Design calculation sheet

Project No. : 1203 Date : Sheet No. : Computed By : Alaa Ramadan


Approved By :
Subject : Natural Smoke Ventilation For Project GWC 41 st.
Checked By :

Fire Smoke Calculation NOTES


Blue Values are Data Input Values
Purple Values are Typical Values, but can be changed
Type of Stored Material

Design Fire HRR Q= 1700 kW NFPA 92B


Convective Fraction Qc = 1.00 xQ Typically ranging from (0.7 to 1.0) (Recommended 0.7)
Convective HRR Qc = 1700 kW

Ambient Temperature TAMB = 319.00 K


Specific Heat of Plume Gases Cp = 1.01 kJ/kg*K
Smoke Layer Temperature TSMOKE = 365.68 K

Elevation EL = 12.00 m
Molecular Weight of Smoke M= 29.00 kg/mol
Density of Ambient Air rAMB= 1.107 kg/m3
Density of Smoke rsmoke= 0.965 kg/m3

Ceiling Height zceiling= 12.00 m


Smoke Height zs = 9.00 m
Flame Height zl = 3.25 m
Smoke Depth db = 3.00 m
Mass Flow of Smoke Produced mp = 36.06 kg/sec Because Z>Zl we use equation 5-4
3
Total Flow Rate Qt= 37.35 m /s
79142 CFM

Natural Ventilation Mass Flow Rate: Steady State


Selected Vent Size AVENT = 2.00 m2
Vent Drag Coefficient C = 0.65 Typically ranging from 0.6 to 1.0
Pressure Drop from Inside-Outside DP = 4.76 Pa
Velocity of Venting Smoke VVENT = 2.042 m/s
Vent Mass Flow Rate mVENT = 3.943 kg/s
Volumetric Smoke Flow Rate Q = 4.08 m3/s
Q = 8654 CFM

Nos. Of Vents N = 9.1 9