Sie sind auf Seite 1von 6

> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 1

About the Coupling Factor Influence on the


Ground Fault Current Distribution on Overhead
Transmission Lines
Maria VINTAN
University L. Blaga of Sibiu, Department of Electrical Engineering and Electronics
E. Cioran Str. No. 4, RO-550025, Sibiu
maria.vintan@ulbsibiu.ro

infinite, in which case the ground fault current distribution is


Abstract A phase-to-ground fault occurring on a independent on the termination of the network; otherwise, they
transmission line divides the line into two sections, each extending must be regarded as finite, in which case the ground fault
from the fault towards one end of the line. These two sections of current distribution may depend greatly on the termination of
the line may be considered infinite if some certain conditions are
met; otherwise, they must be regarded as finite. This paper treats
the network.
the case when those two sections of the line are both very long Based on Kirchoffs theorems and on some methods presented
and allows the determination of the ground fault current by Rudenberg [8], Verma [9], Endreny [4], Edelmann [3] and
distribution in power networks. The influence of the coupling Dawalibi [2], an analytical method in order to determine the
factor between the faulted phase and the ground wire on the ground fault current distribution in effectively grounded power
ground fault current distribution is studied. network, was already presented in previous works [10]-[11].
In [11] it was presented the case when the fault appears to the
Index Termsfault currents, power network, transmission
last tower of the transmission line, considering both infinite
lines
and finite transmission line, respectively the case when the
fault appears at any tower of the transmission line, the two
I. INTRODUCTION sections of the line are finite and it is assumed that the fault is
fed from both directions. The method is applied to three phase
H IGH-VOLTGAE systems have an effectively grounded
neutral. When a ground fault occurs on an overhead
transmission line in a three-phase power network with
systems with mutual coupling between phase conductors and
ground wire.
grounded neutral, the fault current returns to the grounded In this paper it will be developed and analyzed the case
neutral through the towers, ground return path and ground when the fault appears at large distance from both terminals,
wires. and the two sections of the line between the fault and the
Knowledge of fault current distribution is important for the terminals could be considered infinite.
size selection of an overhead ground wire, and respectively for The calculation method is based on the following
the evaluation of the faulted towers voltage rise. In assumptions: impedances are considered as lumped parameters
electromagnetic interference problems, the best way to in each span of the transmission line, line capacitances are
investigate the soils behavior as conducting media is to neglected; the contact resistance between the tower and the
determine the current distribution within ground [6]. ground wire, and the tower resistance between the ground wire
The ground fault divides the line into two sections, each and the faulted phase are neglected; the network is considered
extending from the fault towards one end of the line. linear in the sinusoidal steady-state.
Depending of the number of towers between the faulted tower In the following section it will be shown how might be
and the stations, respectively of the distance between the obtained the expressions of the currents flowing to ground
towers, these two sections of the line may be considered through the towers and the currents in every span of the
ground conductor. Furthermore, the influence of the coupling
factor between the faulted phase and the ground wire on the
This work was partially supported by the Romanian National Council of ground fault current distribution is studied, too.
It is considered an overhead transmission line with one
Academic Research CNCSIS-UEFISCU through the research Grant No. ground wire, connected to the ground at every tower of the line
485/2008. and the fault appears at one tower located at very large
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 2

distance from both terminals.


( I n1 I n ) Z st
in = + I d (3)
II. FAULTS ON OVERHEAD LINE Z cp
Figure 1 presents the connection of a ground wire to earth d
through transmission towers. It is assumed that all the
Similarly:
transmission towers have the same ground impedance Z st and
the distance between towers is long enough to avoid the ( I n I n +1 ) Z st
influence between their grounding electrodes. i n+1 = + I d (4)
The self-impedance of the ground wire connected between Z cp
two grounded towers, called the self-impedance per span, was d
noted with Z cp .
d Substituting equations (3) and (4) in equation (1), for the
It was assumed that the distance between two consecutive current in the faulted tower will be obtained the next equation,
which is a second order difference equation:
towers is the same for every span. Z cp represents the
m
mutual-impedance between the ground wire and the faulted Z cp
phase conductor, per span. d (5)
In = I n +1 2 I n + I n 1
As a first step and without loosing the generality, it is Z st
assumed that the fault occurs at the last tower. The half-line
will be studied first, and then the full-line analysis will be According to [8], the sollution of this equation is:
accomplished by regarding it as a composite of two half-lines.
When the fault appears, part of the ground fault current will n n
get to the ground through the faulted tower, and the rest of the I n = Ae + Be (6)
fault current will get diverted to the ground wire and other
towers. According with the solution (6) which contains the arbitrary
parameters A and B, the current flowing to ground through
successive towers, has an exponentially variation. The
arbitrary parameters A and B could be obtained from the
boundary conditions.
Parameter in the solution (6) could be obtained by
substituting the solution (6) in equation (5). Because
Z cp << Z st , it can be written:
Figure 1. Fault current distribution d

As it was already presented in [11], the current I n flowing Z cp


d
to ground through the n-th tower, counted from the terminal (7)
tower where the fault is assumed to take place, is equal with Z st
the difference between the currents i n and i n +1 :
By applying equation (1) to the (n-1) tower, it will be obtained
the following expression:
I n = i n i n+1 (1)
I n1 = in 1 in (8)
The loop equation for the n-th mesh is given by the next
expression: By substituting the equations (1) and (8) in equation (2), it will
be obtained the next equation with a constant term:
I n Z st I n1Z st + in Z cp I d Z cp = 0 (2)
d d
Z cpd Z cpd
in = in +1 2in + in 1 + I d (9)
in expression (2) represents the coupling factor between Z st Z st
Z cpm
the overhead phase and ground wire ( = ). Similar with equation (5), the current in the ground wire is
Z cpd
given by the next solution:
The equation (2) could be written in the next form:
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 3

in = aen + be n + I d (10)

I 0 = B = (1 )( 1 e )Id (20)
In expression (10), a, b represents the arbitrary parameters.
Because of the link between currents i n and I n , the arbitrary The current in the first span, counted from the faulted tower,
will be:
parameters A, B and a, b are not independent. By substituting
the solutions (6) and (10) in equation (1), it will be obtained:

i1 = I d I 0 = I d [e + (1 e )] (21)
n n n n
Ae + Be = ae (1 e ) + be (1 e ) (11)
The voltage rise at the terminal tower is:
Because these relations are the same for every value of n, it
will be obtained the next expressions: U 0 = Z st I 0 = Z st (1 )(1 e ) I d (22)

A long line is one which has a middle section where the line
A = a (1 e ) (12)
is divided by each tower into infinite half-lines. Next, it is
B = b (1 e ) (13) treated the case when those two sections of the line are both
long.
The current in the ground wire will be then given by the In figure 2 the fault occurs at large distance from both
following expression: terminals, at the tower number 0. The fault divides the line into
two sections, each extending from the fault towards one end of
e n e n the line.
in = A +B + I d (14)
1 e 1 e

The boundary condition at the terminal tower of figure 1 is:

I d = I 0 + i1 (15)

That means that the fault current is given by the sum Figure 2. Fault current distribution
between the current in the faulted tower and the current in the
first span of the ground wire. The boundary condition at the faulted tower will be:
In case that it is considered that the line is sufficiently long
so that, after some distance, the varying portion of the current I d = I 0 + 2i1 (23)
exponentially decays to zero, then the parameter A 0 . In
this case only the parameter B must be found from the
Substituting expressions (16) and (17) in (23), with n = 0 for
boundary conditions [9]. According to (6) and (14), results:
I n and n = 1 for i n , it will be obtained:
n
I n = Be (16)
in = B (e
n
/1 e

) + I d (17) e
I d = B + 2( B + I d ) (24)
1 e
Substituting these expressions in (15), with n = 0 for I n and
Then, the current in the faulted tower will get the expression:
n = 1 for i n , it will be obtained:

1 e
I d = B + B (e /1 e ) + I d (18) I0 = B = (1 2 ) I d (25)
1 + e

For B it will be obtained the next expression:


The current in the first span, counted from the faulted tower,
will be the following:

B = (1 )(1 e )I d (19)
I I
i1 = d 0 (26)
The current in the faulted tower will get the expression:
2
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 4

phase conductor, because it could not be assumed that a line


The voltage at the faulted tower will be: section of a few spans is transposed.
The fault was assumed to occur on the phase which is the
(27)
furthest from the ground conductors, because the lowest
U 0 = Z st I 0 = Z st (1 2 ) I d th coupling between the phase and ground wire will produce the
2
highest tower voltage.
If the the coupling factor between the overhead phase and The total fault current from both stations was assumed to be
ground wire is neglected, then the current in the faulted tower I d =15000A. Those values are valid for a soil resistivity of
will get the following expression: 100 m.
It was assumed that the fault appears at the middle tower of
the line, so there are N=20 towers between the faulted tower
I 0 = B = I d th (28)
2 and each of the terminals.
All the further presented quantitative results are based on
The voltage at the faulted tower will be: the theoretical approaches developed during the previous
section. In order to do this there were developed some
(29) numerical intensive programs written in Matlab 7.0 software
U 0 = Z st I 0 = Z st I d th = ZI d
2 frame.
Figure 4 shows the currents flowing in the transmission line
With Z in expression (29) was noted the equivalent towers ( Z st = 4 ), first considering the mutual coupling
impedance of the network looking back from the fault. between the faulted phase and the ground conductor, than
neglecting that mutual coupling.
III. RESULTS
1800
C urrents in tow ers [A]

In order to illustrate the theoretical approach outlined in


1600
section above, it is considering that the line who connects two
stations is a 110kV transmission line with aluminium-steel 1400
185/32mm2 and one aluminium-steel ground wire 95/55mm2 neglecting coupling factor
(figure 3) [5]. 1200

1000

800

600

400

200
considering
coupling factor
0
-20 -15 -10 -5 0 5 10 15 20
Towers on left side Faulted tower Towers on right side
Figure 4. Currents flowing through the transmission line towers
Figure 3. Disposition of line conductors
It can be seen that in the absence of mutual coupling, the
The line impedances per one span are determined on the fault current will flow through the ground through a smaller
bases of the following assumptions: the average spans length number of towers than in the mutual coupling presence.
is 250m; the resistances per unit length of ground wire is Figure 5 shows the currents flowing in the ground wire for
0.3 / km and its diameter is 16mm. Z st = 4 , first considering the mutual coupling between the
Ground wire impedance per one span Z cp and the mutual faulted phase and the ground conductor, than neglecting that
d
mutual coupling.
impedance Z between the ground wire and the faulted phase It can be seen that in the absence of coupling between the
m
are calculated for different values of the soil resistivity with overhead phase and ground wire, the total fault current will
gradually flow into the ground through the towers, and, if the
formulas based on Carsons theory of the ground return path
line is long enough, no current remains in the overhead wire.
[1].
In contrast, in the presence of coupling factor a portion of the
Impedance Z is calculated only in relation to the faulted current will stay in the overhead wire.
m
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 5

8000 1.6
Currents in ground wire [A]

Infinite line impedance []


7000
considering coupling factor 1.4

1.2
6000
neglecting coupling factor
1
5000
neglecting coupling factor
0.8
4000

0.6
3000
0.4
2000 considering coupling factor
0.2
1000
0
0 5 10 15 20 25 30 35 40 45 50
0 Zst[]
-20 -15 -10 -5 0 5 10 15 20
Spans on left side Faulted tower Spans on right side Figure 7. Equivalent impedance of the infinite
Figure 5. Currents flowing in the ground wire
In order to validate the proposed analytical expressions their
The voltage rise of the faulted tower depends of a number results were compared with those measured in similar
of factors. Some of the most important factors are: conditions using real fault tests [2]. Also the developed
magnitudes of fault currents on both sides of the fault analytical methods were compared with other recognized
location, fault location with respect to the line terminals, analytical methods [7]. In both cases the obtained results were
conductor arrangement on the tower and the location of the very similarly with those obtained by other researchers. For
faulted phase, the ground resistance of the faulted tower, soil example, the faulted towers voltage rise error is always
resistivity, number, material and size of ground wires. smaller than 5%. As important advantages, the presented
Figure 6 shows the influence of the mutual impedance method is simpler and far less time consuming than others.
between the faulted phase and the ground wire on the voltage
rise of faulted tower. It was considered that the ground wire IV. CONCLUSION
impedance is Z cp = 0.19 . A parametric analysis is done in order to study the effects of
d
4
the coupling factor between the faulted phase and the ground
x 10
2.5 wire on the ground fault current distribution in power
Voltage rise of faulted tower [V]

networks. It was considered an overhead transmission line with


2
one ground wire, connected to the ground at every tower of the
line. It was assumed that the fault occurs at large distance from
considering coupling factor
both terminals. There were presented the expressions of the
1.5 currents flowing to ground through the towers and the currents
in every span of the ground conductor. These currents are
1
varying exponentially and their expressions contain arbitrary
parameters which could be obtained from the boundary
conditions. For the long lines case, one of these parameters
0.5 neglecting coupling factor
could be zero. It is apparent that in the absence of coupling
between the overhead phase and ground wire the total fault
0 current will gradually flow into the ground through the towers,
0 5 10 15 20 25 30 35 40 45 50
Zst[] and, if the line is long enough, no current remains in the
Figure 6. Voltage rise of the faulted tower as a function of the tower ground
overhead wire; whereas in the presence of coupling factor a
impedance portion of the current will stay in the overhead wire.
The mutual impedance between the ground conductor and
In order to see the efect of the mutual coupling between the faulted phase conductor reduces the total circuit
the faulted phase and the ground wire, in figure 7 is impedance. Neglecting this mutual impedance the fault current
represented the impedance of the infinite line from equation would be significantly higher.
(29), for a ground wire impedance Z cp = 0.19 , as a From the model presented above, it can be seen that due to
d the mutual coupling, the fault current is reduced with (1 )
function of the tower ground impedance, considering,
factor. It also can be seen that in the absence of mutual
respective neglecting the coupling factor.
coupling, the fault current will flow through the ground
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 6

through a smaller number of towers than in the mutual March 1984


[3] Edelmann H. Electrical Calculus of Interconnected Networks,
coupling presence. As a consequence, in this case the faulted Publishing Technical House, Bucharest, 1966 (in Romanian)
towers voltage rise and also its neighbours voltage rises will [4] Endrenyi J. Analysis of Transmission Tower Potentials during Ground
be higher in an artificial manner. In conclusion our developed Faults, IEEE Transactions on Power Apparatus and Systems, Vol.PAS-
model involves more accurate realistic analysis of the power 86, No.10, October 1967
[5] *** - Methodology of Current Fault Calculus in Electrical Networks -
transmission networks. PE 134/1984, Electrical Research and Development - ICEMENERG,
The paper presents a practical method for ground fault Bucharest 1993 (in Romanian)
analysis being extremely useful in designing grounding [6] Micu D., Munteanu R., et. al.- Original Approaches for Solving
Electromagnetic Interference Problems, Advances in Electrical and
systems. The method can be also used for the design of new Computer Engineering, vol. 9, Number 2, 2009
transmission lines in order to select the size of the ground wire [7] Popovic L. M. - Practical Method for Evaluating Ground Fault Current
and for evaluating safety conditions near transmission towers. Distribution in Station, Towers and Ground Wire, IEEE Transactions on
Power Delivery, Vol.13, No.1, January 1998
[8] Rudenberg R. Transient Performance of Electric Power Systems,
Publishing Technical House, 1959, (translated into Romanian)
ACKNOWLEDGMENT
[9] Verma R., Mukhedkar D. - Ground Fault Current Distribution in Sub-
This work was supported by the CNCSIS-UEFISCU Station, Towers and Ground Wire, IEEE Transactions on Power
through the research Grant No. 485 / 2008. Apparatus and Systems, Vol.PAS-98, No.3, May/June 1979
[10] Vintan M., Buta A. Ground fault current distribution on overhead
transmission lines, FACTA UNIVERSITATIS (NIS), ISSN: 0353-3670,
ser.: Electronics and Energetics, vol.19, No.1, April 2006, Serbia
REFERENCES [11] Vintan M. - Evaluating transmission towers potentials during ground
[1] Carson J. R. - Wave propagation in Overhead Wires with Ground faults, Journal of Zhejiang University SCIENCE A, Zhejiang University
Return, Bell System Techn. 1, vol. 5, 1926 Press, co-published with Springer-Verlag GmbH, Volume 9, Number
[2] Dawalibi F., Niles G. B. Measurements and Computations of Fault 2/February, 2008, pp. 182-189, ISSN 1673-565X (Print); ISSN 1862-
Current Distribution on Overhead Transmission Lines, IEEE 1775 (Online), China, 2008
Transactions on Power Apparatus and Systems, Vol. PAS-103, No. 3,

Das könnte Ihnen auch gefallen