + 8 + 16).
NOTE
For convenience in setting LON address switches, a Rocker Switch Table is included in the EQP System
manual (form 95-8533).
ON
1 2 3 4 5 6 7 8
BINARY
VALUE 1 2 4 8 16 32 64 128
After setting address switches, record the address number and device type on the Address Identification Chart
(form 95-8487). Post the chart in a convenient location near the Controller for future reference.
IMPORTANT
The OPECL sets the LON address only when power is applied to the device. Therefore, it is important to set
the switches before applying power. If an address is ever changed, system power must be cycled before
the new address will take effect.
WARNING
Disassembly of the OPECL housing and removal of the electronics module from the bulkhead is required
to gain access to the network address switches. Power should be removed from the detector before
disassembly. If disassembly is performed in a hazardous areas, the area must be de-classified before
starting disassembly.
WARNING
Disassembly of the OPECL detector should only be performed with proper electrostatic discharge grounding
protection. A controlled lab or shop setting is recommended for device programming.
The OPECL detector contains semiconductor devices that are sensitive to electrostatic discharge (ESD).
Damage caused by electrostatic discharge can be virtually eliminated if the equipment is handled only in
a static safeguarded work area and protective measures against static electricity discharge are employed
during the disassembly process. Since a static safeguarded work area is usually impractical in most field
installations, handle the device by the housing, taking care not to touch electronic components or terminals.
Use a wrist grounding strap or similar method at all times to control accidental ESD when disassembling,
programming, or reassembling the OPECL gas detector.
ELECTRONIC MODULE
REMOVED FROM HOUSING
ADDRESS SWITCHES
A2192
Removal of four stainless steel flange bolts and the front electronic module of the OPECL receiver from the
bulkhead is required in order to gain access to the network address DIP switch. Tools required for this procedure
include a 4mm hex wrench and a torque wrench capable of accurately measuring 40 inch-pounds.
2. Remove the four stainless steel flange bolts using a 4mm hex wrench. Take care to properly support the
electronic module as the last flange bolt is removed.
3. Carefully remove the electronic module by extracting it straight out from the bulkhead.
Note
Take care to properly align the modules electrical connector with the bulkhead connector before attempting
to fully insert the module. Failure to do so may result in damage to the module and/or bulkhead.
7. Insert and tighten the four flange bolts in an opposing consecutive order in two stages first partially tighten
all four bolts equally, and then fully tighten each bolt in an opposing order to 40 inch-pounds of torque.
8. Apply power after all network addresses have been programmed and all field enclosures are properly
installed.
TYPICAL APPLICATIONS
Figure H-3 is a simplified drawing of a typical EQP system. This system includes an EQP Controller and various
LON field devices.
52 B 49 5 B 2 11 B 3 6 B 10 14 B 4 9 B 6 9 B 6
53 A 50 4 A 1 10 A 2 5 A 9 15 A 5 8 A 5 8 A 5
P6
BUS BAR P3
C 45
C 1 N CIRCUIT 1 + 1
FAULT NO 46 P4 P3
B 2 CIRCUIT 1 2
NC 47 A + SUPPLY A AC LINE
P9 P8 3 CIRCUIT 2 + 3
B IN/OUT+ B +
CH 1
CH 5
GND 5 57 GND GND 54 24 VDC 4 H CIRCUIT 2 4
C COMMON C SUPPLY
RXD 2 58 RxD B 55
TXD 3 59 TxD A 56 A + SUPPLY A
DB-9 H N
H-6
P2 P3
CONNECTION B IN/OUT+ B AC LINE
CH 6
CH 2
TO COM PORT 5 1+ 5+ 13
OF PC
6 1 5 14 C COMMON C
+
7 2+ 6+ 15
A + SUPPLY A 24 VDC
8 2 6 16 BATTERY
B IN/OUT+ B
CH 3
CH 7
9 3+ 7+ 17 EQP2401NE EQP2200DCU PIRECL/OPECL EQP2500ARM EQP2500SAM
10 3 7 18 C COMMON C
4 SHIELD 9 6 SHIELD 3
DIGITAL INPUTS
11 4+ 8+ 19
A + SUPPLY A
12 4 8 20 6 24 VDC 7 13 24 VDC 14 4 24 VDC 1 13 24 VDC 14 13 24 VDC 14
B IN/OUT+ B
CH 4
CH 8
P4 P5 5 24 VDC + 8 11 24 VDC + 12 5 24 VDC + 2 11 24 VDC + 12 11 24 VDC + 12
21 C C 33 C COMMON C
COM2 COM1 COM2 COM1 COM2 COM1 COM2 COM1 COM2 COM1
22 NO NO 34
RELAY 5
SHIELD SHIELD SHIELD SHIELD SHIELD
RELAY 1
12 1 7 8 12 9 7 8 7 8
23 NC NC 35
24 C C 36 11 B 3 6 B 10 11 B 8 6 B 10 6 B 10
25 NO NO 37
RELAY 6
A A A A A
RELAY 2
10 2 5 9 10 7 5 9 5 9
26 NC NC 38
27 C C 39 POINTWATCH
CALIBRATE 1 CALIBRATE 13 + 1 OUTPUT 1 + 1
28 NO NO 40
RELAY 7
4 TO 20 MA IN
RELAY 3
2 2 OUTPUT 1 2
29 NC NC 41
3 + 3 OUTPUT 2 + 3
30 C C 42 SENSOR
DUAL SOLENOIDS
SINGLE SOLENOID
POWER
31 NO NO 43 + 4 4 OUTPUT 2 4
RELAY 4
RELAY 8
A2100
32 NC NC 44
95-8556
95-8556
FlexSonicTM Acoustic X3301 Multispectrum PointWatch Eclipse IR FlexVu Universal Display Eagle Quantum Premier
Leak Detector IR Flame Detector Combustible Gas Detector with GT3000 Toxic Gas Detector Safety System
Corporate Office Phone: 952.946.6491 All trademarks are the property of their respective owners.
6901 West 110th Street Toll-free: 800.765.3473 2013 Detector Electronics Corporation. All rights reserved.
Minneapolis, MN 55438 USA Fax: 952.829.8750 Det-Tronics manufacturing system is certified to ISO 9001
www.det-tronics.com det-tronics@det-tronics.com the worlds most recognized quality management standard.