Sie sind auf Seite 1von 6

SRN Description Stand By DG Set

LTP-Limited-time running power is defined as the


maximum power available, under the agreed
operating conditions, for which the generating set
is capable of delivering for up to 500 h of
operation per year with the maintenance
intervals and procedures being carried out as
prescribed by the manufacturers.
ISO-Definition

Stand By DG Set rating is declared at the


maximum Capcity of the Engine which is
equivalent to overload capacity of Prime Engine.
Under this rating DG sets are allowed to be use
1 Power Limit the power for specific time

2 10% Overload Not Available

No of Hour Usage
3 Limitation 500 hrs in a Year
4 Life Span of Engine Shorter

Applicability in Stand by is becoming popular rating in India with


5 Indian Conditions DG primarily being used as back up power to EB

6 Average Loading 85% for rated Power

6 Ratin Example 1100


Prime DG set Continuous DG Set

PRP-Prime power is defined as being the maximum


power which a generating set is capable of delivering
continuously whilst supplying a variable electrical COP-Continuous power is defined as being the
load when operated for an unlimited number of maximum power which the generating set is capable
hours per year under the agreed operating of delivering continuously whilst supplying a
conditions with the maintenance intervals and constant electrical load when operated for an
procedures being carried out as prescribed by the unlimited number of hours per year under the
manufacturer.The permissible average power output agreed operating conditions with the maintenance
(Ppp) over 24 h of operation shall not exceed 70 % of intervals and procedures being carried out as
the PRP unless otherwise agreed by the RIC engine prescribed by the manufacturer
manufacturer.

Prime DG set rating are declared considering the Continuous DG set rating are declared considering
100% Power of the Enfgine. 10% Overload is the 100% Power of the Engine. 10% Overload is not
available over and above this rating definition. Under available. These DG sets are meant to run for 100%
this rating DG set are allowed to run on average base load for 24/7 operation without any variation of
loading for getting optimum life of Engine. load.

Available Not Available

Unlimited No of hours of Usage Unlimited No of hours of Usage


Longer lesser than Prime.

99.5% of the DG set sold in India for Various Almost 0% Continuous rated DG sets are slod in
applications are Prime DG sets only India. Major ratings are Prime rated DG set.

80% of Rated Power 100% of Rated Power

1010 800
Remark

Engines for stand by DG sets are


utilised for its maximum capacity
and as result wear an tear of the
Engine is more, as regards to
prime DG set which run on the
optimum loading. Engines with
Continous capacity is loaded at a
minimum capacity so that wear
and tear is limited for continuous
base load running.

Streched Capacity of Engines is


used to declare stand by rating of
DG set.Continuous rated DG set
are meant for 100% base load
running without variation of load
and hence dont allow over load

Stand By has limited usage as


compared to Prime DG set.
Since the DG set is utilised for its
maximum capacity even though
for limited time but life span is
comparitively lesser than Prime
DG set.

Prime DG sets are sold in huge


nos in India because of the
uncertain power situation in India

Das könnte Ihnen auch gefallen