DPC Smart Hybrid Power Solution

DUM-48/50H(HD)

Introduction

DPC Smart Hybrid Power Solution DUM-48/50H(HD), with its


simple, intelligent and efficient features to help operators to
achieve a simple network deployment, whole network
energy-saving, efficient operation and maintenance and the
future smooth evolution. DPC DUM-48/50H(HD) solution
highly integrated power supply system, temperature control
system, site monitoring system and shelter system, providing
a safe and reliable energy supply and working environment
to the main equipment.

This series of products, according to the system capacity, can


be configured "Power cabinet + battery cabinet" or "AC
distribution cabinet + DC distribution cabinet +Rectifier
cabinet+ Battery cabinet", can choose outdoor or indoor
type, to facilitate the use of customers. This series is suitable
for the location of the tower, telecommunications, mobile,
transmission, access network, and private network (such as
water, electricity, military, public security, railways, banks,
computer centers, etc.) which need DC power system. DUM 48/50H outdoor power cabinet

Application Scenarios

DPC Smart Hybrid Power Solution DUM-48/50H(HD) can


apply to various outdoor&indoor sites, provides excellent
performance for sites in off-grid and poor-grid areas with
abundant sunshine.
DPC outdoor solar hybrid solution, integrate diesel or grid,
can be used in wireless coverage site and small node site.
DPC indoor solar hybrid solution, integrate diesel or grid,
can be used in central base station and enterprise
DUM 48/50H indoor power cabinet
communication network.
1
Features

Green & hybrid:


"Solar output priority", energy saving, zero carbon emissions.
The system use solar energy, diesel generators, main grid and battery hybrid between different energy use
(customized), stable output - 48 V DC voltage, to the DC load power supply and battery charging.

Efficient:

MPPT efficiency 99%


Efficiency 96%

GS-48/50H(Solar module)

Efficiency 96%

DZY-48/50HI(rectifier)

2
Reliable:
The solar module and the rectifier module are output in parallel. When the PV input is insufficient, the rectified
input can be connected immediately.
The solar power module is isolated module , even if the module fails, it will not affect the back-end equipment,
high security and reliability.
The solar modules and rectifier modules, have a perfect self-protection function, don't need an extra junction
box.

Easy operation & maintenance:


The system uses the same type of rectifier module, solar modules, PV modules and rectifier modules,
maintenance is very convenient.
The system redundancy two rectifier module slots, two MPPT PV module slots, to meet the post-site expansion
needs.
The system using modular design, modular structure, more flexible and smoother for operation & maintenance.

Configuration

DPC Smart Hybrid Power Solution DUM-48/50H(HD) using modular design, modular structure, composed by the
monitoring unit, AC power distribution, DC power distribution, solar power distribution, battery control unit,
power detection unit, rectifier modules, PV modules and other components.

3
4
System configuration

System configuration Function

AC distribution unit/cabinet Access to the AC input/ output

Rectifier unit/cabinet Install and connect rectifier module, solar module, to achieve AC / DC, DC / DC
conversion.
DC distribution unit/cabinet Access to batteries, DC load, solar panels

Battery combiner Switch between old and new batteries

AC meter Detection of AC input voltage, current, power


Monitoring unit Battery management, hybrid mode setting and management, rectifier module and
solar module status monitoring, lightning fault detection, sub circuit state monitoring
and energy metering.
Battery Lead acid battery or Li-battery

Battery Inspection Device Battery inspection and monitoring

Monitoring unit DKD 51-3

Model DKD51-3
Input Voltage Range 36V72V (full load input range)
Maximum number of monitor modules 48
Sampling accuracy 0.5%
Working Temperature -40~55(100% rated power)
Humidity 95%
Noise 45DB
Cooling Air cooling
Specifications
MBTF 400000 h
Overheat reducing capacity protection, starting
55 / 75 (overheating unstopping)
voltage/to 5% capacity voltage
Module fault Sound and light alarm
Dimension See package
Net weight 3kg
Installation method Hot pull plug
Grounding 5

5
Battery combiner

The system can incorporate old and new batteries through a battery combiner, which can choose different types
of batteries, such as: new lead-acid battery, and old lead-acid batteries, lithium iron batteries (- 48 v), etc.;
Customer can choose different types, different capacity, different manufacturers of the battery.
Different types of batteries can supply to the same load power supply; Can ensure that at least one battery is
connected to the system, without affecting the performance and service life of each other, and ensure supply
continuous power supply to electrical equipment.
Each battery combiner can support 4 groups of battery in parallel.

Battery combiner

Group 1 Group 2 Group 3 Group 4

6
Type Outdoor Indoor
Cabinet Power cabinet Battery cabinet AC distribution cabinet + DC
distribution cabinet +Rectifier
cabinet+ Battery shelf
Cooling HEX, TEC DC air conditioner Natural cooling
Installation Ground mounted Ground mounted Ground mounted
Mode

Cabling up-out and down-in up-out and down-in up-out and down-in
Mode

System Noise Level 65dB


Battery 10KW: DJ500, 500AH*2 50KW: DJ3000, 3000AH *2
Model and 15KW: DJ800, 800AH*2 60KW: DJ2000, 2000AH*4
Capacity 20KW: DJ1000, 1000AH*2 75KW: DJ3000, 3000AH *3
25KW: DJ1000, 1000AH*2 100KW: DJ3000, 3000AH *4
35KW: DJ1000, 1000AH*4
MTBF 400000h
Integrated IDG Type Optional Optional
D.G.
ACDU Type Optional MCCB: 400A*2, 250A*2

AC
Distribution

ATS Type Optional Optional


Input Mode Three - phase five-wire Three - phase five-wire system
system phase voltage: 220VAC
phase voltage: 220VAC line voltage: 380VAC
line voltage: 380VAC Frequency: 50/60Hz
Frequency: 50/60Hz
SPD Three phase B + c-level Three phase B + c-level
lightning protection, In lightning protection, In8/20
8/20s=50KA s=20KAImax8/20s
Imax8/20s=100KA. =40KA.
DCDU Type Fuse: 630A*2,400A*4,200A*4;
Circuit breaker:
100A/1P*10,63A/1P*10,32A/1P
*10,16A/1P*10

7
Output 53.5Vdc 53.5Vdc
Voltage
DC Distribution
Maximum 10KW: 250A; 50KW900A;
Capacity 15KW:300A; 60KW1150A;
20KW:400A; 75KW1300A;
25KW:450A; 100KW1600A.
35KW:600A. (2 rectifier modules
(2 rectifier modules redundancy)
redundancy)
Battery Fuse 10KW: fuse 160A*4; 50KW: 1000A*4;
15KW~25KW: 60KW: 500A*4;
fuse 250A*4; 75KW: 1000A*4;
35KW: fuse 250A*4. 100KW: 1000A*4.
LLVD1 Circuit breaker:
100A/1P*2,
63A/1P*4,32A/1P*4,16
A/1P*2

LLVD2/BLVD 63A/1P*2,32A/1P*2,
16A/1P*2
SPD (Imax)15kA (Imax)15kA
Rectifier DZY-48/50HI(rectifier) DZY-48/50HI(rectifier)
Rectifier Type GS-48/50H(Solar GS-48/50H(Solar module)
module)
Rated Power 2880W 2880W
Controller Type Monitoring unit Monitoring unit
Operating -20+55
Temperature
Storage -45+70
Temperature
Environment Operating Operating relative humidity: 90% (40 2 ) (no condensation);
Humidity Storage relative humidity: 95% (40 2 ) (no condensation)
Altitude -60 ~ + 4000m Altitude above 3000m The system should be used for derating, and the
working environment temperature is reduced by 1 for every 200m above sea level.
Protection IP55 IP55 IP20