Beruflich Dokumente
Kultur Dokumente
Yonggang Lei, Yazi Li, Shenglan Jing, Chongfang Song, Yongkang Lyu, Fei
Wang
PII: S1359-4311(17)32255-X
DOI: http://dx.doi.org/10.1016/j.applthermaleng.2017.07.081
Reference: ATE 10749
Please cite this article as: Y. Lei, Y. Li, S. Jing, C. Song, Y. Lyu, F. Wang, Design and performance analysis of the
novel shell-and-tube heat exchangers with louver baffles, Applied Thermal Engineering (2017), doi: http://
dx.doi.org/10.1016/j.applthermaleng.2017.07.081
This is a PDF file of an unedited manuscript that has been accepted for publication. As a service to our customers
we are providing this early version of the manuscript. The manuscript will undergo copyediting, typesetting, and
review of the resulting proof before it is published in its final form. Please note that during the production process
errors may be discovered which could affect the content, and all legal disclaimers that apply to the journal pertain.
Design and performance analysis of the novel shell-and-tube heat
Abstract
Two novel shell-and-tube heat exchangers with louver baffles are invented and
designed for energy conservation. A certain amount louver baffles at the inclination
angle between shell side flow direction and louver baffle are equipped in shell side to
support tube bundles. Numerical simulations are carried out to investigate the
segmental baffles also studied in the paper. Fluid flow structures and temperature
distributions are presented for the analysis of the physical behavior of fluid flow and
heat transfer. Oblique flow is produced in the shell side of the shell-and-tube heat
exchangers with louver baffles that decrease and eliminate the dead spaces and augment
the local heat transfer. Compared with the shell-and-tube heat exchanger with segmental
baffles, abrupt change of fluid flow is avoided that decrease the pressure drop in the
shell side. The numerical results indicated that the heat transfer coefficient per pressure
drop of both the shell-and-tube heat exchangers with louver baffles are higher than that
of the shell-and-tube heat exchanger with segmental baffles. This implies that at the
same heat transfer quantity, the pumping power of the shell-and-tube heat exchangers
1
with louver baffles is lower than that of the shell-and-tube heat exchanger with
Numerical simulation
1. Introduction
widely used due to versatility, robustness, and reliability[1-3]. The segmental baffle is
the most common baffle in shell-and-tube heat exchanger that widely used in power
However, there are some disadvantage for the conventional shell-and-tube heat
exchanger with single segmental baffles such as high pressure drop, dead zone, and high
In the past few decades, numerous investigations have been conducted thus far in
order to find preferable types of baffle for shell-and-tube heat exchangers with high
However the zigzag pattern in shell side of the traditional shell-and-tube heat
exchanger with single segmental baffles is not changed radically and the principle
drawbacks is still remain for the above mentioned structure with improved baffles.
In order to further improve the performance in shell side of the shell-and-tube heat
side which change the transverse flow manner to longitudinal flow and helical flow.
2
Rod-baffle heat exchanger originally presented by Phillips Petroleum Company is the
typical longitudinal flow heat exchanger which tube bundles are supported by Rod
baffles[17,18]. Dong et al. [19] used a periodic flow unit as the simplified model to
study the performance of Rod-baffle heat exchanger. The numerical simulation results
indicated that pressure drop and heat transfer coefficient decrease with the increase of
baffle pitch at the same fluid velocity and the decrease extent of pressure drop is larger
than heat transfer. You et al. [20] adopted round rods with arc cuts as supported structure
to improve the shell side performance of rod-baffle heat exchanger. The influences of
performance were studied. Liu et al. [21] conducted numerical investigation on the fluid
flow and heat transfer in shell side of a rod-baffle heat exchangers with spirally
corrugated tubes. Physical quantity synergy analysis was conducted for the performance
study. Wang and You et al. [22,23] investigated the heat transfer and flow resistance
on shell side of the shell-and-tube heat exchanger with flower baffles. Yang and Liu [24]
proposed a shell-and-tube heat exchanger with new plate baffles. They reported that the
plate baffles heat exchanger has a higher comprehensive performance of 115% 122%
generating helical flow in shell side by helical baffles. The discontinuous helical baffles
and Nemcansky [25]. They found that plug flow are generated in shell side that
reducing back mixing and increasing heat transfer. In recent yeas, Lei et al. [26] studied
the performance of a heat exchanger with single helical baffles by using experimental
3
and numerical method, and designed a shell-and-tube heat exchanger with two-layer
helical baffles. Lei et al. [27] also studied the effects of baffle inclination angle on the
for shell-and-tube heat exchangers with middle-overlapped helical baffles at helix angle
of 20, 30, 40, 50. Wang et al. [29] numerically studied the performance of a
baffles in outer shell pass which improve the heat transfer. Three dimensional numerical
middle-overlapped helical baffles were also carried out by Zhang et al [30, 31].
Movassag et al. [32] reported the performance comparison of shell and tube heat
exchangers by tube bundle replacement. It indicated that helical baffles have higher heat
transfer for the same pressure drop. Azar et al. [33] experimentally studied the
performance of tube bundle replacement for segmental and helical baffles. The results
indicated that it not only improved heat transfer of the helix bundle over segmental
bundle, but also increases up to two-three times of operational running times. In order to
block triangular leakage zones in original heat exchangers with helical baffles, fold
helical baffle and ladder-type fold baffle was presented by Wen and Wang et al. [34,35].
Yang et al. [36] proposed a combined single shell-pass shell-and-tube heat exchanger
with two-layer continuous helical baffles. The results show that the new shell-and-tube
heat exchanger has a higher heat transfer performance with a lower pressure drop.
It can be seen from the foregoing literature review, although researchers have put
4
there are insufficient to meet all requirements and restrains such as assemblage, fouling,
consumption. It is still challenging to design and improve baffle structure to meet the
demand of easy assembly and low pumping power consumption for energy saving. To
our best knowledge, the investigation on shell side flow structure are focus on
transverse, longitudinal, and helical flow pattern. There is very few researches on the
oblique flow in shell side of shell-and-tube heat exchanger. notably, there are no
In this study, two types of reformed shell-and-tube heat exchangers with louver
baffles are invented and designed in order to decrease the pumping power and improve
the overall performance of the shell side compared with the shell-and-tube heat
exchangers with conventional segmental baffles. For the novel heat exchangers, Oblique
flow is produced in the shell side by louver baffles that not only decrease and eliminate
the dead spaces, but also avoid the abrupt change of the direction of flow in the shell
side. In the paper, the thermo-hydraulic performance of the novel heat exchangers are
investigated by using three dimension numerical simulation and the comparison of the
numerical and experimental results is present for the validation of numerical method.
Details of the flow structures and temperature distributions in the shell side will be
shell-and-tube heat exchangers with louver baffles and the shell-and-tube heat
5
2. Physical models of the novel types of heat exchangers
The new types of heat exchangers are designed on the base of louver baffles at the
inclination angle between shell side flow direction and louver baffle which generate
oblique flow. A certain amount louver baffles which fixed on the baffle rings are placed
in shell side to support tube bundles. The schematic diagram of the arrangement of
louver baffles and tube bundles for the two heat exchangers with louver baffles are
presented in Fig1. For the convenience of discussion, hereinafter, one is assigned the
name STHX-LV1 as illustrated in Fig1(a) and another is assigned the name STHX-LV2
as shown in Fig1(b). It can be seen from Fig1(a) , for STHX-LV1, one period of louver
baffles consist of two baffle groups. The first baffle group has three inclined plates fixed
on one baffle ring and the second baffle group has two inclined plates fixed on another
baffle ring. The total area of blades of these two baffles group is equal to the shell cross
section area. As shown in Fig1(b), for STHX-LV2, one period of louver baffles is also
composed of two baffle groups with baffle cut of 20% that like conventional segmental
segmental baffles at baffle cut of 20%, which is named STHX-SG, is also studied in the
paper. The three shell-and-tube heat exchangers of the STHX-SG, STHX-LV1 and
STHX-LV2 have same dimensions of shell, tube, inlet and outlet. Contour of the two
heat exchangers with louver baffles are presented in Fig2. The layout of tube bundles of
the three heat exchangers is also identical as shown in Fig3. Base geometry dimensions
of the heat exchangers are listed in Table1. The only difference of the three heat
6
3. Numerical simulation
The working fluid in shell side of the three heat exchangers is water which is steady,
turbulence, and incompressible. The fluid physical properties are constant and the effect
of gravity is negligible. The RNG k turbulence model with standard wall functions
be written as follows:
Continuity equation:
ui
=0 (1)
xi
Momentum equation:
(uiu j ) P ui (2)
= +
x j xi x j x j
Energy equation:
( u jT )= k T (3)
x j x j C p x j
( kui ) k (4)
(k ) + = k eff + Gk
t xi x j x j
( ui ) 2 (5)
( ) + = eff +C1 Gk C2
t xi x j x j k k
k2 (1 / o )
where: e ff = + t , t =C , C 1 = C 1 ,
1+ 3
7
k u j
= ( 2 E ij E ij ) 1/ 2 , E ij = 1 ( u i + ),
2 x j xi
ui u j ui
Gk = t ( + )
x j xi x j
The empirical constants for the RNG k model are assigned as follows.
The uniform velocity boundary condition was set for shell side inlet of these heat
exchangers. The fluid temperature is kept constant of 333K at the shell side inlet.
Non-slip boundary condition was employed on all solid walls. the boundary condition of
adiabatic was imposed for the shell wall, inlet and outlet nozzle walls, while the tube
walls were set as constant temperature of 298K. The outflow boundary condition was
applied for the shell side outlet. Fluid-solid conjugated heat transfer was modeled for
the baffles because of the conjugated heat transfer characteristics between the baffle
walls and fluid. The standard wall functions was employed for the near wall region to
mentioned above were discretized by the finite volume method with SIMPLE
pressure-velocity coupling algorithm. QUICK scheme was applied for both the
convective and diffusive terms in the numerical simulation. The convergence criterion
were taken as 110-4 for the flow equations and 110-8 for the energy equation.
The tetrahedron unstructured grids were employed for the computational domain
due to the complex of the models which composed of tube bundle, shell, baffles, inlet
and outlet nozzle. Mesh refinements were employed for the region adjacent to tubes
8
and baffles wall. Fig.4. demonstrate the meshes of STHX-LV1. Grid independence
tests have been conducted for the computational models to ensure the quality of meshes
and the accuracy of simulation. Six mesh systems with 8.5 105 , 1.06 106 , 1.5 106 ,
2.05 106 , 2.35 106 and 3.56 106 cells were generated for STHX-LV1. Fig.5. shows
the results of grid independence tests. It was found that the relative deviation between
the fifth grid system and sixth grid system is less 1% for heat transfer coefficient and
2% for pressure drop. Thus, the fifth grid system with 2.35 106 cells was selected for
computation considering both the solution precisions and numerical resource cost. The
similar grid independence tests were also carried out for STHX-SG and STHX-LV2.
Shell-side pressure drop and heat transfer coefficient are employed to analyze the
heat exchanger performance. The major equations on how to process date are shown as
follows:
Q = m C p ( T ou t Tin ) (6)
h = Q / Tm A (7)
( T in T w ) (T o u t T w )
Tm = (8)
ln [ ( T in T w ) /(T o u t T w ) ]
A = n d L (9)
where Q is the heat transfer rate, m is the mass flow rate of working fluid, Cp is the
specific heat of water, h is the heat transfer coefficient, Tm is the log mean temperature
difference, Tin and Tout are temperature at shell-side inlet and outlet, T w is the temperature
of the tube walls, A is the total heat transfer area, n is the number of tubes, d is the
9
3.5 Model validation
In order to validate the reliability of the present computational model and numerical
method, the heat exchanger model with segmental baffles that has same geometric
parameters from literature[28] was calculated at first. There are two cycles, oil cycle
and water cycle, in this experiment system. Oil flow is in the shell side while water act
as a coolant flowing inside the tubes. For the heat exchanger, the diameter of the shell is
325mm, the diameter of the tubes is 19mm, the number of the tubes is 97, the tube pitch
is 25mm, the baffle pitch is 130mm, and the number of the baffles is 8. The comparison
between numerical simulation results and experimental data is shown in Fig6. The
results indicated that the numerical simulation data line of the shell-side pressure drop
has similar tendency just as that of the experimental results. The maximum deviation of
two results is less than 15%. The agreement between the numerical results and
The path lines in the shell side of the STHX-SG, STHX-LV1, STHX-LV2 are
illustrated in Fig.7. It can be seen from Fig.7(a) that the zigzag flow pattern is generated
in the shell side of the heat exchanger with conventional segmental baffles. The
direction of flow is changed abruptly when the flow hits the segmental baffles.
Therefore, larger momentum change and severe pressure drop caused in shell side. An
important phenomenon can be clearly found that that large dead spaces and recirculation
zones appear behind the segmental baffles which result in ineffective heat transfer area
and heat transfer deterioration in the region. As can be seen from Fig.7(b) and Fig.7(c),
10
the fluid flows in shell side of the heat exchangers with louver baffles are in oblique
flow pattern that is different from the flow structure in shell side of the heat exchanger
with conventional segmental baffles. The cross flow paths are found throughout the
shell volume and the flow is well developed. The flow structure in shell side caused by
louver baffles is smoother than that by segmental baffles. It is worth to note that the tube
bundles in the shell-and-tube heat exchanger with louver baffles are washed out by
oblique flow which decrease and eliminate the dead spaces and back mixing at the back
of the baffles that mentioned above in the heat exchanger with segmental baffles as
marked with a circle in Fig.7(a). Therefore, the local heat transfer in the region behind
baffles is significantly improved. It can be also observed that path lines in the shell side
of the STHX-LV1 are obviously smoother than that of the STHX-LV2. The different
flow structures among the three heat exchangers cause the different thermo-hydraulic
Fig.8 display the temperature distributions of these three heat exchangers. For the
in Fig.8(a) is obviously non-uniform along the shell side. The temperature behind the
baffles as marked with a circle is very low that indicate the local heat transfer in the
region is terrible. This phenomenon is because of the dead spaces and recirculation
zones in the region. It is interesting to note that from the Fig.8(b) and Fig.8(c), the
temperature is distributed more uniform in the shell side of the two heat exchangers
with louver baffles that can effectively improve the thermo-hydraulic performance.
Particularly, the temperature behind the louver baffles is higher than that behind the
11
4.2 Pressure drop
Because pumping power costs are depended on the pressure drop of a heat exchanger,
the pressure drop is a very important parameter in the design of shell-and-tube heat
exchanger. Fig.9 demonstrates the pressure drop versus flow rate in shell side. For
comparison, the same function for shell-and-tube heat exchanger with segmental baffles
is also presented in the figure. For all heat exchangers, the pressure drop increase with
the increase of flow rate. It is clear that the pressure drops in shell side of the two heat
exchangers with louver baffles are remarkably lower than that of the heat exchanger
with segmental baffles at same flow rate which imply the lower pumping power for the
two heat exchangers with louver baffles at same flow rate. The reason for above
phenomenon can be attributed to the followings. For STHX-SG, zigzag flow pattern are
caused out in shell side and primary flow direction change dramatically which result in
abrupt momentum change and severe pressure drop. Whereas for STHX-LV1 and
STHX-LV2, the fluid flow in shell side become smoother and fluid obliquely wash the
tube bundles in shell side by louver baffles that the primary flow direction does not
change dramatically. So, the pressure loss in shell side of the shell-and-tube heat
exchangers with louver baffles can be reduced comparing with the shell-and-tube heat
exchangers with conventional segmental baffles. The results indicated that comparing to
the conventional STHX-SG at the flow rate from 5m3/h to 15m3/h , the pressure drops
in shell side of STHX-LV1 and STHX-LV2 are decreased by about 63% and 55% on
average, respectively. It can be also seen that the pressure drop in shell side of
STHX-LV1 is lower than that of the STHX-LV2 and the difference increases with the
increases of flow rate. In comparison with the STHX-LV2, the pressure drop of the
12
STHX-LV1 is shown to decrease by 19%.
The heat transfer rate versus pumping power are given in Fig.10. A higher position
in the figure signifies a better heat transfer quantity at same pumping power, which also
implies less pumping power is required to reach the same heat transfer rate. It can be
seen from the figure that at the same pumping power, the heat transfer rates of the two
shell-and-tube heat exchangers with louver baffles obviously above that of the
shell-and-tube heat exchanger with segmental baffles. This means that under the same
pumping power, the heat transfer performance of the shell-and-tube heat exchangers
with louver baffles are superior to the shell-and-tube heat exchanger with segmental
baffles. The deviations of the heat transfer rate at the same pumping power is small in
the region of low pumping power, while the difference become larger for the region of
high pumping power. It is very interesting to note that the heat transfer rate has a fast
increase with increasing of pumping power in the region of lower pumping power. The
results indicated that for the same heat transfer rate, the shell-and-tube heat exchanger
with segmental baffles will need much more pumping power than that of the two
shell-and-tube heat exchangers with louver baffles. It is understood that the pumping
power cost for the shell-and-tube heat exchangers with louver baffles is much less than
that of the heat exchanger with segmental baffles at a given heat transfer quantity.
Considering both the heat transfer coefficient and pressure drop of heat exchangers
are significant to indicate the efficiency of heat exchangers. It is desirable to obtain the
higher heat transfer rate at the same pressure drop that improve the comprehensive
13
performance. In the present study, the overall performance of the three shell-and-tube
heat exchangers is evaluated by using the heat transfer coefficient per pressure drop.
Fig.11 depicts the heat transfer coefficient per pressure drop versus flow rate for the
STHX-LV1, STHX-LV2, and STHX-SG. It can be observed that the heat transfer
coefficient per pressure drop of all the heat exchangers decrease with increasing flow
rate. It is very interesting to note that the overall performance of both STHX-LV1 and
STHX-LV2 are obviously higher than that of the STHX-SG. It can be concluded that the
heat exchanger with segmental baffles. The heat transfer efficiency at the same pressure
drop for the two new shell-and-tube heat exchangers with louver baffles is superior to
the shell-and-tube heat exchanger with segmental baffles. The reason for the results can
be explained as followings. On one hand, the louver baffles smooth the fluid flow and
decrease the dead spaces in shell side, hence resulting in a better thermal mixing and
local heat transfer improvement. On other hand, the primaries flow direction in shell
side of the two shell-and-tube heat exchangers with louver baffles doesn't change
dramatically that decrease the abrupt momentum change and severe pressure loss. The
results indicated that the heat transfer coefficients per pressure drop of the STHX-LV1
and STHX-LV2 are about 94.6% ~ 118.2% and 73.3% ~ 89.7% on average higher than
that of the STHX-SG. Furthermore, The heat transfer coefficients per pressure drop of
STHX-LV1 increase by 10.1% ~ 15.5% over that of STHX-LV2. It was found that the
STHX-LV1 shows the best overall performance among the three heat exchangers.
14
5. Conclusions
In the present paper, Two reformed shell-and-tube heat exchangers with louver
baffles (STHX-LV1 and STHX-LV2) are proposed and designed for energy saving.
The physical behavior of fluid flow and thermo-hydraulic were analyzed by three
segmental baffles (STHX-SG) was also numerically studied for comparison. The
obtained and the performance comparisons were explored. The main conclusions are
drawn as follows:
1 Oblique flow pattern is generated in the shell side of the heat exchangers with
louver baffles which is smoother than the flow pattern in the shell side of the heat
exchangers with segmental baffles. Compared with the heat exchanger with
segmental baffles, dead spaces and recirculation zones are decreased for the new
shell-and-tube heat exchangers that improve the heat transfer efficiency. Abrupt
change of the direction of flow is avoided in the shell side of the two new
2 The temperature distributions in the shell side of the two new shell-and-tube heat
exchangers with louver baffles are more uniform that can effectively improve the
baffles is higher than that behind the segmental baffles which imply the
3 Compared with the conventional STHX-SG at the same flow rate, the pressure
drops in shell side of STHX-LV1 and STHX-LV2 are decreased by about 63%
15
and 55% on average, respectively. The pressure drop in shell side of STHX-LV1
is 19% lower than that of the STHX-LV2. At the same pumping power, the heat
transfer rates of the two shell-and-tube heat exchangers with louver baffles
obviously are higher than that of the shell-and-tube heat exchangers with
segmental baffles.
4
The overall performance of the two novel shell-and-tube heat exchangers with
louver baffles are superior to the shell-and-tube heat exchanger with segmental
baffles. It was found that the heat transfer coefficients per pressure drop of the
STHX-LV1 and STHX-LV2 are about 94.6% ~ 118.2% and 73.3% ~ 89.7%
higher than that of the STHX-SG. The heat transfer coefficients per pressure drop
of the STHX-LV1, which have the best overall performance among the three heat
Acknowledgements
This work is supported by the National Natural Science Foundation of China (Grant
No.U1510136). The first author wish to thank Prof. Yaling He, Prof. Wenquan Tao, Prof.
Notation
Ds diameter of shell, mm
d diameter of tube, mm
16
k turbulent kinetic energy,
P pressure drop, Pa
Pr Prandtl number,
n number of tubes
u velocity vector
x, y, z Cartesian coordinates
Greek symbols
thermal conductivity, W / (m K)
dynamic viscosity, Ns / m2
density, kg / m3
References
[1] Markowski M, Trafczynski M, Urbaniec K. Identification of the influence of fouling on the
heat recovery in a network of shell and tube heat exchangers. Appl Energy 2013; 102:
755764.
[2] Yang J, Fan AW, Liu W, Jacobi AM. Optimization of shell-and-tube heat exchangers
17
Convers Manage 2014; 78: 468476.
[3] Pal E, Kumar I, Joshi JB, Maheshwari NK. CFD simulations of shell-side flow in a
shell-and-tube type heat exchanger with and without baffles. Chem Eng Sci 2016: 143
314-340.
[4] Webb RL. Principles of enhanced heat transfer, New York; Wiley: 1994.
[5] Stehlik P, Nemcansky J, Kral D, Swanson LW. Comparison of correction factors for
shell-and-tube heat exchangers with segmental or helical baffles. Heat Transfer Eng 1994;
15: 55-65.
[6] Li HD, Kottke V. Effect of the leakage on pressure drop and local heat transfer in
shell-and-tube heat exchangers for staggered tube arrangement. Int J Heat Mass Transfer
[7] Soltan BK, Saffar-Avval M, Damangir E. Minimization of capital and operating costs of
shell and tube exchangers. Appl Therm Eng 2004; 24: 2801-2810.
[8] Saffar-Avval M, Damangir E. A general correlation for determining optimum baffle spacing
for all types of shell and tube exchangers. Int J Heat Mass Transfer 1995; 38: 2501-2506.
[9] Mukherjee R. Effectively design shell-and-tube heat exchangers. Chem Eng Progress 1998;
94: 21-37.
[10] Deng XH, Den SJ. Investigation of heat transfer enhancement of roughened tube bundles
supported by ring or rod supports. Heat Transfer Eng 1998; 19: 21-27.
[11] Sthlik P, Wadekar VV. Different Strategies to improve Industrial heat exchange. Heat
[12] Bell KJ. Heat exchanger design for the process Industries. ASME J Heat Transfer 2004;
126: 877-885.
[13] Chen YP, Sheng YJ, Dong C, Wu JF. Numerical simulation on flow field in circumferential
overlap trisection helical baffle heat exchanger. Appl Therm Eng 2013; 50: 1035-1043.
[14] You YH, Chen YQ, Xie MQ, Luo XB, Jiao L, Huang SY. Numerical simulation and
performance improvement for a small size shell-and-tube heat exchanger with trefoil-hole
[15] Mukherjee R. Use double-segmental baffles in the shell-and-tube heat exchangers. Chem
18
[16] Li HD, Kottke V. Analysis of local shell side heat and mass transfer in the shell-and-tube
heat exchanger with disc-and-doughnut. Int J Heat Mass Transfer 1999; 42: 3509-3521.
[17] Gentry CC. Rod-baffle heat exchanger technology. Chem Eng Prog 1990; 86: 48-56.
[18] Gentry CC. Rod baffle heat exchanger. Appl Therm Eng 1998; 18: VII-VIII.
[19] Dong QW, Wang YQ, Liu MS. Numerical and experimental investigation of shell side
characteristics for Rod baffle heat exchanger. Appl Therm Eng 2008; 28: 651-660.
[20] You Y, Zhang F, Fan A, Dai F, Luo X, Liu W. A numerical study on the turbulent heat
transfer enhancement of Rod baffle heat exchanger with staggered tubes supported by
round rods with arc cuts. Appl Therm Eng 2015; 76: 22032.
[21] Liu JJ, Liu ZC, Liu W. 3D numerical study on shell side heat transfer and flow
characteristics of rod-baffle heat exchangers with spirally corrugated tubes. Int J Therm Sci
[22] Wang YS, Liu ZC, Huang SY, Liu W, Li WW. Experimental investigation of shell-and-
tube heat exchanger with a new type of baffles. Heat Mass Transfer 2011; 47: 8339.
[23] You YH, Fan AW, Huang SY, Liu W. Numerical modeling and experimental validation of
heat transfer and flow resistance on the shell side of a shell-and-tube heat exchanger with
[24] Yang J, Liu W. Numerical investigation on a novel shell-and-tube heat exchanger with plate
baffles and experimental validation. Energy Convers Manage 2015; 101; 689696.
[25] Lutcha J, Nemcansky J. Performance improvement of tubular heat exchangers by helical baffles.
[26] Lei YG, He YL, Chu P, Li R. Design and optimization of heat exchangers with helical baffles.
[27] Lei YG, He YL, Li R, Gao YF. Effects of baffle inclination angle on flow and heat transfer
of a heat exchanger with helical baffles. Chem Eng Progress 2008; 47: 23362345.
[28] Zhang JF, Li B, Huang WJ, Lei YG, He YL, Tao WQ. Experimental performance comparison of
shell-side heat transfer for shell-and-tube heat exchangers with middle-overlapped helical
baffles and segmental baffles. Chem Eng Sci 2009; 64: 1643-1653.
[29] Wang QW, Chen QY, Chen GD, Zeng M. Numerical investigation on combined multiple
shell-pass shell-and-tube heat exchanger with continuous helical baffles. Int J Heat Mass
19
Transfer 2009; 52: 1214-1222.
[30] Zhang JF, He YL, Tao WQ. 3D numerical simulation on shell-and-tube heat exchangers with
middle-overlapped helical baffles and continuous baffles-part I: numerical model and results of
whole heat exchanger with middle overlapped helical baffles. Int J Heat Mass Transfer 2009;
52: 5371-5380.
[31] Zhang JF, He YL, Tao WQ. 3D numerical simulation on shell-and-tube heat exchangers with
middle-overlapped helical baffles and continuous baffles-part II: simulation results of periodic
model and comparison between continuous and noncontinuous helical baffles. Int J Heat Mass
[32] Movassag SZ, Taher FN, Razmi K, Azar RT. Tube bundle replacement for segmental and
helical shell and tube heat exchangers: Performance comparison and fouling investigation on
[33] Azar RT, Khalilarya S, Jafarmadar S. Tube bundle replacement for segmental and helical shell
and tube heat exchangers: Experimental test and economic analysis. Appl Therm Eng 2014; 62:
622-632.
[34] Wang SM, Wen J, Yang HZ, Xue YL, Tuo HF. Experimental investigation on heat transfer
enhancement of a heat exchanger with helical baffles through blockage of triangle leakage
[35] Wen J, Yang HZ, Wang SM, Xue YL, Tong X. Experimental investigation on performance
comparison for shell-and-tube heat exchangers with different baffles. Int J Heat Mass
[36] Yang JF, Zeng M, Wang QW. Numerical investigation on combined single shell-pass
shell-and-tube heat exchanger with two-layer continuous helical baffles. Int J Heat Mass
20
Captions
Fig.1. Schematic diagram of the arrangement of louver baffles and tube bundles for heat
exchanger with louver baffles: (a) STHX-LV1; (b) STHX-LV2
Fig.2. Contour of the heat exchangers with louver baffles: (a) STHX-LV1; (b)
STHX-LV2
Fig.3. Tube bundle layout
Fig.4. Mesh topology: (a) front view; (b) local grids of louver baffles ; (c) side view
Fig.5. Results of different grid systems
Fig.6. The comparison of numerical results and experimental data
Fig.7. The path lines in the shell side of the three shell-and-tube heat exchangers: (a)
STHX-SG ; (b) STHX-LV1; (c) STHX-LV2
Fig.8. The temperature distributions in the shell side of the three shell-and-tube heat
exchangers: (a) STHX-SG ; (b) STHX-LV1; (c) STHX-LV2
Fig.9. Pressure drop in shell side versus flow rate
Fig.10. Heat transfer rate in shell side versus pumping power
Fig.11. Heat transfer coefficient per pressure drop in shell side versus flow rate
Table1. Geometric parameters
Table 2. Thermo-physical properties of water
21
First baffle group Second baffle group
(a)
22
First baffle group Second baffle group
(b)
Fig.1. Schematic diagram of the arrangement of louver baffles and tube bundles for heat
exchanger with louver baffles: (a) STHX-LV1; (b) STHX-LV2
23
(a)
(b)
Fig.2. Contour of the heat exchangers with louver baffles: (a) STHX-LV1; (b)
STHX-LV2
24
Fig.3. Tube bundle layout
25
(a)
(b)
(c)
Fig.4. Mesh topology: (a) front view; (b) local mesh of louver baffles ; (c) partial
side view
26
5 6 6 6 6 6 6 6
5.0x10 1.0x10 1.5x10 2.0x10 2.5x10 3.0x10 3.5x10 4.0x10
580
560 h
h /(wm-2K-1)
540
520
500
480
460
155
Ps
150
Ps /(Pa)
145
140
135
5 6 6 6 6 6 6 6
5.0x10 1.0x10 1.5x10 2.0x10 2.5x10 3.0x10 3.5x10 4.0x10
Grid number
27
16
Experimental[28]
14
Numerical
12
10
P / (kPa) 8
0
0 5 10 15 20 25 30
3 -1
Vs / (m h )
28
(a)
(b)
(c)
Fig.7. The path lines in the shell side of the three shell-and-tube heat exchangers: (a)
STHX-SG ; (b) STHX-LV1; (c) STHX-LV2
29
(a)
(b)
(c)
Fig.8. The temperature distributions in the shell side of the three shell-and-tube heat
exchangers: (a) STHX-SG ; (b) STHX-LV1; (c) STHX-LV2
30
4000
STHX-SG
STHX-LV1
STHX-LV2
3000
P/ (Pa) 2000
1000
0
4 5 6 7 8 9 10 11 12 13 14 15 16
3 -1
Vs / (m h )
31
5
4.0x10
STHX-SG
5
STHX-LV1
3.5x10 STHX-LV2
5
Q /(Js )
-1
3.0x10
5
2.5x10
5
2.0x10
5
1.5x10
5
1.0x10
0 2000 4000 6000 8000 10000 12000 14000 16000
-1
N /(Pakgs )
32
4.0
STHX-SG
3.5 STHX-LV1
STHX-LV2
3.0
h/Ps\ wm K Pa )
2.5
-1
-1
2.0
-2
1.5
1.0
0.5
0.0
4 5 6 7 8 9 10 11 12 13 14 15 16
3 -1
Vs / (m h )
Fig.11. Heat transfer coefficient per pressure drop in shell side versus flow rate
33
Table1. Geometric parameters
Item Dimensions and description
STHX-LV1 STHX-LV2
Shell-side parameters
Ds (mm) 250 250
Tube parameters
d (mm) 19 19
L (mm) 2500 2500
Number 61 61
Tube pitch (mm) 25 25
Arranging style for tubes triangle triangle
Baffle parameters
Baffle group numbers 6 6
Width of each plate (mm) 50 62.5
Plate pitch (mm) 100 62.5
o
Plate inclination angle / 60 60o
34
Table 2. Thermo-physical properties of working fluid
Parameter Value
Cp (J/kg K) 4183
Pr 7.02
2
(m /s) 1.0048 10
3
(kg/m ) 998.2
(W/mK) 0.599
35
Highlights
Two novel shell-and-tube heat exchangers with louver baffles are proposed.
36